MINIMUM VSD COMPRESSOR START/RUN FREQUENCY
MINIMUM VSD START FREQUENCY
The Minimum VSD Compressor Start Frequency is
based on ambient temperature and determines the
frequency (speed) the compressor(s) is ramped to at start.
At higher ambients, higher speeds are needed to provide
adequate motor cooling. At low ambients, higher motor
speeds are needed to develop oil pressure differential at
start. The temperature ranges and the associated start
frequency follows the guidelines below:
·
If the ambient temperature is 25°F or less, the
Minimum VSD Start Frequency will be
70 Hz.
·
If the ambient temperature is 26-40 °F, the
Minimum VSD Start Frequency is 60 HZ.
·
If the ambient temperature is 41-110 °F, the
Minimum VSD Start Frequency will be
50 Hz.
·
If the ambient is 110-125 °F, the Minimum VSD
Start Frequency is scaled according to the
following formula:
(3X Ambient Temperature)-280°F.
The formula is also represented by the graph in FIG.
30.
NOTE: The graph above also illustrates the scaled frequency:
FIG. 30 - MINIMUM VSD START FREQUENCY
LD10627
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
Ambient Temperature (°F)
Mi
ni
mu
m
VSD
F
re
que
ncy
(H
z)
NOTE: The graph above also illustrates the scaled frequency:
FIG. 31 - MINIMUM VSD RUN FREQUENCY
LD10628
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
Ambient Temperature (°F)
Mi
ni
mu
m
VSD
F
re
que
ncy
(H
z)
MINIMUM VSD RUN FREQUENCY
The Minimum VSD Compressor Run Frequency is based
on ambient temperature and determines the minimum
frequency (speed) the compressor(s) is permitted to run
as the system unloads. At high ambients, higher motor
speeds are needed to cool the compressor motor. The
temperature ranges and the associated start frequency
follows the guidelines below:
·
If the ambient temperature is <110°F, the Minimum
VSD Run Frequency will be 50 Hz.
·
If the ambient is 110-125°F, the Minimum VSD
Run Frequency is scaled according to the following
formula:
(3X Ambient Temperature)-280°F.
The formula is also represented by the graph in FIG.
31.
OPERATION
·
Above 125°F, the minimum VSD Start
Frequency is 95 Hz.
·
If the ambient temperature is >125°F, the Minimum
VSD Run Frequency will be 95 Hz.
Summary of Contents for YCAV0157
Page 43: ...43 JOHNSON CONTROLS FORM 201 21 NM1 1223 This page intentionally left blank 6...
Page 55: ...55 JOHNSON CONTROLS FORM 201 21 NM1 1223 This page intentionally left blank 6...
Page 57: ...57 JOHNSON CONTROLS FORM 201 21 NM1 1223 ELEMENTARY CONTROL WIRING DIAGRAM CON T 6 LD12519...
Page 64: ...64 JOHNSON CONTROLS FORM 201 21 NM1 1223 LOCATION LABEL LD10519 TECHNICAL DATA...
Page 65: ...65 JOHNSON CONTROLS FORM 201 21 NM1 1223 This page intentionally left blank 6...
Page 123: ...123 JOHNSON CONTROLS FORM 201 21 NM1 1223 This page intentionally left blank 6...
Page 211: ...211 JOHNSON CONTROLS FORM 201 21 NM1 1223 8 This Page Intentionally Left Blank...
Page 233: ...233 JOHNSON CONTROLS FORM 201 21 NM1 1223 This page intentionally left blank 8...
Page 253: ...253 JOHNSON CONTROLS FORM 201 21 NM1 1223 8 This page intentionally left blank...
Page 281: ...281 JOHNSON CONTROLS FORM 201 21 NM1 1223 8 This page intentionally left blank...