background image

JOHNSON CONTROLS

10

FORM 115.20-NOM6 (1106)

MAINTENANCE

MOTOR

The blower motor should be cleaned annually and if it 

has oiling ports, it should be oiled with a good grade 

of SAE 20 oil. Normally a few drops of oil in each 

bearing is sufficient.

COIL

The coil must be kept clean by any of the following 

methods.

    1.  Cleaning with low-pressure compressed air.
    2.  Flushing or rinsing with water (a detergent is  

 

advisable for greasy surfaces).

FILTERS

The  intervals  at  which  filters  require  replacement 

depend on local conditions.

Because of dust and lint in the room, room-air filters 

load up much more rapidly than outdoor-air filters.  

Under normal conditions, the room air filter requires 

replacement every six to eight weeks.

Clean or replace air filters regularly

Dirty filters reduce the air and heating 

capacities of the unit.  When the filters 

are excessively dirty, the unit heating 

capacity will be so reduced that it is in-

effective for heating the room.  When 

a room fails to heat, always check the 

filters.

To ensure proper maintenance of the filters, it is best 

to follow an organized maintenance procedure.  The 

following one is recommended:

Divide the total number of units on the job into six 

equal groups.  Each week inspect, clean or replace 

the filters in each group, in rotation.  This insures 

a uniform servicing interval.  The interval may be 

lengthened or shortened as determined by experience.  

If inspection shows only the room-air filter to be dirty, 

this one alone should be replaced.

CLEAN UNIT INTERIOR

Once a year clean the fans and coils of the unit thor-

oughly.  Remove the access panel as necessary.

Wipe the interior of the unit clean with a rag.  Wipe 

the motor and inside and outside of the fan housings.  

(In cooling units, clean out the drain pan.)

Summary of Contents for YCW

Page 1: ...mance and or a possible hazardous safety condition to service personnel and occupants Company employees and or contractors are not authorized to waive this warning Notes 1 For proper operation control valve must be normally closed 2 Aquastats provided where required 3 Electric Heat is available as an option MODELS YCW SERIES YCW Series 2 pipe 4 pipe or 2 pipe cooling with electric heat LD11554 LD1...

Page 2: ...HILLED WATER LINES 5 8 OD COPPER STUBOUTS HOT WATER RETURN HOT WATER SUPPLY FIG 1 UNIT NOMENCLATURE LD11557A LD11698A CABINET DIMENSIONS INCHES A B C D E F FILTER SIZE COIL CONN OD SWEAT HW CW YCW 22 1 8 15 1 8 40 14 10 1 2 3 5 8 18 X 18 5 8 YCW HW 22 1 8 15 1 8 43 18 12 1 2 3 5 8 18 X 18 5 8 5 8 YCWE 22 1 8 15 1 8 40 14 10 1 2 3 5 8 18 X 18 5 8 10 YCW 31 CFM 100 s 3 4 6 8 10 12 Unit Style YCW 2 p...

Page 3: ...provided with 2 coils with single end sheets cooling connections are on the top panel right side and the hot water connec tions are on the top panel middle front This unit is designed to be installed vertically in the upflow position and can be installed on a closet plat If damage is found a claim should be filed against the carrier immediately form platform not provided hung on a closet wall use wa...

Page 4: ... POWER SUPPLY WIRING WALL PANEL FRAME HOT WATER OUTLET HOT WATER INLET DRY WALL 2 X 4 WALL STUD CW UNITS CHILLED WATER CONNECTION Note Front edge of unit to be flush with dry wall CROSS MEMBER ON EDGE 2 X 4 WALL STUD WALL PANEL FRAME SCREW DETAIL OF WALL PANEL FRAME INSTALLATION DRY WALL LD11695A TABLE 1 DRYWALL OPENINGS MODEL NUMBER DRYWALL CUTOUT DIM HT x WD 3YWC 28 x 42 4YWC 28 x 50 6YWC 28 x 5...

Page 5: ...standard 120 volt power wired to a dis connect terminal block and a ground lug Fan motor hi med and low speed leads are wired to the control board There may be an unused motor lead from the motor its needs to be capped off The board is also wired to handle either 24v or 120v control wiring To use 24v remove jumpers on the control board For your 24v hot water control valve wire it in series with th...

Page 6: ... N A N A N A N A N A 2 2 1 5 9 4 8 3 12 11 15 15 3 3 2 3 13 6 11 9 17 15 20 15 4 4 3 0 17 8 15 5 23 20 25 20 5 5 3 8 21 9 19 1 28 24 30 25 6 6 4 5 26 1 22 7 33 29 35 30 8CWE 0 0 0 0 1 7 N A N A N A N A N A 3 3 2 3 14 2 12 5 18 16 20 20 4 4 3 0 18 4 16 1 23 21 25 25 5 5 3 8 22 5 19 7 29 25 30 25 6 6 4 5 26 7 23 5 34 30 35 30 8 8 6 0 35 0 30 5 44 39 50 40 10CWE 0 0 0 0 2 7 N A N A N A N A N A 3 3 2 ...

Page 7: ...eringtobronzeorbrass heatthepiping while in the socket cup and begin introducing the solder when the flux boils rapidly Avoid direct flame into the solder joint Heat can only be applied to the cup of the valve body for a minimal time before damage occurs even with the use of wet rags Avoid rapid quenching of solder joints as this will produce joints of inferior quality Connect all piping per accepte...

Page 8: ...ure exists at the drain pan and a minimum trap of 1 1 2 must be provided in the drain line to assure proper drainage Drain connections primary and secondary are 3 4 MPT see Fig 5 for details On units with plastic drain pans the drain connections must be made hand tight only INSTALLATION FIG 5 CWE SERIES WALL CLOSET FAN COILS Chilled Water with Electric Heat CONDENSATE DRAIN CONNECTIONS With drain ...

Page 9: ...C O thermostat and the TB3 3 TB2 5 jumper is in place the fan will con tinue to operate at the fan speed selected Removing the jumper will cause the fan to shut down when the thermostat is satisfied When using the T200 thermostat the stat will auto matically regulate the fan speed based on the differ ence between the space temp and setpoint 4 F off setpoint the fan will run HI 3 F off setpoint the ...

Page 10: ...e the air and heating capacities of the unit When the filters are excessively dirty the unit heating capacity will be so reduced that it is in effective for heating the room When a room fails to heat always check the filters To ensure proper maintenance of the filters it is best to follow an organized maintenance procedure The following one is recommended Divide the total number of units on the job i...

Page 11: ...11 JOHNSON CONTROLS FORM 115 20 NOM6 1106 This Page Intentionally Left Blank ...

Page 12: ...ture from accumulating in the bearings See Form 50 20 NM3 Long Term Storage Installer has cleaned out interior Ensure drain pan free from foreign material Ensure air filters are clean installed properly and secured Use the directional arrows or other information on the filter to determine the proper flow direction INSTALL CHECKLIST Equipment received as ordered Unit checked for damage interior and ex...

Reviews: