266
JOHNSON CONTROLS
FORM 201.21-NM1 (616)
MICRO PANEL
SERVICE KEY (CON'T)
SERVICE DO J10-1
EVAP PUMP RUN
RB1 TB1-20
STATUS = XXX
SERVICE DO J10-2
SYS 2/4 VSD RUN
RB1 TB1-18
STATUS = XXX
SERVICE DO J10-3
SYS 2/4 ALARM
RB1 TB1-16
STATUS = XXX
SERVICE DO J10-4
CHILLER RUN
RB1 TB1-14
STATUS = XXX
SERVICE DO J10-5
SYS 2 SPARE
RB1 TB1-12
STATUS = XXX
SERVICE DO J10-6
SPARE 3
RB1 TB1-10
STATUS = XXX
SERVICE DO J10-7
SPARE 4
RB1 TB1-8
STATUS = XXX
SERVICE DO J10-8
SYS COND 2 FAN OUT 1
RB1 TB1-6
STATUS = XXX
SERVICE DO J10-9
SYS COND 2 FAN OUT 2
RB1 TB1-5
STATUS = XXX
SERVICE DO J10-10 SYS COND 2 FAN OUT 3
RB1 TB1-4
STATUS = XXX
SERVICE DO J10-11
SYS 2 COMP HEATER
RB1 TB1-3
STATUS = XXX
SERVICE DO J10-12 SYS 2 ECON SOL VALVE
RB1 TB1-2
STATUS = XXX
SERVICE DO J11-1
SYS 4 COND FAN OUT 1
RB1 TB1-20
STATUS = XXX
SERVICE DO J11-2
SYS 4 COND FAN OUT 2
RB1 TB1-18
STATUS = XXX
SERVICE DO J11-3
SYS 4 COND FAN OUT 3
RB1 TB1-16
STATUS = XXX
SERVICE DO J11-4
SYS 4 COMP HEATER
RB1 TB1-14
STATUS = XXX
SERVICE DO J11-5
SYS 4 ECON SOL VALVE
RB1 TB1-12
STATUS = XXX
SERVICE DO J11-6
SYS 4 SPARE
RB1 TB1-10
STATUS = XXX
SERVICE DO J11-7
SYS 3 SPARE
RB1 TB1-8
STATUS = XXX
SERVICE DO J11-8
SYS 3 COND FAN OUT 1
RB1 TB1-6
STATUS = XXX
SERVICE DO J11-9
SYS 3 COND FAN OUT 2
RB1 TB1-5
STATUS = XXX
SERVICE DO J11-10
SYS 3 COND FAN OUT 3
RB1 TB1-4
STATUS = XXX
SERVICE DO J11-11
SYS 3 COMP HEATER
RB1 TB1-3
STATUS = XXX
SERVICE DO J11-12
SYS 3 ECON SOL VALVE
RB1 TB1-2
STATUS = XXX
The fifth data section displays the Analog Outputs
(AO) that can be viewed from the Service Mode. The
Analog Output signals are typically referenced to the
common (return, ground) in the system. J12-3 can also
be used as common, as well as chassis ground, or the
common terminal point on the Chiller Control Board.
See the wiring diagrams. GND on the plug. Displays
for systems 3 and 4 are skipped if the systems are not
present on the chiller. XXX is replaced with ON or OFF
in the actual display. The state of these outputs is only
viewable unless the password 9675
(ENTER) key was
entered from the initial Service Mode display with the
UNIT Switch in the OFF position. The chiller will not
be permitted to run when the outputs are made active.
The outputs can be programmed for a specific % output
by keying in the value and pressing the
(ENTER) key.
These messages will only be displayed in English.
SERVICE AO J15-1
SYS 1 FEED VALVE OUT
XXX.X %
= XX.X VDC
SERVICE AO J15-3
SYS 1 DRAIN VALVE OUT
XXX.X %
= XX.X VDC
SERVICE AO J15-5
SYS 2 FEED VALVE OUT
XXX.X %
= XX.X VDC
SERVICE AO J15-7
SYS 2 DRAIN VALVE OUT
XXX.X %
= XX.X VDC
Summary of Contents for YCAV0157-0267
Page 43: ...43 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Page 55: ...55 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Page 57: ...57 JOHNSON CONTROLS FORM 201 21 NM1 616 ELEMENTARY CONTROL WIRING DIAGRAM CON T 6 LD12519 ...
Page 64: ...64 JOHNSON CONTROLS FORM 201 21 NM1 616 LOCATION LABEL LD10519 TECHNICAL DATA ...
Page 65: ...65 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Page 123: ...123 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Page 211: ...211 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This Page Intentionally Left Blank ...
Page 233: ...233 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 8 ...
Page 253: ...253 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This page intentionally left blank ...
Page 281: ...281 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This page intentionally left blank ...