Tr
oubleshooting
Page 82
For Super-slim cassette type:
Operation
lamp
Timer
lamp
Defrosting
lamp
Alarm
lamp
Display
Error
Information
Solution
OFF
flflFlash
OFF
OFF
E2
Indoor room temperature sensor T1 is in open
circuit or has short circuited
Page 96
Flash
OFF
OFF
OFF
E3
Evaporator coil temperature sensor T2 is in
open circuit or has short circuited
Page 96
OFF
OFF
Flash
OFF
E4
Condenser coil temperature sensor T3 is in
open circuit or has short circuited (except for
18k/24k/36k cooling-only models)
Page 96
Flash
Flash
OFF
OFF
E7
Indoor unit EEPROM parameter error
Page 97
OFF
OFF
OFF
Flash
E8
Water level alarm malfunction
Page 98
Flash
Flash
Flash
OFF
Ed
Protection of Low pressure (only for 48k
and 60k models)
Page 105
Flash
OFF
OFF
Flash
EC
Refrigerant leakage detection
Page 99
Flash
OFF
Flash
Flash
F0
Communication malfunction between main
PCB and up-down panel PCB
Page 100
OFF
Flash
Flash
Flash
F1
Up-down panel malfunction
Page 101
OFF
ON
Flash
Flash
F2
Up-down panel is not closed
-
For other errors:
The display board may show a garbled code or a code undefined by the service manual. Ensure that this code is not a
temperature reading.
Troubleshooting:
Test the unit using the remote control. If the unit does not respond to the remote, the indoor PCB requires replacement.
If the unit responds, the display board requires replacement.