FORM 201.25-NM1 (302)
73
YORK INTERNATIONAL
An example message follows:
Each digital input display will include:
• Name of the measured value
(example: Sys 1 Run Perm)
• Input to the -AMB (example: J4-5)
• State of input (ON or OFF)
An example message follow:
S Y S 1
R U N
P E R M
J
4 - 5
I S
O N
S Y S 1
R U N
P E R M
J
4 - 5
I S
O N
S Y S 1
S U C T
P R J
1 3 - 7
X . X V D C
=
X . X
P S I G
Each digital output display will include:
• Name of the controlled item
(example: Sys 1 LLSV)
• Output from the -AMB (example: J7-3)
• State of the output (ON or OFF)
An example message follows.
TABLE 6 –
PROGRAMMED PRESSURE/TEMPERATURE SETTINGS
SETPOINTS
LOCAL COOLING SETPOINT KEY
SETPOINT
40°F TO 70°F WATER
10°F TO 70°F GLYCOL
(4.5°C TO 21.1°C)
(-12.2° TO 21.2°C)
RANGE
+/- 0.9°C TO 0.9°C
REMOTE COOLING SETPOINT KEY
RANGE
36°F TO 71°F (2°C TO 22°C)
FIRST MECHANICAL DISCHARGE PRESSURE CUTOUT
275 PSIG (27.2 BARG)
SECOND MECHANICAL DISCHARGE PRESSURE CUTOUT
297 PSIG (27.9 BARG)
PROGRAM KEY
MICRO DISCHARGE PRESSURE CUTOUT
297 PSIG (26.5 BARG)
DISCHARGE PRESSURE UNLOAD
275 PSIG (25.7 BARG)
SUCTION PRESSURE CUTOUT
44 TO 70 PSIG SET
-5 TO 70 PSIG BARG
TO 44 BARG WATER
GLYCOL
HIGH AMBIENT TEMP CUTOUT
113°F STANDARD (45°C)
LOW AMBIENT TEMP CUTOUT
25°F STANDARD (-3.9°C)
LEAVING LIQUID TEMP CUTOUT
36°F WATER
9°F to 36°F( -12.9° TO 2.2°C)
(2.2°C)
GLYCOL
HIGH MOTOR CURRENT UNLOAD
30 TO 105% FLA
ANTI-RECYCLE TIME
300 - 600 SECONDS
7