235
JOHNSON CONTROLS
FORM 201.21-NM1 (616)
The next key press displays the current limit values set
locally on the panel under the PROGRAM key, remotely
by an ISN, and remotely by the Current Limit input.
Any current limits that are inactive will display “XXX”
instead of a numeric value.
VSD DATA KEY (CON'T)
The next key press displays DC bus voltage for 2 and 3
compressor units.. On 4 compressor units, the 2nd mes-
sage will apply, since two DC bus voltages are present
(Systems 1/3 and 2/4).
VSD CURRENT LIMIT LOCAL = XXX %FLA
ISN = XXX
REMOTE = XXX %FLA
The next key press displays the Control Panel/VSD
Internal Ambient Temperature and VSD Cooling Pump/
Fan Status. YYY will indicate ON or OFF.
VSD DC BUS VOLTAGE = XXX VDC
The next key press displays the IGBT highest baseplate
temperature for 2 and 3 compressor units. 4 compres-
sor units display temperatures for Systems 1/3 (T1) and
Systems 2/4 (T2).
VSD DC BUS VOLTAGES BUS 1 = XXX VDC
BUS 2 = XXX VDC
VSD
COMP 3 MOTOR OVERLOAD = XXX AMPS
COMP 4 MOTOR OVERLOAD = XXX AMPS
VSD
COMP 1 MOTOR OVERLOAD = XXX AMPS
COMP 2 MOTOR OVERLOAD = XXX AMPS
VSD
INTERNAL AMBIENT TEMP = XXX.X °F
COOLING SYSTEM STATUS = YYY
VSD IGBT BASEPLATE TEMPS T1 = XXX °F
T2 = XXX °F
The next key press displays the state of the Precharge
signal, where XXX is either ON or OFF. The first dis-
play is for 2 and 3 compressor units, the second display
shown is for 4 compressor units where Precharge 1 is
for compressors 1 and 3 DC Bus and Precharge 2 is for
compressors 2 and 4 DC Bus.
VSD
PRECHARGE SIGNAL = XXX
VSD
PRECHARGE 1 SIGNAL = XXX
VSD
PRECHARGE 2 SIGNAL = XXX
The next key press displays the setting of the VSD’s
105% FLA overload potentiometer for Compressor #1
and 2. The settings are determined by the adjustment of
the overload potentiometers on the VSD Logic Board.
These pots are factory set and should not require chang-
ing unless the circuit board is replaced. See TABLE 34
for factory settings.
The next key press displays the setting of the VSD’s
105% FLA potentiometer for Compressor #3 and #4 (3
and 4 compressor units only). The second line will be
blanked out on 3 compressor units.
8
Summary of Contents for YCAV0157-0267
Page 43: ...43 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Page 55: ...55 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Page 57: ...57 JOHNSON CONTROLS FORM 201 21 NM1 616 ELEMENTARY CONTROL WIRING DIAGRAM CON T 6 LD12519 ...
Page 64: ...64 JOHNSON CONTROLS FORM 201 21 NM1 616 LOCATION LABEL LD10519 TECHNICAL DATA ...
Page 65: ...65 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Page 123: ...123 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Page 211: ...211 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This Page Intentionally Left Blank ...
Page 233: ...233 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 8 ...
Page 253: ...253 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This page intentionally left blank ...
Page 281: ...281 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This page intentionally left blank ...