213
JOHNSON CONTROLS
FORM 201.21-NM1 (616)
NEW 331-03478-XXX MICROBOARD
TP10 +24V
TP5 +15V
TP4 +12V
TP1 GND
U18 VSD
RS-485 Driver
VSD RX
VSD TX
Port 2
RX2
TX2
RS-232
to Printer
Power LED
Status
LED
TP3
+5V
TP2
+3.3V
SD
Card
Power
LED
U5 RTC/
BRAM
JP4 JP5 JP6 Remote
Setpoint Jumpers
Port 2
RS-485 to
E-Link
U26 Port 1
RS-485 Driver
U23 Port 2
RS-485 Driver
Port 1
Future
Native
BAS
LD19331
8
If the chiller control is malfunctioning, the power sup-
ply test points should be measured to determine the sta-
tus of the microboard.
POWER SUPPLY TEST POINTS
TP1 GND (Measure TP2, TP3, TP4 and TP5 in refer-
ence to this Test Point)
TP2 +3.3V [3.2 to 3.4VDC] provides power to the pro-
cessors
TP3 +5V [4.8 to 5.2VDC] power communiaction ports
2,3 and 4 and analog sensors
TP4 +12V [11.64 to 12.36VDC] powers the display
and backlight and is regulated to become the +5V
TP5 +15V [11.3 to 16.6VDC] powers the analog out-
puts to the EEV valves
CONFIGURATION JUMPERS
The same configuration jumpers that existed on the
02478 are provided on the 03478.
JP4 Remote Temp Reset jumper position Pins 1 to 2
(left) = 4-20 mA, Pins 2 to 3 (right) = 0-10 VDC
JP5 Remote Current Limit jumper position Pins 1 to 2
(left) = 4-20 mA, Pins 2 to 3 (right) = 0-10 VDC
JP6 Remote Sound Limit jumper position (Pins 1 to 2
(left) = 4-20 mA, Pins 2 to 3 (right) = 0-10 VDC
COMMUNICATION PORTS
TB3 Port 1 Native BAS RS-485.
SW1 RS-485 Biasing Switch for Port. Set to ON if Chill-
er is in an End Of Line position on the network.
U26 is the Port 1 RS-485 Driver Chip. It is socketed to
allow field replacement. RX1 and TX1 LEDs illuminate
to indicate Port 1 communications activity.
E-LINK
SW2 RS-485 Biasing Switch for E-link Port 2, should be
in the OFF position.
TB2 is the Port 2 RS-485 E-Link Communications Port.
RX2 and TX2 LEDs illuminate to indicate the Port
2 communications activity. U23 is the Port 2 RS-485
Driver Chip. It is socketed to allow field replacement.
J16 pr12VDC to power the E-Link.
Summary of Contents for YCAV0157-0267
Page 43: ...43 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Page 55: ...55 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Page 57: ...57 JOHNSON CONTROLS FORM 201 21 NM1 616 ELEMENTARY CONTROL WIRING DIAGRAM CON T 6 LD12519 ...
Page 64: ...64 JOHNSON CONTROLS FORM 201 21 NM1 616 LOCATION LABEL LD10519 TECHNICAL DATA ...
Page 65: ...65 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Page 123: ...123 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Page 211: ...211 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This Page Intentionally Left Blank ...
Page 233: ...233 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 8 ...
Page 253: ...253 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This page intentionally left blank ...
Page 281: ...281 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This page intentionally left blank ...