16
Model
Rated
Voltage
Voltage
Min/Max
Compressor
HWA
Pump
FLA
Ext
Loop
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC
RLA
LRA
LRA*
022
208-230/60/1
187/253
14.0
9.0
48.0
17.0
0.4
5.4
14.8
17.1
25
030
208-230/60/1
187/253
20.0
12.8
58.3
21.0
0.4
5.4
18.6
21.8
30
036
208-230/60/1
187/253
22.0
14.1
73.0
26.0
0.4
5.4
19.9
23.4
35
042
208-230/60/1
187/253
26.0
16.6
79.0
28.0
0.4
5.4
22.4
26.6
40
048
208-230/60/1
187/253
31.0
19.8
109.0
38.0
0.4
5.4
25.6
30.6
50
060
208-230/60/1
187/253
41.2
26.4
134.0
47.0
0.4
5.4
32.2
38.8
60
070
208-230/60/1
187/253
44.2
28.3
158.0
63.0
0.4
5.4
34.1
41.2
70
026
208-230/60/1
187/253
18.2
11.6
58.3
21.0
0.4
5.4
17.4
20.3
30
038
208-230/60/1
187/253
23.8
15.2
83.0
30.0
0.4
5.4
21.0
24.8
40
049
208-230/60/1
187/253
33.0
21.1
104.0
37.0
0.4
5.4
26.9
32.2
50
064
208-230/60/1
187/253
42.3
27.1
152.9
54.0
0.4
5.4
32.9
39.7
70
072
208-230/60/1
187/253
46.3
29.6
179.2
63.0
0.4
5.4
35.4
42.8
75
4/3/13
Rated voltage of 208-230/60/1
HACR circuit breaker in USA only
All fuses Class RK-5
* With optional GeoStart
Electrical Data
Electronic Thermostat Installation cont.
Single and Dual Capacity Wiring Diagram
Field low voltage point to point wiring:
From
Thermostat
To Air Handler
To Compressor
Section
C
C
C
R
R
R
G
G
O
O
O
Y1
Y1
Y1
Y2
Y2
Y2
W2
W
L
L
Air Handler transformer must be 75VA.
5/29/08
AFFINITY INDOOR SPLIT SERIES INSTALLATION MANUAL