PROBLEM
CAUSE
SOLUTION
Compressor wont
1. Suction pressure > programmed
1. Excessive load. Check OPERATING
load
unload point or operating limitations
LIMITATIONS. Check programmed
(Solenoid valve
have been exceeded.
unloading point.
de-energizes to load
2. Discharge pressure > programmed
2. Check OPERATING LIMITATIONS.
compressor)
load point or operating limitations
Check programmed unloading point.
have been exceeded.
3. Demand not great enough.
3. OK. Become familiar with control
operation.
4. Defective loading solenoid.
4. Replace compressor loading solenoid.
5. Faulty wiring to loading solenoid.
5. Check wiring.
6. Defective water temperature sensor.
6. Compare sensor with a thermometer.
Variation of sensor vs thermometer of
±2°F is not unusual. Replace if necessary.
7. Defective evaporator or optional
7. Replace transducer after verifying with a
discharge transducer.
gauge.
Lack of Cooling
1. Fouled evaporator surface.
1. Contact the local YORK service
Effect
representative.
2. Faulty compressor suction and/or
2. Contact the local YORK service
discharge valves.
representative.
Summary of Contents for YCRJ45E00
Page 29: ...FORM 150 24 NM27 YORK INTERNATIONAL 29 CONTROL CIRCUIT With I O Expansion Board LD02106 ...
Page 30: ...30 YORK INTERNATIONAL FIG 9 SYSTEM WIRING ...
Page 31: ...FORM 150 24 NM27 YORK INTERNATIONAL 31 LD02678 ...
Page 35: ...FORM 150 24 NM27 YORK INTERNATIONAL 35 LD02679 ...
Page 36: ...36 YORK INTERNATIONAL MICROPANEL CONNECTION DIAGRAM With I O Expansion Board LD02107 ...
Page 37: ...FORM 150 24 NM27 YORK INTERNATIONAL 37 LD02108 ...