NOTES:
1. Minimum circuit ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all other
loads included in the circuit, per N.E.C. Article 430-24. If a Factory Mounted Control Transformer is provided, add the following to the system #1
MCA values in the YCU Tables: -17, add 10 amps; -28, add 9 amps; -46, add 4 amps; -58, add 3 amps.
2. Minimum fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs (U.L. Standard 1995, Section 36.1). It is not
recommended in applications where brown-outs, frequent starting and stopping of the unit, and/or operation at ambient temperatures in excess
of 95°F is anticipated.
3. Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit, per
N.E.C. 440-22.
4. The recommended disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the circuit,
per N.E.C. 440-12A1.
5. Maximum HACR is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit, per UL 1995
Fig. 36.2.
6. The “INCOMING WIRE RANGE” is the minimum and maximum wire size that can be accommodated by unit wiring lugs. The “(2)” preceeding the
wire range on “DUAL POINT WIRING (STANDARD)” indicates that two lugs, one on each of the two contactors of the part-wind start of each
system are available where two wires of the same phase of the wire range specified can be connected. The “(1)” preceeding the wire range on
“SINGLE POINT WIRING (OPTIONAL)” indicates that only a single lug is present for each phase. A “(1-3)” indicates that three lugs are present
on each phase where up to three wires of the wire range specified may be connected. Actual wire size and the number of wires required for each
phase must be determined based on the ampacity and job requirements using N.E.C. wire sizing information. All recommendations noted above
are based on the National Electric Code using copper conductors only. Field wiring must also comply with local codes.
7. A ground lug is provided for each compressor system to accommodate field grounding conductor per N.E.C. Article 250-54. A control circuit
grounding lug is also supplied. Incoming ground wire range is #6 - #2/0 (50 - 90 Tons) or #6 - 350 MCM (100 - 140 Tons).
ELECTRICAL DATA
UNIT POWER WIRING
INCOMING WIRING RANGE
6
SYSTEM 1
SYSTEM 2
COMPR.
COMPR.
COND
MODEL
CODE
DUAL ELEM
MAX SIZE
FAN
YCU
MCA
1
FUSE SIZE DISCONNECT CKT BKR
UNIT
YORK SUPPLIED NON-FUSED
RL A
PW/
RL A
PW/
FLA
MIN.
2
MAX.
3
MINIMUM
4
HACR
DISCONNECT (OPTIONAL)
8
LRA
LRA
EACH
TYPE
5
Z330A3
-17
274
350
350
400
350
(2)#6-250MCM (1)#1-600MCM OR (2) #1-250MCM
112
368
112
368
10.6
Z330A3
-28
240
300
300
400
300
(2)#6-250MCM
(1)#4-350MCM
97
320
97
320
10.5
Z330A3
-46
123
150
150
200
150
(2)#6-250MCM
(1)#4-350MCM
48.5
160
48.5
160
6.8
Z330A3
-58
99
110
125
200
125
(2)#6-250MCM
(1)#4-350MCM
38.8
128
38.8
128
5.6
Z440A3
-17
319
350
450
400
450
(2)#6-250MCM (1)#1-600MCM OR (2)#1-250MCM
132
414
132
414
10.6
Z440A3
-28
278
350
350
400
350
(2)#6-250MCM (1)#1-600MCM OR (2)#1-250MCM
114
360
114
360
10.5
Z440A3
-46
142
175
175
200
175
(2)#6-250MCM
(1)#4-350MCM
57
180
57
180
6.8
Z440A3
-58
114
125
150
200
150
(2)#6-250MCM
(1)#4-350MCM
45.6
144
45.6
144
5.6
Z740B3
-17
352
400
500
400
500
(2)#6-250MCM (1)#1-600MCM OR (2)#1-250MCM
159
683
132
414
10.6
Z740B3
-28
308
350
400
400
400
(2)#6-250MCM (1)#1-600MCM OR (2)#1-250MCM
138
594
114
360
10.5
Z740B3
-46
157
175
225
200
225
(2)#6-250MCM
(1)#4-350MCM
69
297
57
180
6.8
Z740B3
-58
126
150
175
200
175
(2)#6-250MCM
(1)#4-350MCM
55
245
45.6
144
5.6
Z770B3
-17
379
450
500
400
500
(2)#6-250MCM (1)#1-600MCM OR (2)#1-250MCM
159
683
159
683
10.6
Z770B3
-28
332
400
450
400
450
(2)#6-250MCM (1)#1-600MCM OR (2)#1-250MCM
138
594
138
594
10.5
Z770B3
-46
169
200
225
200
225
(2)#6-250MCM
(1)#4-350MCM
69
297
69
297
6.8
Z770B3
-58
135
150
175
200
175
(2)#6-250MCM
(1)#4-350MCM
55
245
55
245
5.6
Z880B3
-17
467
600
600
600
600
(2)#6-250MCM
(2)#4/0-500MCM
198
858
198
858
10.6
Z880B3
-28
409
450
500
600
500
(2)#6-250MCM
(2)#4/0-500MCM
172
746
172
746
6.8
Z880B3
-46
208
250
250
400
250
(2)#6-250MCM
(1)#4-350MCM
86
373
86
373
6.8
Z880B3
-58
167
200
225
200
225
(2)#6-250MCM
(1)#4-350MCM
68.8
304
68.8
304
5.6
CONTROL POWER SUPPLY
MAXIMUM
UNIT
CONTROL
MINIMUM
DUAL-
NON-FUSED
VOLTAGE
POWER
CIRCUIT
ELEMENT
DISC. SWITCH
SUPPLY
AMPACITY
FUSE SIZE
SIZE
All Models
without
155-1-60
20A
20A, 250V
30A, 240V
Transformers