JOHNSON CONTROLS

FORM 115.20-NOM6 (1106)

INSTALLATION

RECEIVING

Material in this shipment has been inspected at the 

factory and released to the transportation agency in 

good condition. When received, a visual inspection of 

all cartons should be made immediately. Any evidence 

of rough handling or apparent damage should be noted 

on the delivery receipt and the material inspected in 

the presence of the carrier’s representative.

STORAGE

If the equipment is not to be immediately installed, 

store it in a dry location with the motor protected 

against moisture, dust, corrosion and physical damage.  

If units are to be stored for six months or longer, 

see 

long term storage requirements (Form 50.20-NM3).

DESCRIPTION

The YCW  models  are  available  as  2-pipe  cooling 

(YCW), 2-pipe cooling with electric heat (YCWE) 

and a 4-pipe heating/cooling (YCW-HW). All units are 

provided with a 3-speed fan control in the control box 

in the fan section (left side), with 24v access on the top 

panel, left. Manual and auto changeover thermostats 

and the T200 auto speed control thermostats can be 

used with this unit.  Twenty-four volt (24 v) power is 

provided in the unit for thermostat operation.

The 2-pipe cooling unit is provided with a single coil 

with connections on the top panel, right side.

The  2-pipe  cooling  with  electric  heat  is  provided 

with a single chilled water coil and electric heat ele-

ments; coil connections are on the top panel, right 

side; electrical connections are on the top panel, left 

side and the units are provided with a disconnect on 

the front panel.

The 4-pipe heating/cooling unit is provided with 2 

coils with single end sheets – cooling connections are 

on the top panel, right side and the hot water connec-

tions are on the top panel, middle front. 

This unit is designed to be installed vertically in the 

upflow position and can be installed on a closet plat-

If damage is found, a claim should be 

filed against the carrier immediately.

form (platform not provided), hung on a closet wall 

(use wall hanging kit option) or recessed in a wall 

between wall studs (use front panel kit option).

 

FEATURES

Non-corrosive drain pan, installed in sloped position, 

¾” female primary and secondary connections acces-

sible from either side or bottom.

Filters provided, are 1” throwaway accessible from 

the front.

Coils  and  fan  motor/blower  assemblies  accessible 

from the front, when installed with the optional front 

panel assembly. 

Front air return standard, optional bottom return avail-

able but requires bottom return option.

Options available are thermostats, wall front panels, 

condensate pan overflow switch, closet hanger bracket 

kit, bottom return air kit and chilled water coil valve 

packages.  Consult  applications  group 

@

  717-771-

7073 for details on ordering and availability of these 

options.

Cabinet is fully insulated with 1” coated fiberglass 

panels.

All units have 0” clearance to combustible surfaces, 

so the units can be installed against wall studs and 

drywall.

CLEARANCES

Clearance  required  in  front  of  the  unit  to  provide 

access to coils, electrical controls and motor/blower 

assembly. This clearance should be equal to the depth 

of the cabinet.

MOUNTING - YCW UNIT STYLE

Recessed In Wall

All units must be installed level to insure proper drain-

age and operation.

1.  Frame the unit as required so the front panel 

of the wall unit will be flush with the drywall 

surface when installed 

(see Fig. 3).

Summary of Contents for YCW

Page 1: ...mance and or a possible hazardous safety condition to service personnel and occupants Company employees and or contractors are not authorized to waive this warning Notes 1 For proper operation control valve must be normally closed 2 Aquastats provided where required 3 Electric Heat is available as an option MODELS YCW SERIES YCW Series 2 pipe 4 pipe or 2 pipe cooling with electric heat LD11554 LD1...

Page 2: ...HILLED WATER LINES 5 8 OD COPPER STUBOUTS HOT WATER RETURN HOT WATER SUPPLY FIG 1 UNIT NOMENCLATURE LD11557A LD11698A CABINET DIMENSIONS INCHES A B C D E F FILTER SIZE COIL CONN OD SWEAT HW CW YCW 22 1 8 15 1 8 40 14 10 1 2 3 5 8 18 X 18 5 8 YCW HW 22 1 8 15 1 8 43 18 12 1 2 3 5 8 18 X 18 5 8 5 8 YCWE 22 1 8 15 1 8 40 14 10 1 2 3 5 8 18 X 18 5 8 10 YCW 31 CFM 100 s 3 4 6 8 10 12 Unit Style YCW 2 p...

Page 3: ...provided with 2 coils with single end sheets cooling connections are on the top panel right side and the hot water connec tions are on the top panel middle front This unit is designed to be installed vertically in the upflow position and can be installed on a closet plat If damage is found a claim should be filed against the carrier immediately form platform not provided hung on a closet wall use wa...

Page 4: ... POWER SUPPLY WIRING WALL PANEL FRAME HOT WATER OUTLET HOT WATER INLET DRY WALL 2 X 4 WALL STUD CW UNITS CHILLED WATER CONNECTION Note Front edge of unit to be flush with dry wall CROSS MEMBER ON EDGE 2 X 4 WALL STUD WALL PANEL FRAME SCREW DETAIL OF WALL PANEL FRAME INSTALLATION DRY WALL LD11695A TABLE 1 DRYWALL OPENINGS MODEL NUMBER DRYWALL CUTOUT DIM HT x WD 3YWC 28 x 42 4YWC 28 x 50 6YWC 28 x 5...

Page 5: ...standard 120 volt power wired to a dis connect terminal block and a ground lug Fan motor hi med and low speed leads are wired to the control board There may be an unused motor lead from the motor its needs to be capped off The board is also wired to handle either 24v or 120v control wiring To use 24v remove jumpers on the control board For your 24v hot water control valve wire it in series with th...

Page 6: ... N A N A N A N A N A 2 2 1 5 9 4 8 3 12 11 15 15 3 3 2 3 13 6 11 9 17 15 20 15 4 4 3 0 17 8 15 5 23 20 25 20 5 5 3 8 21 9 19 1 28 24 30 25 6 6 4 5 26 1 22 7 33 29 35 30 8CWE 0 0 0 0 1 7 N A N A N A N A N A 3 3 2 3 14 2 12 5 18 16 20 20 4 4 3 0 18 4 16 1 23 21 25 25 5 5 3 8 22 5 19 7 29 25 30 25 6 6 4 5 26 7 23 5 34 30 35 30 8 8 6 0 35 0 30 5 44 39 50 40 10CWE 0 0 0 0 2 7 N A N A N A N A N A 3 3 2 ...

Page 7: ...eringtobronzeorbrass heatthepiping while in the socket cup and begin introducing the solder when the flux boils rapidly Avoid direct flame into the solder joint Heat can only be applied to the cup of the valve body for a minimal time before damage occurs even with the use of wet rags Avoid rapid quenching of solder joints as this will produce joints of inferior quality Connect all piping per accepte...

Page 8: ...ure exists at the drain pan and a minimum trap of 1 1 2 must be provided in the drain line to assure proper drainage Drain connections primary and secondary are 3 4 MPT see Fig 5 for details On units with plastic drain pans the drain connections must be made hand tight only INSTALLATION FIG 5 CWE SERIES WALL CLOSET FAN COILS Chilled Water with Electric Heat CONDENSATE DRAIN CONNECTIONS With drain ...

Page 9: ...C O thermostat and the TB3 3 TB2 5 jumper is in place the fan will con tinue to operate at the fan speed selected Removing the jumper will cause the fan to shut down when the thermostat is satisfied When using the T200 thermostat the stat will auto matically regulate the fan speed based on the differ ence between the space temp and setpoint 4 F off setpoint the fan will run HI 3 F off setpoint the ...

Page 10: ...e the air and heating capacities of the unit When the filters are excessively dirty the unit heating capacity will be so reduced that it is in effective for heating the room When a room fails to heat always check the filters To ensure proper maintenance of the filters it is best to follow an organized maintenance procedure The following one is recommended Divide the total number of units on the job i...

Page 11: ...11 JOHNSON CONTROLS FORM 115 20 NOM6 1106 This Page Intentionally Left Blank ...

Page 12: ...ture from accumulating in the bearings See Form 50 20 NM3 Long Term Storage Installer has cleaned out interior Ensure drain pan free from foreign material Ensure air filters are clean installed properly and secured Use the directional arrows or other information on the filter to determine the proper flow direction INSTALL CHECKLIST Equipment received as ordered Unit checked for damage interior and ex...

Reviews: