38
Heat of Extraction/Rejection Data - Single Speed Units
Model
GPM
Heat of Extraction (kBtuh)
Heat of Rejection (kBtuh)
30°F
50°F
70°F
90°F
30°F
50°F
70°F
90°F
110°F
022
3.0
13.6
18.0
22.0
25.6
25.4
23.5
4.5
9.9
14.3
19.1
23.0
23.3
25.8
25.5
23.5
22.3
6.0
10.0
14.8
19.4
23.5
23.5
26.0
25.5
23.6
22.4
030
4.0
19.2
25.0
29.8
31.2
31.5
29.8
6.0
14.0
19.8
26.0
31.0
29.0
31.1
31.4
29.7
26.4
8.0
14.2
20.4
26.5
32.5
29.3
31.4
31.6
29.9
26.5
036
5.0
23.6
31.0
37.2
38.6
39.7
36.7
7.0
17.5
24.7
32.3
38.8
32.1
38.5
39.6
36.6
35.7
9.0
17.9
25.2
32.9
39.4
32.5
38.9
39.9
36.8
35.9
042
5.0
26.9
33.4
36.6
46.7
47.6
43.9
8.0
20.8
28.2
35.1
42.0
43.1
46.9
47.9
44.2
42.3
11.0
21.2
29.0
36.2
43.5
43.4
47.2
48.2
44.4
43.1
048
6.0
34.7
43.5
50.7
57.6
57.5
51.3
9.0
26.5
36.3
45.8
53.8
53.4
57.8
57.9
51.7
51.6
12.0
27.0
37.3
47.2
55.6
53.7
58.1
58.0
51.8
51.6
060
9.0
41.0
52.4
61.2
75.4
74.0
68.9
12.0
28.9
42.3
54.1
65.0
72.9
75.6
74.3
68.7
64.9
15.0
30.0
43.2
56.3
65.8
73.5
75.7
73.9
68.9
67.0
070
12.0
50.3
64.2
70.3
82.9
84.1
74.7
15.0
36.4
51.6
67.0
74.6
75.9
83.0
82.2
74.4
70.7
18.0
36.6
52.1
68.1
76.3
76.3
83.6
83.1
75.2
71.4
Note: operation not recommended in shaded areas.