Tr
oubleshooting
Page 83
2.2 Error Display (Outdoor Unit)
(excep for 18k/24k/36k single phase cooling-only models)
LED1
LED2
LED3
Error
Information
Solution
Flash
OFF
OFF
Phase sequence
Page 102
Flash
OFF
OFF
Lack of phase(A,B)
Page 103
OFF
OFF
OFF
Lack of phase(C)
Page 103
Flash
Flash
OFF
Protection of low pressure (only for 48k and 60k
models)
Page 105
off
OFF
Flash
Overload of current
Page 104
off
Flash
Flash
Open-circuit and short-circuit trouble of T3
Page 96
Off
Flash
Off
protection of high pressure (only for 48k and 60k
models)
Page 105
Flash
Flash
Flash
High temperature protection of condenser
Page 105
Summary of Contents for YEFE BZSM-MOW1 Series
Page 2: ......
Page 4: ......
Page 18: ...Specifications Page 14 YUFE60BYTM MS 1 R S C YUFE60BYSM MS 1 R ...