15
Dual Capacity Unit with Variable Speed ECM Motor
Model
Rated
Voltage
Voltage
Min/Max
Compressor
Ext
Loop
FLA
Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC
RLA
LRA
LRA**
026
208-230/60/1
187/253
18.2
11.6
58.3
21.0
5.4
4.0
21.0
24.0
35
038
208-230/60/1
187/253
23.8
15.2
83.0
30.0
5.4
4.0
24.6
28.4
40
038*
208-230/60/1
187/253
23.8
15.2
83.0
30.0
5.4
7.0
27.6
31.4
50
049
208-230/60/1
187/253
33.0
21.1
104.0
37.0
5.4
7.0
33.5
38.8
60
064
208-230/60/1
187/253
42.3
27.1
152.9
54.0
5.4
7.0
39.5
46.2
70
072
208-230/60/1
187/253
46.3
29.6
179.2
63.0
5.4
7.0
42.0
49.4
70
*With optional 1 HP Variable Speed ECM motor 7/10/17
**With optional IntelliStart
Rated Voltage of 208/230/60/1
HACR circuit breaker in USA only
All fuses Class RK-5
Electrical Data
AFFINITY SERIES