33
Cooling -- No Hot Water Generator
Entering Water
Temp °F
Water
Flow GPM/
Ton
YAZS022 thru YAZS060
YAZS070
YAZS022 thru YAZS070
Suction
Pressure PSIG
Discharge
Pressure PSIG
Suction
Pressure PSIG
Discharge
Pressure PSIG
Superheat
Subcooling
Water Temp
Rise °F
Air Temp Drop
°F DB
50
1.5
115-150
205-245
115-130
205-245
12-22
7-14
5-22
18-24
3.0
110-145
200-235
110-125
200-235
14-26
6-12
8-12
18-24
70
1.5
125-160
260-300
125-160
275-300
8-14
8-12
5-19
18-22
3.0
115-150
265-295
115-135
265-295
9-16
4-16
5-12
18-22
90
1.5
125-160
320-370
125-160
330-370
8-14
6-13
14-22
18-22
3.0
120-150
305-355
120-150
325-365
9-16
4-16
5-12
18-22
Heating -- No Hot Water Generator
Entering Water
Temp °F
Water
Flow GPM/
Ton
YAZS022 thru YAZS060
YAZS070
YAZS022 thru YAZS070
Suction
Pressure PSIG
Discharge
Pressure PSIG
Suction
Pressure PSIG
Discharge
Pressure PSIG
Superheat
Subcooling
Water Temp
Drop °F
Air Temp Rise
°F DB
30
1.5
65-85
290-310
65-85
330-360
7-13
2-21
7-10
18-24
3.0
70-90
265-330
70-90
335-365
6-12
2-21
3-7
22-26
50
1.5
95-120
320-345
95-120
395-430
6-12
2-21
5-11
21-34
3.0
100-125
280-365
100-125
375-405
6-12
4-22
5-11
24-33
70
1.5
135-155
315-380
135-155
435-485
8-14
10-20
8-14
26-46
3.0
135-156
315-395
135-155
440-490
8-14
10-20
3-10
25-48
Operating Parameters
NOTES:
Cooling performance based on entering air temperatures of 80°F DB, 67°F WB.
Heating performance based on entering air temperatures of 70°DB.
5/29/08
AFFINITY INDOOR SPLIT SERIES INSTALLATION MANUAL
Single Speed Models - YAZS022 thru YAZS070
(with YAH Series Air Handler)