The values displayed under each of the key presses may
be changed by keying in new values and pressing the
(ENTER) key to store the new value into memory.
Where more than one value may be keyed in on a dis-
play, a portion of the data that does not need updating
may be skipped by pressing the
(ENTER) key. The
(ENTER) key must also be pressed after the last value
in the display to store the data into memory.
The ▲ (ARROW) key allows scrolling back through
the setpoints displays.
The minimum, maximum, and default values allowed
under the SETPOINTS key are provided in TABLE
16, below:
SETPOINTS KEY (CON'T)
TABLE 16 - SETPOINT LIMITS
PROGRAM VALUE
MODE
LOW LIMIT
HIGH LIMIT
DEFAULT
Leaving Chilled Liquid Setpoint
Water Cooling
40.0°F
60.0°F
44.0°F
4.4°C
15.6°C
6.7°C
Glycol Cooling
15.0°F
70.0°F
44.0°F
-9.4°C
15.6°C
6.7°C
Leaving Chilled Liquid Control Range
-
1.5°F
2.5°F
2.0°F
0.8°C
1.4°C
1.1°C
Max. Remote Temperature Reset
-
2°F
40°F
20°F
1°C
22°C
11°C
MICRO PANEL
Summary of Contents for YCAV0157
Page 43: ...43 JOHNSON CONTROLS FORM 201 21 NM1 1223 This page intentionally left blank 6...
Page 55: ...55 JOHNSON CONTROLS FORM 201 21 NM1 1223 This page intentionally left blank 6...
Page 57: ...57 JOHNSON CONTROLS FORM 201 21 NM1 1223 ELEMENTARY CONTROL WIRING DIAGRAM CON T 6 LD12519...
Page 64: ...64 JOHNSON CONTROLS FORM 201 21 NM1 1223 LOCATION LABEL LD10519 TECHNICAL DATA...
Page 65: ...65 JOHNSON CONTROLS FORM 201 21 NM1 1223 This page intentionally left blank 6...
Page 123: ...123 JOHNSON CONTROLS FORM 201 21 NM1 1223 This page intentionally left blank 6...
Page 211: ...211 JOHNSON CONTROLS FORM 201 21 NM1 1223 8 This Page Intentionally Left Blank...
Page 233: ...233 JOHNSON CONTROLS FORM 201 21 NM1 1223 This page intentionally left blank 8...
Page 253: ...253 JOHNSON CONTROLS FORM 201 21 NM1 1223 8 This page intentionally left blank...
Page 281: ...281 JOHNSON CONTROLS FORM 201 21 NM1 1223 8 This page intentionally left blank...