Fig. 10 Duct Connection 

z

Wrap both the inlet-side and outlet-side flange and 
the duct connection area with aluminium tape for 
something similar to prevent air escaping. 

z

Please attach an air filter inside the air passage on 
the inlet-side. (Use an air filter which duct 
collection efficiency (in a gravimetric technique) is 
higher than 50%) 

z

Be sure to insulate the duct to prevent condensate 
water from forming. (Material: glass wool or 
polyethylene foam, above 25mm thickness) 

 
 

z

Duct pressure drop of YDCC06~18/YDCC018~053 
indoor unit models cannot be higher than 30 Pa; 
YDCC25~45/YDCC066~115 indoor unit models 
cannot be higher than 80 Pa; 
YDCC50~60/YDCC140~175 indoor unit models 
cannot be higher than 100 Pa. 

z

The air outlet cannot be too high and be positioned 
at the place where it directly blows the people for a 
long period. 

z

To reduce vibration and noise, it is better to use
flexible connection to connect the air inlet and
outlet duct with indoor unit. 

9

SET THE ESP 

z

YDCC06~18/YDCC018~053 indoor unit models’ ESP 
(External Static Pressure) can be divided as 3 types 
– 0 Pa, 15 Pa and 30 Pa; 

YDCC25-45/YDCC066-115 indoor unit models’ ESP 
(External Static Pressure) can be divided as 3 types 
– 15 Pa, 40 Pa and 100 Pa; 
YDCC50~60/YDCC140~175 indoor unit models’ ESP 
(External Static Pressure) can be divided as 3 types 
– 15 Pa, 50 Pa and 100 Pa; 

Out factory state, YDCC indoor unit ESP is 15 Pa 
(default value). User can adjust the ESP according 
to the actual pressure drop of the air duct. 

z

Indoor unit ESP can be adjusted by changing the 
connection site of fan wiring in the control board. 
For detail setting method of different indoor ESP, 
please refer to the wiring diagram attached to the 
control box lid. 

10

ELECTRIC WIRING WORK 

10.1 General introduction 

z

Shut off the power before doing any work. 

z

All field supplied parts and materials and electric 
works must conform to local laws. 

z

All wiring works should be performed by specially 
qualified electricians. 

z

Install a wiring interrupter or ground-fault circuit 
interrupter for the power supply wiring. 

z

Be   

z

Be sure the air-conditioner is well grounded. Never 
connect the ground line with gas pipe, water pipe, 
lightning conductor or telephone lines. 

z

Do not turn on the power sully unless all the work 
has been done. 

z

Wiring of different thickness or diameter cannot be 
connected to one power supply wiring terminal. 

z

For wiring, please use the designated power supply 
wiring and connect firmly, then secure to prevent 
external pressure being exerted on the terminal 
board.

z

The terminal screw should not be tightened too 
hard or too loose. Too hard may damage the 
terminal board and too loose may result in bad 
connection and danger due to terminal board 
overheating.

10.2 Electrical parameters 

Indoor unit power supply and Max operation current 

Indoor Unit Model 

Power Supply 

Max Operation Current(A) 

BTU type 

kW type 

H0 type 

  (or Cooling Only) 

H2 type 

H4 type 

YDCC06

̚

09 YDCC018

̚

025 

220V

̚

 50Hz 

0.26 4.76  - 

YDCC12

̚

25 YDCC034

̚

066 

0.85 8.15 9.85 

YDCC30

̚

45 YDCC078

̚

115 

1.31 10.31 15.81 

YDCC50 YDCC140 

2.8 

YDCC60 YDCC175 

3.18 

 

NO

TE

CAUTION 

Summary of Contents for YDCC06-45

Page 1: ...YORKVRFAir Conditioner 250 12 YDCC IOM English YGF 0911 Installation Manual...

Page 2: ...TY CONSIDERATIONS 2 BEFORE INSTALLATION 2 3 SELECTING INSTALLATION SITE 2 4 BEFORE INSTALLATION 3 5 INDOOR UNIT INSTALLTION 4 6 REFRIGERANT PIPING WORK 4 7 DRAIN PIPING WORK 6 8 INSTALLING THE DUCT 7...

Page 3: ...the doors and windows immediately to ventilate the room thoroughly z Toxic gas may be produced if the refrigerant comes in contact with fire such as a fan heater stove or cooking device z Power off t...

Page 4: ...tdoor unit 3 SELECTING INSTALLATION SITE z If it has the possibility that the temperature and humidity inside the ceiling might exceed 30 C and RH80 please reinforce the insulation on the unit Use gla...

Page 5: ...0 mm2 z Also inspection opening for repairing should be installed in the ceiling right below the unit The size should be no smaller than the unit diameter BhE shown in the Fig 2 YDCC06 45 YDCC018 112...

Page 6: ...installed within the hanger bracket for fear of bolt rolling out this may result in danger 6 REFRIGERANT PIPING WORK z Execute insulation completely on both sides of the gas piping and the liquid pipi...

Page 7: ...nt piping and let the pressure slowly rise to 4 15MPa b The specified pressure should be maintained for 10 minutes and then soapy water or other foaming agent are applied to the connection positions s...

Page 8: ...Central Drain Pipe z For the indoor unit with pump drainage a Be sure the drain raising pipe height is within 700mm b Place the drain raising pipe vertically and make sure it is no further than 300mm...

Page 9: ...rding to the actual pressure drop of the air duct z Indoor unit ESP can be adjusted by changing the connection site of fan wiring in the control board For detail setting method of different indoor ESP...

Page 10: ...system while the other indoor units are controlled by another switch 10 4 Indoor unit field wiring z For detail indoor unit wiring see the Wring Diagram attached to the control box lid when laying the...

Page 11: ...oller can connect to max 4 indoor units Note indoor unit series type of A B C and D is determined by the specific letter in the bar code attached on the unit For example indoor unit YDCC C means C typ...

Page 12: ...721239 YDCC IOM English YGF 0911 NOTHING...

Reviews: