background image

YORK VRF Air-Conditioner IOM

 

z

Do not use flux when brazing refrigerant piping. 
Therefore, use the phosphor copper brazing filler 
metal (BCuP) which does not require flux. 

If chlorine based flux is used, it will cause pipe 
corrosion and contamination of refrigerant oil 

6.1 Connect the piping 

z

Be sure to use both a spanner and torque wrench 
together, as shown in Fig. 6, when connecting or 
disconnecting pipes to/from the unit. 
 

 

Fig. 6 Piping Connection 

z

Refer to Table 1 for the tightening torque. 

 

Table 1 

Pipe Diameter 

mm (inch) 

Tightening Torque 

(N

g

m) 

Ħ

6.35(1/4") 14

̚

17 

Ħ

9.53(3/8") 32.5

̚

40 

Ħ

12.7(1/2") 49.5

̚

60 

Ħ

15.88(5/8") 62

̚

75 

Ħ

19.05(3/4") 80

̚

95

 

Ħ

22.23(7/8") 100

̚

115

 

z

If no torque wrench is available, please follow the 
below method to do the installation.   

Using a wrench to tighten flare nuts causes the 
tightening torque to suddenly grow much tighter 
after a certain point. From that point, tighten the 
nut further by the appropriate angle listed in Table 
2. 

Table 2 

Pipe Diameter 

mm (inch) 

Further tightening 

angle 

Recommended arm length 

of toll 

Ħ

6.35(1/4") 60

 90

e

 

̚

150mm 

Ħ

9.53(3/8") 60

 90

e

 

̚

200mm 

Ħ

12.7(1/2") 45

 75

e

 

̚

250mm 

Ħ

15.88(5/8") 45

 75

e

 

̚

300mm 

Ħ

19.05(3/4") 30

60

e

 

̚

400mm 

Ħ

22.23(7/8") 30

60

e

 

̚

400mm 

 

Over tightening may damage the flare and cause 
leakage. 

 

6.2 AIR TIGHT TEST 

z

Air tight test should be done after the piping 
connection completed. 

z

Operation method: 

(a) Fill in dry nitrogen into the refrigerant piping 

and let the pressure slowly rise to 4.15MPa. 

(b) The specified pressure should be maintained 

for 10 minutes, and then soapy water or other 
foaming agent are applied to the connection 
positions, such as brazing seams, screwed 
joints ,etc. for leakage detection. 

(c) If it has leakage, then tighten or braze the 

leakage point. 

(d) After it has been confirmed that the piping 

does not leak, the dwelling test should be 
performed. Fill in the dry nitrogen again and 
let the pressure slowly rise to 4.15MPa. 

(e) The pressure needs to be maintained for 6 

hours and then record the pressure value 
through the manometer. 24 hours later, record 
the pressure again. 

(f) No pressure drop after 24 hours means it has 

no leakage. Otherwise, the leaking point must 
be found and mended. Then repeat the above 
(d) and (e) steps. 

 

 

z

Gas pressure is relevant to ambient temperature.
So temperature should be considered when judging 
the pressure variation. The relationship of pressure 
and temperature is shown below. 

2

1

1

273 1

273

t

P P

t

§

·

'   u

¨

¸

©

¹

       

2

correction

P

P

P

   '

 

 

P

'

— Pressure correction value         (bar) 

correction

P

— the correced pressure value      (bar) 

1

P

— 1

st

2

P

 record pressure                (bar) 

— 2

nd

1

t

 record pressure                              (bar) 

— 1

st

1

t

 record temperature                          (°C) 

—2

nd

 

 record temperature                          (°C) 

z

Do not connect indoor units with outdoor units in 
during the air test process. Otherwise, it may result 
in nitrogen gas emtering into the outdoor unit. 

6.3 Insulate the piping 

z

After checking it has no leakage, be sure to insulate 
the connection parts of both liquid and and gas 
pipe with sufficient thickness heat-resistant 

NO

TE

NO

TE

CAUTION 

CAUTION 

Summary of Contents for YDCC06-45

Page 1: ...YORKVRFAir Conditioner 250 12 YDCC IOM English YGF 0911 Installation Manual...

Page 2: ...TY CONSIDERATIONS 2 BEFORE INSTALLATION 2 3 SELECTING INSTALLATION SITE 2 4 BEFORE INSTALLATION 3 5 INDOOR UNIT INSTALLTION 4 6 REFRIGERANT PIPING WORK 4 7 DRAIN PIPING WORK 6 8 INSTALLING THE DUCT 7...

Page 3: ...the doors and windows immediately to ventilate the room thoroughly z Toxic gas may be produced if the refrigerant comes in contact with fire such as a fan heater stove or cooking device z Power off t...

Page 4: ...tdoor unit 3 SELECTING INSTALLATION SITE z If it has the possibility that the temperature and humidity inside the ceiling might exceed 30 C and RH80 please reinforce the insulation on the unit Use gla...

Page 5: ...0 mm2 z Also inspection opening for repairing should be installed in the ceiling right below the unit The size should be no smaller than the unit diameter BhE shown in the Fig 2 YDCC06 45 YDCC018 112...

Page 6: ...installed within the hanger bracket for fear of bolt rolling out this may result in danger 6 REFRIGERANT PIPING WORK z Execute insulation completely on both sides of the gas piping and the liquid pipi...

Page 7: ...nt piping and let the pressure slowly rise to 4 15MPa b The specified pressure should be maintained for 10 minutes and then soapy water or other foaming agent are applied to the connection positions s...

Page 8: ...Central Drain Pipe z For the indoor unit with pump drainage a Be sure the drain raising pipe height is within 700mm b Place the drain raising pipe vertically and make sure it is no further than 300mm...

Page 9: ...rding to the actual pressure drop of the air duct z Indoor unit ESP can be adjusted by changing the connection site of fan wiring in the control board For detail setting method of different indoor ESP...

Page 10: ...system while the other indoor units are controlled by another switch 10 4 Indoor unit field wiring z For detail indoor unit wiring see the Wring Diagram attached to the control box lid when laying the...

Page 11: ...oller can connect to max 4 indoor units Note indoor unit series type of A B C and D is determined by the specific letter in the bar code attached on the unit For example indoor unit YDCC C means C typ...

Page 12: ...721239 YDCC IOM English YGF 0911 NOTHING...

Reviews: