background image

JOHNSON CONTROLS

4

FORM 115.20-NOM6 (1106)

INSTALLATION

2.  Frame  around  the  perimeter  of  the  unit  as 

required for securing the drywall. 

See Table 1 

below for drywall openings.

3.  Mount the unit in its permanent location, making 

sure it is level to insure proper drainage and 

operation (two 1/2” holes have been provided 

on each end of the unit for securing the unit to 

the wall studs).

4.  After the drywall has been installed, recheck to 

make sure the unit’s front panel is flush with the 

exterior drywall surface. Shimming of the unit 

may be required to get a seal between the unit 

and panel.

FIG. 3 – CW-HW RECESSED WALL and CLOSET 

MOUNTING

VERTICAL 2X 4
WALL STUDS

CLOSET MOUNT:
BRACKET
PLACEMENT
FOR HANGING

MOUNT UNIT
FLUSH WITH
DRY WALL (1/2"
MIN. IN FRONT
OF WALL STUD)

LEAVE SUFFICIENT SPACE
FOR DRAIN PIPING 10" TO 12"
MIN. RECOMMENDED

ATTACH UNIT TO FRAMING

USING SIX SCREWS/NAILS

IN CABINET LOCATIONS

SHOWN

CROSS MEMBER - TOP &

BOTTOM (PLACE UPPER CROSS

MEMBER 3" ABOVE UC UNIT)

SUPPORT FRAMING

RECESSED WALL UNIT TOP VIEW

THERMOSTAT

WIRING

POWER SUPPLY

WIRING

WALL PANEL FRAME

HOT

WATER

OUTLET

HOT

WATER

INLET

DRY WALL

2 X 4 WALL
STUD

CW UNITS:
CHILLED WATER
CONNECTION

Note: Front edge of unit to
be flush with dry wall.

CROSS MEMBER
(ON EDGE)

2 X 4 WALL STUD

WALL PANEL FRAME

SCREW

DETAIL OF WALL PANEL FRAME INSTALLATION

DRY WALL

LD11695A

TABLE 1 - DRYWALL OPENINGS

MODEL NUMBER

DRYWALL CUTOUT DIM

HT x WD

3YWC

28 x 42

4YWC

28 x 50

6YWC

28 x 58

8YWC

28 x 66

10YWC

28 x 74

12YWC

28 x 82

5.  Install the wall panel to the front of the unit using 

the 1/4-20 x 1-1/2” long, painted, Phillips head 

screws (four on unit sizes 3, 4, 6 and 8; six on 

unit sizes 10 and 12) (1/4” cage nuts are located 

in the slotted front panel of the unit). 

6.  Remove the lower return air grille to get access 

to the filter.

7. 

See Fig. 2 for unit details and dimensions.

Hung on a Closet Wall

Unit can be mounted in a closet using the bracket 

support option 90PK3.

These brackets mount to the top, back of the cabinet. 

See Fig 3 for location.

The unit should be isolated from the wall to be sure 

sound is not transferred from the unit to the wall.

Platform Mounted in a Closet

Unit can be set on a platform (provided by others) in 

a closet.

Be sure to allow for sufficient space below the platform 

for drain piping.

Summary of Contents for YCW

Page 1: ...mance and or a possible hazardous safety condition to service personnel and occupants Company employees and or contractors are not authorized to waive this warning Notes 1 For proper operation control valve must be normally closed 2 Aquastats provided where required 3 Electric Heat is available as an option MODELS YCW SERIES YCW Series 2 pipe 4 pipe or 2 pipe cooling with electric heat LD11554 LD1...

Page 2: ...HILLED WATER LINES 5 8 OD COPPER STUBOUTS HOT WATER RETURN HOT WATER SUPPLY FIG 1 UNIT NOMENCLATURE LD11557A LD11698A CABINET DIMENSIONS INCHES A B C D E F FILTER SIZE COIL CONN OD SWEAT HW CW YCW 22 1 8 15 1 8 40 14 10 1 2 3 5 8 18 X 18 5 8 YCW HW 22 1 8 15 1 8 43 18 12 1 2 3 5 8 18 X 18 5 8 5 8 YCWE 22 1 8 15 1 8 40 14 10 1 2 3 5 8 18 X 18 5 8 10 YCW 31 CFM 100 s 3 4 6 8 10 12 Unit Style YCW 2 p...

Page 3: ...provided with 2 coils with single end sheets cooling connections are on the top panel right side and the hot water connec tions are on the top panel middle front This unit is designed to be installed vertically in the upflow position and can be installed on a closet plat If damage is found a claim should be filed against the carrier immediately form platform not provided hung on a closet wall use wa...

Page 4: ... POWER SUPPLY WIRING WALL PANEL FRAME HOT WATER OUTLET HOT WATER INLET DRY WALL 2 X 4 WALL STUD CW UNITS CHILLED WATER CONNECTION Note Front edge of unit to be flush with dry wall CROSS MEMBER ON EDGE 2 X 4 WALL STUD WALL PANEL FRAME SCREW DETAIL OF WALL PANEL FRAME INSTALLATION DRY WALL LD11695A TABLE 1 DRYWALL OPENINGS MODEL NUMBER DRYWALL CUTOUT DIM HT x WD 3YWC 28 x 42 4YWC 28 x 50 6YWC 28 x 5...

Page 5: ...standard 120 volt power wired to a dis connect terminal block and a ground lug Fan motor hi med and low speed leads are wired to the control board There may be an unused motor lead from the motor its needs to be capped off The board is also wired to handle either 24v or 120v control wiring To use 24v remove jumpers on the control board For your 24v hot water control valve wire it in series with th...

Page 6: ... N A N A N A N A N A 2 2 1 5 9 4 8 3 12 11 15 15 3 3 2 3 13 6 11 9 17 15 20 15 4 4 3 0 17 8 15 5 23 20 25 20 5 5 3 8 21 9 19 1 28 24 30 25 6 6 4 5 26 1 22 7 33 29 35 30 8CWE 0 0 0 0 1 7 N A N A N A N A N A 3 3 2 3 14 2 12 5 18 16 20 20 4 4 3 0 18 4 16 1 23 21 25 25 5 5 3 8 22 5 19 7 29 25 30 25 6 6 4 5 26 7 23 5 34 30 35 30 8 8 6 0 35 0 30 5 44 39 50 40 10CWE 0 0 0 0 2 7 N A N A N A N A N A 3 3 2 ...

Page 7: ...eringtobronzeorbrass heatthepiping while in the socket cup and begin introducing the solder when the flux boils rapidly Avoid direct flame into the solder joint Heat can only be applied to the cup of the valve body for a minimal time before damage occurs even with the use of wet rags Avoid rapid quenching of solder joints as this will produce joints of inferior quality Connect all piping per accepte...

Page 8: ...ure exists at the drain pan and a minimum trap of 1 1 2 must be provided in the drain line to assure proper drainage Drain connections primary and secondary are 3 4 MPT see Fig 5 for details On units with plastic drain pans the drain connections must be made hand tight only INSTALLATION FIG 5 CWE SERIES WALL CLOSET FAN COILS Chilled Water with Electric Heat CONDENSATE DRAIN CONNECTIONS With drain ...

Page 9: ...C O thermostat and the TB3 3 TB2 5 jumper is in place the fan will con tinue to operate at the fan speed selected Removing the jumper will cause the fan to shut down when the thermostat is satisfied When using the T200 thermostat the stat will auto matically regulate the fan speed based on the differ ence between the space temp and setpoint 4 F off setpoint the fan will run HI 3 F off setpoint the ...

Page 10: ...e the air and heating capacities of the unit When the filters are excessively dirty the unit heating capacity will be so reduced that it is in effective for heating the room When a room fails to heat always check the filters To ensure proper maintenance of the filters it is best to follow an organized maintenance procedure The following one is recommended Divide the total number of units on the job i...

Page 11: ...11 JOHNSON CONTROLS FORM 115 20 NOM6 1106 This Page Intentionally Left Blank ...

Page 12: ...ture from accumulating in the bearings See Form 50 20 NM3 Long Term Storage Installer has cleaned out interior Ensure drain pan free from foreign material Ensure air filters are clean installed properly and secured Use the directional arrows or other information on the filter to determine the proper flow direction INSTALL CHECKLIST Equipment received as ordered Unit checked for damage interior and ex...

Reviews: