2. General Troubleshooting
2.1 Error Display (Indoor Unit)
When the indoor unit encounters a recognized error, the indicator light will flash in a corresponding series, the timer
display may turn on or begin flashing, and an error code will be displayed. These error codes are described in the
following table:
For Ceiling&floor type:
Operation
lamp
Timer
lamp
Defrosting
lamp
Alarm
lamp
Display
Error
Information
Solution
OFF
flflFlash
OFF
OFF
E2
Indoor room temperature sensor T1 is in open
circuit or has short circuited
Page 96
Flash
OFF
OFF
OFF
E3
Evaporator coil temperature sensor T2 is in open
circuit or has short circuited
Page 96
OFF
OFF
Flash
OFF
E4
Condenser coil temperature sensor T3 is in
open circuit or has short circuited (except for
18k/24k/36k cooling-only models)
Page 96
Flash
Flash
OFF
OFF
E7
Indoor unit EEPROM parameter error
Page 97
Flash
off
off
Flash
EC
Refrigerant leak detected
Page 99
OFF
OFF
OFF
Flash
E8
Water level alarm malfunction
Page 98
For A6 Duct type:
Operation
lamp
flashes
Timer lamp
Display
Error
Information
Solution
1 time
OFF
E0
Indoor unit EEPROM parameter error
Page 97
5 times
OFF
E4
Indoor room temperature sensor T1 is in open circuit or has
short circuited
Page 96
6 times
OFF
E5
Evaporator coil temperature sensor T2 is in open circuit or
has short circuited
Page 96
7 times
OFF
EC
Refrigerant leak detected
Page 99
8 times
OFF
EE
Water level alarm malfunction
Page 98
3 times
ON
F2
Condenser coil temperature sensor T3 is in open circuit or has
short circuited (except for 18k/24k/36k cooling-only models)
Page 96
11 times
ON
FA
Dual chips communication malfunction
-