HISTORY KEY (CON'T)
UNIT DATA
Evaporator Leaving and Return Chilled Liquid
Temps
This message indicates the leaving and entering chilled
liquid temperatures at the time of the fault.
Ambient Air Temperature
UNIT CHILLED LIQUID LEAVING = XXX.X °F
ENTERING = XXX.X °F
This message indicates the ambient air temperature at
the time of the fault.
Load / Unload Timers
UNIT
OUTSIDE AMBIENT AIR TEMP = XXX.X °F
UNIT
LOAD TIMER = XXX SEC
UNLOAD TIMER = XXX SEC
This message indicates remaining time on the load and
unload timers at the time of the fault.
Chilled Liquid Temperature Error and Rate of
Change
UNIT ACTIVE REMOTE CONTR0L = XXXXXX
UNIT
EVAP PUMP RUN = XXX
EVAP HEATER = XXX
UNIT SOUND LIMIT
LOCAL = XXX %
ISN = XXX
REMOTE = XXX %
VSD FREQUENCY
ACTUAL = XXX.X HZ
COMMAND = XXX.X HZ
UNIT
TEMP ERROR = XXX.X °F
RATE = XXX.X °F/M
This message indicates the temperature error between
the actual and the programmed setpoint at the time of
the fault and the rate of temperature change.
Programmed Lead System Selection and
Flow Switch Status
This message indicates the designated lead system at the
time of the fault and whether the flow switch was ON
(Closed) or OFF (Open) at the time of the fault.
Evaporator Pump and Evaporator Heater
UNIT LEAD SYSTEM NUMBER = X
FLOW SWITCH = XXX
Status
This message indicates the status of the evaporator pump
and the evaporator heater at the time of the fault. XXX
indicates ON or OFF.
Active Remote Control Status
This message indicates whether the system was operat-
ing under active remote control (RCC, ISN, LOAD,
TEMP, or SOUND) or standard control (NONE) at the
time of the fault.
This message indicates that sound limiting was in ef-
fect, the amount, and whether it was local or remotely
limited.
VSD DATA
VSD Actual and Command Frequency
This message indicates the VSD actual operating
frequency and the command frequency at the time of
the fault. Actual and command may not match due to
load/unload timers, limitation of 1 Hz per load/unload
increment, and to allowable acceleration/deceleration
of the motor.
Compressor AMPS and %FLA
VSD COMP 1 = XXX AMPS
= XXX %FLA
COMP 2 = XXX AMPS
= XXX %FLA
The message indicates the compressor %FLA and cur-
rents for systems 1 and 2 at the time of the fault.
8
Summary of Contents for YCAV0157-0267
Page 43: ...43 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Page 55: ...55 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Page 57: ...57 JOHNSON CONTROLS FORM 201 21 NM1 616 ELEMENTARY CONTROL WIRING DIAGRAM CON T 6 LD12519 ...
Page 64: ...64 JOHNSON CONTROLS FORM 201 21 NM1 616 LOCATION LABEL LD10519 TECHNICAL DATA ...
Page 65: ...65 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Page 123: ...123 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Page 211: ...211 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This Page Intentionally Left Blank ...
Page 233: ...233 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 8 ...
Page 253: ...253 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This page intentionally left blank ...
Page 281: ...281 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This page intentionally left blank ...