background image

5012886-YIM-B-0517

10

Johnson Controls Unitary Products

Refrigerant Mains

Line Sizing

When sizing refrigerant pipe for a split-system air conditioner, 
check the following: 

1.

Suction line pressure drop due to friction.

2.

Liquid line pressure drop due to friction.

3.

Suction line velocity for oil return.

4.

Liquid line pressure drop due to vertical rise. For certain 
piping arrangements, different sizes of suction line pipe 
may have to be used. The velocity of the refrigerant vapor 
must always be great enough to carry the oil back to the 
compressor.

5.

Evaporator Located Below Condenser

 - On a split 

system where the evaporator blower is located below the 
condenser, the suction line must be sized for both pressure 
drop and for oil return.

6.

Condenser Located Below Evaporator

 - When the 

condenser is located below the evaporator blower, the 
liquid line must be designed for the pressure drop due to 
both friction loss and vertical rise. If the pressure drop due 
to vertical rise and friction exceeds 60 psi, some refrigerant 
will flash before it reaches the thermal expansion valve.

Flash gas:

1.

Increases the liquid line pressure loss due to friction that in 
turn causes further flashing. 

2.

Reduces the capacity of the refrigerant control device 
which starves the evaporator. 

3.

Erodes the seat of the refrigerant control device. 

4.

Causes erratic control of the refrigerant entering the 
evaporator.

Take Adequate Precautions

Many service problems can be avoided by taking adequate 
precautions to provide an internally clean and dry system and 
by using procedures and materials that conform to established 
standards.

Use hard drawn copper tubing where no appreciable amount of 
bending around pipes or other obstructions is necessary. If soft 
copper is used, care should be taken to avoid sharp bends that 
may cause a restriction. Pack fiberglass insulation and a 
sealing material such as permagum around refrigerant lines 
where they penetrate a wall to reduce vibrations and to retain 
some flexibility.

Support all tubing at minimum intervals with suitable hangers, 
brackets or clamps.

Braze all copper-to-copper joints with Silfos-5 or equivalent 
brazing material. Do not use soft solder. Insulate all suction 
lines with a minimum of 1/2" ARMAFLEX or equivalent that 
meets local codes. Liquid lines exposed to direct sunlight and/
or high temperatures must also be insulated. Never solder 
suction and liquid lines together. They can be taped together for 
convenience and support purposes, but they must be 
completely insulated from each other.

The liquid and suction service ports on the condenser section 
permit leak testing, evacuation, and partial charging of the field 
piping and the evaporator without disturbing refrigerant stored 
in the condenser during initial installation.

Before beginning installation of the main lines, be sure that the 
evaporator section has not developed a leak in transit. Check 
pressure at the Schrader valve located on the header of each 
coil. If pressure still exists in the system, it can be assumed to 
be leak free. If pressure DOES NOT exist the section will need 
to be repaired before evacuation and charging is performed.

A filter-drier MUST be field-installed in the liquid line of every 
system to prevent dirt and moisture from damaging the system. 
Properly sized filter-driers are shipped with each condensing 
section.

NOTE: 

Installing a filter-drier does not eliminate the need for 
the proper evacuation of a system before it is charged.

A field-installed moisture indicating sight-glass should be 
installed in the liquid line(s) between the filter-drier and the 
evaporator coil. The moisture indicating sight-glass can be used 
to check for excess moisture in the system.

Both condenser and evaporator sections have copper sealing 
disks brazed over the end of liquid and suction connections. 
The temperature required to make or break a brazed joint is 
high enough to cause oxidation of the copper unless an inert 
atmosphere is provided.

NOTE: 

Dry nitrogen should flow through the system at all times 
when heat is being applied and until the joint has 

This Split-System (Air Condensing / Air Handling) unit is 
one component of an entire system. As such it requires 
specific application considerations with regard to the 
rest of the system (air handling unit, duct design, 
condensing unit, refrigerant piping and control scheme). 
Failure to properly apply this equipment with the rest of 
the system may result in premature failure and/or 
reduced performance / increased costs. Warranty 
coverage specifically excludes failures due to improper 
application and Unitary Products specifically disclaims 
any liability resulting from improper application.
 Please refer to the equipment Technical Guide, 
Installation Manual and the piping applications bulletin 
247077 or call the applications department for Unitary 
Products @ 1-877-UPG-SERV for guidance.

Summary of Contents for YD360 Series

Page 1: ...Unit 9 6 Unit Dimensions Inches 14 7 Piping And Electrical Connection Sizes 30 40 50T Inches 16 8 Electrical Power Knockout Sizes Inches 16 9 Smart Equipment UCB Details 23 LIST OF FIGURES 1 Corner We...

Page 2: ...50 Ton C00 Cooling Only Product Options AA None TA Technicoat Condenser Coil Installation Options A None 2 208 230 3 60 4 460 3 60 5 575 3 60 Configured Split Condenser Model Number Nomenclature A St...

Page 3: ...n the carrier s freight bill A separate request for inspection by the carrier s agent should be made in writing Improper installation may create a condition where the operation of the product could ca...

Page 4: ...em Scroll Tandem Scroll Quantity 2 2 2 Cooling Nominal Capacity Tons System 1 15 20 25 System 2 15 20 25 Capacity Stages System 1 2 2 2 System 2 2 2 2 SYSTEM DATA No Refrigeration Circuits 2 2 2 Sucti...

Page 5: ...ngth to support the unit The condensing unit must be mounted on level supports The supports can be channel iron beams or wooden beams treated to reduce deterioration Minimums of two 2 beams are requir...

Page 6: ...on of vibration Holes are provided in the base rails for bolting the unit to its foundation For ground level installations precautions should be taken to protect the unit from tampering and unauthoriz...

Page 7: ...of the unit When preparing to move the unit always determine the center of gravity see Table 3 and Figure 1 of the unit in order to equally distribute the weight Slings connected to the compressor end...

Page 8: ...to compressor replacement repairing refrigerant leaks replacing refrigerant components such as filter drier pressure switch metering device or coil Units are shipped with compressor mountings which ar...

Page 9: ...3 60 1 1 2 4 2 9 63 5 70 575 3 60 4 9 0 14 78 575 3 60 1 1 2 4 2 2 47 1 50 YD480 208 230 3 60 4 30 1 47 225 208 230 3 60 1 1 2 4 5 8 151 1 175 460 3 60 4 16 7 26 114 460 3 60 1 1 2 4 2 9 82 6 90 575 3...

Page 10: ...emperatures must also be insulated Never solder suction and liquid lines together They can be taped together for convenience and support purposes but they must be completely insulated from each other...

Page 11: ...ctions of the main lines Connect the main liquid line to the liquid line connection on the evaporator unit while maintaining a flow of nitrogen Make the suction line connection at the evaporator and r...

Page 12: ...Line Solenoid Wiring NOTE For applications on airhandlers evaporator DX coils other than ND360 600 certified matchups liquid line solenoids may be required for proper operation and refrigerant system...

Page 13: ...On non ND models isolation relays must be installed to avoid overloading on 75 VA transformer on condensing unit Non ND units may not include any or all of the components required to wire the unit Use...

Page 14: ...4 Johnson Controls Unitary Products Figure 6 YD Unit Dimensions Table 6 Unit Dimensions Inches MODEL A B C D E F G H YD360 128 5 88 5 37 5 41 8 40 0 46 1 37 1 23 6 YD480 128 5 88 5 57 7 41 8 40 0 46 1...

Page 15: ...183 2 313 88 140 22 358 20 858 19 358 37 518 12 878 9 628 5012886 YIM B 0517 Johnson Controls Unitary Products 15 Figure 7 30 Ton Power And Control Wiring Connections Figure 8 40 50 Ton Power And Cont...

Page 16: ...NTRY SIZE SUCTION LINE SYS 1 1 5 8 OD LIQUID LINE SYS 1 7 8 OD SUCTION LINE SYS 2 1 5 8 OD LIQUID LINE SYS 2 7 8 OD POWER WIRING KNOCKOUT SEE TABLE 8 CONTROL WIRING 7 8 HOLE Table 8 Electrical Power K...

Page 17: ...ent clearances been provided 2 Has all foreign matter been removed from the interior of the unit tools construction or shipping materials etc 3 Have the condenser fans been rotated manually to check f...

Page 18: ...minute If it fails to close the unit will shut down the associated compressor and begin an ASCD If the call for cool is still present at the end of the anti short cycle time delaying the control boar...

Page 19: ...of System 2 When the LPS of UCB 2 falls below its cut out point the PR2 relay brings on the 3LLS Solenoid allowing refrigerant in system 2 to return flow to the compressor for normal mechanical coolin...

Page 20: ...enance consists of changing or cleaning filters and general cleaning of the outdoor coil MOTORS Outdoor fan motors are permanently lubricated and require no maintenance OUTDOOR COIL Dirt should not be...

Page 21: ...cursor is on the top Status line hit the ENTER button This action steps the LCD display into the status mode Hit ENTER to view the status menu Press Enter Step 2 Scroll down to DVent Mode This is the...

Page 22: ...CANCEL JOY C PWR 7 7 77 Clg Engaged LeadLag Engaged Press Enter Joy Stick Down 2 Step 6 By toggling down twice the screen reaches the ClgOcc SP screen or Cooling Occupied Set Point ENTER CANCEL JOY C...

Page 23: ...mostat connection strip C and indoor blower VFD pin C 24V 24 VAC 75 VA transformer hot Powers the UCB microprocessor connects through circuit trace to the SD 24 terminal SD 24 24 VAC hot out for facto...

Page 24: ...hing in series Unit wiring harness jumper plug for factory shutdown accessories must be removed if the switching of field added external accessories for unit shutdown are wired between thermo stat con...

Page 25: ...ut from 10K 77 F Type III negative temperature coefficient thermistor Input required for 2 compressor heat pump units not required for 2 compressor A C units not active for 1 compressor units 3 625 VD...

Page 26: ...no input within 5 minutes from initiation of H1 output initiates an Ignition Failure alarm input for longer than 5 minutes without H1 output initiates a Gas Valve Mis wire alarm Pin Cooling and fan o...

Page 27: ...put is needed input must be present to allow FAN output and unit operation One FAN OVR trip lasting longer than 5 minutes or three FAN OVR trips in a two hour period cause a Fan Overload Lockout and u...

Page 28: ...munication circuit COM Common for the FC Field Connected BUS BACnet MSTP communication circuit Negative of the VDC FC bus BACnet MSTP communication circuit SHLD Shield for the FC Field Connected BUS B...

Page 29: ...with the TXV s left to the factory setting If the TXV s have been adjusted in the field the charging chart may no longer apply Outdoor Air Entering Condenser F 300 350 400 450 500 550 600 120 130 140...

Page 30: ...scharge Pressure psi Suction Pressure psi Charging Curves 50 Ton 115 105 95 85 65 1 Make sure that all condenser fans are running when charging 2 This chart is applicable to unit with the TXV s left t...

Page 31: ...5012886 YIM B 0517 Johnson Controls Unitary Products 31 Typical Wiring Diagrams Figure 17 Typical 208 230 Volt YD360 480 600 Condensing Unit Wiring Diagram...

Page 32: ...5012886 YIM B 0517 32 Johnson Controls Unitary Products Typical Wiring Diagrams Figure 18 Typical 460 575 Volt YD360 480 600 Condensing Unit Wiring Diagram...

Page 33: ...ocedures are followed and checks are made at initial start up This confidence is supported by the 30 day dealer protection coverage portion of our standard warranty policy which states that Johnson Co...

Page 34: ...he equipment If the system is a VAV system the CFM will be the airflow when the remote VAV boxes are in the full open position and the frequency drive is operating at 60 HZ Do not proceed with the equ...

Page 35: ...ystem 2 Is Condenser below Evaporator Yes No Yes No Total Line Length end to end _______ Ft _______ Ft Vertical Lift in Ft _______ Ft _______ Ft Vertical Fall in Ft _______ Ft _______ Ft Number of Elb...

Page 36: ...t or change required to obtain the correct airflow Was it necessary to increase of decrease the airflow to meet the design conditions If the motor pulley size was changed measure the outside diameters...

Page 37: ...hird if equipped Fourth if equipped Heat Pump 1st Stage Outside air temperature ________________ db F ________________ wb F ________________ RH Return Air Temperature ________________ db F ___________...

Page 38: ..._______________________________ ________________________________________________________________________________________________________ _______________________________________________________________...

Reviews: