191
JOHNSON CONTROLS
FORM 201.21-NM1 (1223)
VSD TEMPERATURE CONTROL, OPERATION OF THE COOLANT PUMP,
AND VSD CABINET COOLING FANS
The Coolant pump and VSD Cabinet Cooling Fans will
run to cool the VSD whenever any of the following
conditions are met:
·
VSD Comp IGBT Baseplate Temperature on a 2 or
4 compressor unit is greater than 10°F below the
cutout (Cutout [218°F]-10°F =208°F). When the
VSD internal ambient falls below the restart tem-
perature (Cutout [218°F] - 15°F = 203°F), the fans
and pump will turned off without a time delay.
·
VSD Comp IGBT Baseplate Temperature on a 3
compressor unit is greater than 10°F below the
cutout (Cutout [232°F] - 10°F = 222°F). When
the VSD internal ambient falls below the restart
temperature (Cutout - 15°F = 217°F), the fans and
pump will be turned off without a time delay.
·
Pre-charge Enable 1 from the Chiller Logic Board
is ON.
·
Pre-charge Enable 2 from the Chiller Logic Board
is ON.
·
VSD Internal Ambient Temp > 158°F (Cutout)
– 10°F = 148°F. When the Internal Ambient Temp
falls < 158°F (Cutout) - 15°F = 143 °F the VSD
cooling fans and glycol pump will turn off.
·
Condenser Fans (as needed) and VSD coolant pump/
fans will run whenever a compressor is running.
Under these conditions, the condenser fans will run
to control discharge pressure and the VSD coolant
pump/fans will run to cool the IGBT baseplate and
internal cabinet. Additional condenser fans will be
brought on, if the IGBT baseplate temperatures or
internal cabinet ambient rises to 5°F below the cut-
out. Condenser fans will turn off, if the compressor
turns off provided VSD cooling is not required. The
glycol pump and cabinet fan may continue to run,
if VSD cooling is required.
·
Glycol Pump and Cabinet Cooling Fans will also
run in the Service Mode if the Fan/Pump Run Bit
is Set.
7
Summary of Contents for YCAV0157
Page 43: ...43 JOHNSON CONTROLS FORM 201 21 NM1 1223 This page intentionally left blank 6...
Page 55: ...55 JOHNSON CONTROLS FORM 201 21 NM1 1223 This page intentionally left blank 6...
Page 57: ...57 JOHNSON CONTROLS FORM 201 21 NM1 1223 ELEMENTARY CONTROL WIRING DIAGRAM CON T 6 LD12519...
Page 64: ...64 JOHNSON CONTROLS FORM 201 21 NM1 1223 LOCATION LABEL LD10519 TECHNICAL DATA...
Page 65: ...65 JOHNSON CONTROLS FORM 201 21 NM1 1223 This page intentionally left blank 6...
Page 123: ...123 JOHNSON CONTROLS FORM 201 21 NM1 1223 This page intentionally left blank 6...
Page 211: ...211 JOHNSON CONTROLS FORM 201 21 NM1 1223 8 This Page Intentionally Left Blank...
Page 233: ...233 JOHNSON CONTROLS FORM 201 21 NM1 1223 This page intentionally left blank 8...
Page 253: ...253 JOHNSON CONTROLS FORM 201 21 NM1 1223 8 This page intentionally left blank...
Page 281: ...281 JOHNSON CONTROLS FORM 201 21 NM1 1223 8 This page intentionally left blank...