York YD A Operating & Maintenance Download Page 11

JOHNSON CONTROLS

11

SECTION 1 – DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION

FORM 160.69-O2 

ISSUE DATE: 9/30/2020

1

Level Control Setpoint. This ramp allows the level to 

go from the present level to the Level Control Setpoint 

over a period programmed as the 

Ramp Up Time 

Setpoint

. After the Ramp Up time has elapsed, the 

level is controlled to the Level Control Setpoint. 
After the Chiller Pulldown Period ends, if the Lag 

compressor has not been brought on line during the 

Chiller Pulldown Period, the Chiller Steady State 

Period begins.  During this period, the Pre-rotation 

Vanes are modulated to maintain the Leaving Chilled 

Liquid Temperature Setpoint. In order to determine if 

the Lead compressor is meeting the load demand dur-

ing this period, the Leaving Chilled Liquid Tempera-

ture minus the Leaving Chilled Liquid Temperature 

Setpoint (Temperature Differential) is monitored. If 

the Temperature Differential exceeds the Maximum 

Delta T Setpoint (1.0 ºF to 5.0 ºF; default 1.0) for a 

period equal to the Maximum Delta T Time Setpoint (1 

to 20 minutes; default 5) and the Chiller Current Limit 

Setpoint is above 50%, the Lag compressor is brought 

on line. 
With only one compressor running, the compressor 

Variable Geometry Diffuser is modulated according to 

the stall and surge activity.
When bringing the Lag Compressor on line, it enters 

the Prelube period. If a high head condition exists, the 

Lead compressor’s Pre-rotation vanes are driven closed 

as described in “Lag Start with High Head” below. The 

Refrigerant Level Control Lag Start mode is initiated as 

described below under “Condenser Refrigerant Level 

Control Lag Start”. During the Lag Prelube, all normal 

Prelube functions are performed except the Oil Pres-

sure Transducer Offset calibration is not performed. 

The offset calculation from the Lead compressor start 

is used. The Prelube time is fixed at 50 seconds. At the 

completion of the Prelube, the Lag compressor motor 

is started and after a 50 second delay, the Lag com-

pressor Discharge Valve is opened (If it doesn’t fully 

open within 40 seconds as indicated by the Discharge 

Valve Limit Switch, a Safety shutdown is performed 

on both compressors and “Discharge #X – Valve Not 

Opened” is displayed). After the Discharge Valve has 

fully opened, the Lag compressor Pre- rotation Vanes 

are modulated to follow Lead motor current. 
Meanwhile, the Lead compressor Pre-rotation Vanes 

have been modulated to maintain the Leaving Chilled 

Liquid Temperature setpoint (unless “Lag Start with 

High Head” was performed). When the Lag motor 

current is 5% of the Lead motor current, the 

run time of the compressors are evaluated to deter-

mine which should be the Lead compressor (The one 

with the least amount of run time is identified as the 

Lead compressor) and if a “Lag Start with High Head” 

was performed, the Lead Pre-rotation vanes are now 

allowed to open and control per the Leaving Chilled 

Liquid Temperature Setpoint. Two minutes after the 

Lag compressor Discharge Valve has opened, the Con-

denser Refrigerant Control ramp-up period begins as 

Described below under “Condenser Refrigerant Level 

Control – Lag Start”.  While both compressors are run-

ning, the Variable Geometry Diffusers are modulated 

according to the stall activity and Pre-rotation Vanes 

position. There is no VGD response to surge activity.
When both compressors have been brought online, 

they will be run for at least 30 minutes (unless the anti-

recycle feature has been disabled, a fault is detected or 

a Local or Remote stop is applied). After the 30 minute 

waiting period, a Soft Shutdown (as described below) 

will be performed on the Lag compressor if the Lead 

compressor motor current goes below the 

Low Load 

Setpoint

 (20% to 60%; default 45%) for a period equal 

to the 

Low Load Time Setpoint

 (1 to 20 minutes; de-

fault 5).

Lag Compressor Start with High Head

(Software version C.MLM.11.02.xxx and later or 

C.OPT.11.02.300 and later)
When operating at high head conditions, surges can 

occur while going from one to two compressor opera-

tion. A high head condition is detected by measuring 

the Delta P/P [(Condenser pressure – Evaporator pres-

sure) / Evaporator pressure] and comparing it to the 

HIGH HEAD DP/P LIMIT Setpoint. By closing the 

Lead compressor’s pre-rotation vanes during a Lag 

compressor start when a high head condition is pres-

ent, surge conditions can be minimized.
With the Lead compressor running and it is determined 

the Lag compressor is required to run, the Delta P/P 

is measured. If it is > the HIGH HEAD DP/P LIMIT 

Setpoint, a close signal is applied to the Lead compres-

sor’s pre-rotation vanes coincident with the start of the 

Lag Compressor’s Pre-lube. They will be allowed to 

open when all the following conditions are met: the 

lag compressor is running, the Lag Discharge Valve is 

open, the difference between the Lead and Lag motor 

currents is < 5%.

Summary of Contents for YD A

Page 1: ...MODEL YD STYLE A B WITH OPTIVIEW CONTROL CENTER AND ELECTRO MECHANICAL STARTER COOLING ONLY CENTRIFUGAL LIQUID CHILLERS OPERATING MAINTENANCE Supersedes 160 69 O2 912 Form 160 69 O2 920 Issue Date Sep...

Page 2: ...ls This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are used in...

Page 3: ...equipment If there is any question regarding the applicability of these documents rig ging lifting and operating service personnel should verify whether the equipment has been modified and if current...

Page 4: ...W CB 5CX DA 5DA DB 5DB DC 5DC DE 5DE DF 5DF DG 5DG DH 5DH DJ 5DJ DK 5DK DL 5DL NOMENCLATURE YD XF XA J2 CA A B or C POWERSUPPLY for 60 Hz 5 for 50 Hz DESIGN LEVEL MODEL CONDENSER CODE XA XB XC XD YA Y...

Page 5: ...System 27 Prolonged Shutdown 27 SECTION 3 SYSTEM COMPONENTS DESCRIPTION 29 General 29 Compressor 29 Capacity Control 29 Compressor Lubrication System 29 Oil Pump 30 Oil Heater 32 Motor Driveline 32 H...

Page 6: ...ing 45 Tube Cleaning Procedures 45 Acid Cleaning Of Tubes 46 Commercial Acid Cleaning 46 Testing For Evaporator And Condenser Tube Leaks 46 Compressor 47 Electrical Controls 47 SECTION 7 PREVENTIVE MA...

Page 7: ...GURE 6 Schematic Drawing YD Compressor Lubrication System 31 FIGURE 7 Oil Return System 35 FIGURE 8 Charging Oil Reservoir With Oil 36 FIGURE 9 Evacuation Of Chiller 39 FIGURE 10 Saturation Curve 41 F...

Page 8: ...JOHNSON CONTROLS 8 FORM 160 69 O2 ISSUE DATE 9 30 2020 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 9: ...y is equipped with a potentiometer to provide vane posi tion A calibration procedure assures displayed posi tion accuracy The vanes can be manually controlled Each compressor also has a Discharge Temp...

Page 10: ...features are detailed separately be low If equipped with the compressor Variable Geometry Diffuser VGD the chiller is started with the VGD in the fully open position Upon receipt of a chiller start s...

Page 11: ...llow Lead motor current Meanwhile the Lead compressor Pre rotation Vanes have been modulated to maintain the Leaving Chilled Liquid Temperature setpoint unless Lag Start with High Head was performed W...

Page 12: ...Con trol Valve while bringing on the Lead compressor It displays Lag Start when performing the Refrigerant Level Control Lag Start mode while starting the Lag compressor The Override Time Remaining d...

Page 13: ...lowed to operate all the way up to its full load amps of 800 Amps because the total chiller current is being limited to 1120 Amps Compressor Lockout The COMPRESSOR LOCKOUT Setpoint available on the Ca...

Page 14: ...e rotation Vanes are driven closed When the Vanes have fully closed or 210 seconds have elapsed whichever occurs first the Discharge Valve is then driven closed When the Discharge Valve has fully clos...

Page 15: ...or Discharge Valve Electro Mechanical Starter Chiller Start Sequence Auto zero the 3 Oil Pressure Transducers Pre Lube cycle Lead Compressor Normal Sequence Extended prelube switch applies only to lea...

Page 16: ...oint Timer Is Lag Compressor Ready to Start Yes Yes Yes NO No No Pre Lube Lag Oil Pump Don t auto zero oil pressure transducers No No 2n Trend rate of pull down on startup to decide on d compr Antirec...

Page 17: ...ontrol Lag Compr PRVs are controlled to follow motor current of Lead System Run Two Compressors 40 Seconds Alarm Fault No Delay 50 seconds To allow motor starting transition time Are Motor Currents Eq...

Page 18: ...Lag Compressor Discharge Valve Lag Compr Disch Valve Closed Stop Lag Compressor Motor Drive Lag Compressor vanes closed Post Lube Run Time Lag Compressor Yes No Yes 1 Compr Running Restart 2nd compr i...

Page 19: ...lves on both compressors Stop both compressor motors Post Lube Run time both compr oil pumps Energize Oil Heater 1 Compressor Running from Page 1 or 4 Chiller normal or cycling stop signal Stop Lead c...

Page 20: ...ult Stop manual or auto restart Stop both compressors simultaneously Chiller Fault Condition Post Lube Run time both compr oil pumps Energize Oil Heater 1 Compressor Running from Page 1 or 4 Chiller F...

Page 21: ...ng LChWT Lag Compressor following current of Lead No Yes No Yes Close Compressor Pre rotation Vane Motors No Have of Total Surge Counts Exceeded the allowed within time period setting Stop and Lockout...

Page 22: ...JOHNSON CONTROLS 22 FORM 160 69 O2 ISSUE DATE 9 30 2020 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 23: ...IR Proper operating oil level During operation the oil level should fall to the Operating Range identified on the vertical oil level indicator label See Figure 3 on page 23 If the oil level during ope...

Page 24: ...initiated and will run for 30 minutes after the compressor starts If the chiller shuts down during this period of time it cannot be started until the timer completes the 30 minute cycle 4 The chilled...

Page 25: ...hilled water temperature Cooling tower fan cycling will normally provide adequate control of the entering condenser water temperature on most instal lations OPERATING LOG SHEET A permanent daily recor...

Page 26: ...procedure the operator will avoid serious operating difficulty The following list of inspections and procedures should be used as a guide Daily 1 Check OptiView Control Center displays 2 If the compre...

Page 27: ...eously with the oil pump The actual water pump con tact operation is dependent upon the position of Microboard jumper J54 3 Open the switch to the cooling tower fan motors if used 4 The compressor sum...

Page 28: ...JOHNSON CONTROLS 28 FORM 160 69 O2 ISSUE DATE 9 30 2020 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 29: ...ssor is able to handle the load more efficiently COMPRESSOR LUBRICATION SYSTEM The chiller lubrication system consists of the oil pump oil filter oil cooler and all interconnecting oil piping and pass...

Page 30: ...e oil pump should operate at all times during chiller operation On shutdown of the system for any reason the oil pump operates and continues to run for 150 seconds The system cannot restart during tha...

Page 31: ...NTROLS 31 SECTION 3 SYSTEM COMPONENTS DESCRIPTION FORM 160 69 O2 ISSUE DATE 9 30 2020 3 LOW SPEED GEAR REAR BEARING DOUBLE BELLOWS SHAFT SEAL Figure 6 SCHEMATIC DRAWING YD COMPRESSOR LUBRICATION SYSTE...

Page 32: ...ors or suction baffles are located above the tube bundle to prevent liquid refrig erant carryover into the compressor A 2 liquid level sight glass is located on the side of the shell to aid in determi...

Page 33: ...the refrigerant in this system must be performed by a qualified service technician OPTIONAL HOT GAS BYPASS Hot gas bypass is optional and is used to eliminate compressor surge during light load or hig...

Page 34: ...JOHNSON CONTROLS 34 FORM 160 69 O2 ISSUE DATE 9 30 2020 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 35: ...To change the dehydrator use the following procedure 1 Shut the stop valves on the condenser gas line oil return line to rotor support and inlet end of the dehydrator 2 Remove the dehydrator Refer to...

Page 36: ...il and connect the pump discharge connection to the oil charging valve A located on the remote oil reservoir cover plate See Figure 8 on page 36 Do not tighten the connection at the charging valve unt...

Page 37: ...roblem Remove obstruction Temperature difference between leav ing chilled water and refrigerant in evaporator greater than normal with high discharge temperature Evaporator tubes dirty or restricted C...

Page 38: ...Inspect and replace worn parts Partially blocked oil supply inlet Check oil inlet for blockage SYMPTOM OIL PRESSURE GRADUALLY DECREASES NOTED BY OBSERVATION OF DAILY LOG SHEETS When oil pump VSD frequ...

Page 39: ...leaks too small to be found by the soap test To test with R 22 proceed as follows 1 With no pressure in the system charge R 22 gas into the system through the charging valve to a pressure of 2 PSIG 14...

Page 40: ...pressure of 5 mm Hg is reached See Table 2 on page 40 for corre sponding values of pressure 4 To improve evacuation circulate hot water not to exceed 125 F 51 7 C through the evaporator and condenser...

Page 41: ...n pressure tested and found to be tight prior to evacuation then the saturation tempera ture recordings should follow a curve similar to the typical saturation curve shown as Figure 10 on page 41 The...

Page 42: ...rant is connected or changed Refrigerant may be furnished in cylinders contain ing either 30 50 125 or 1750 lbs 207 345 862 or 12 066 kg of refrigerant R 134A EVAPORATOR CODE LBS KG S FB 11022 5000 FC...

Page 43: ...rigerant level should be observed and the level re corded after initial charging HANDLING REFRIGERANT FOR DISMANTLING AND REPAIRS If it becomes necessary to open any part of the refriger ant system fo...

Page 44: ...RM 160 69 O2 ISSUE DATE 9 30 2020 SECTION 6 MAINTENANCE LD00476 Figure 12 MOTOR STARTER TEMPERATURE AND INSULATION RESISTANCES Minimum Insulation Resistance vs Temperature per IEEE Std 43 Open Motors...

Page 45: ...radual drop off in cooling capacity can also be caused by a gradual leak of refrigerant from the system or by a combination of fouled tubes and shortage of refrigerant charge An excessive quantity of...

Page 46: ...ten at each section of tubes for a hissing sound that would indicate gas leakage This will assist in locating the section of tubes to be further investigated If the probable location of the leaky tube...

Page 47: ...passages or dirty oil fil ters If the unit is shutting down on HOT High Oil Temperature or Low Oil Pressure OP change the oil filter element Examine the oil filter element for the presence of aluminu...

Page 48: ...JOHNSON CONTROLS 48 FORM 160 69 O2 ISSUE DATE 9 30 2020 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 49: ...tion Grease fittings are not supplied and bearings are designed for long life under standard conditions Frames 284T thru 587UZ are furnished with double shielded or open ball or roller bearings It is...

Page 50: ...e to the benefit of the user to provide for proper water treatment to provide for a longer and more economical life of the equipment The following recommendation should be followed in determining the...

Page 51: ...lsius multiply by 5 9 or 0 5556 Example 10 0 F range x 0 5556 5 6 C range Table 5 SI METRIC CONVERSION MEASUREMENT MULTIPLY ENGLISH UNIT BY FACTOR TO OBTAIN METRIC UNIT Capacity Tons Refrigerant Effec...

Page 52: ...ennsylvania USA 17349 1 800 524 1330 Subject to change without notice Printed in USA Copyright by Johnson Controls 2020 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 69 O2 920 Issue Date Septem...

Reviews: