Dual Capacity ECM Blower Table with IntelliZone2•24V
MODEL
MAX
ESP
AIR FLOW SPEED SETTINGS
1
2
3
4
5
6
7
8
9
10
11
12
026
0.50
400
475
G
625
725
L
775
850
H
950
1050
1175
Aux
038
0.50
650
700
G
825
950
1075
L
1175
1275
H
1375
1450
1500
Aux
038 W/1HP*
0.75
675
850
G
1025
L
1250
H
1425
1625
1750
1925
2075
Aux
2225
049
0.75
675
850
G
1000
1200
1400
L
1600
H
1750
1900
2100
2150
Aux
064
0.75
700
875
G
1025
1225
1425
1625
L
1775
1925
H
2125
2175
Aux
072
0.75
700
875
1025
G
1225
1425
1625
1775
L
1925
2125
H
2175
Aux
Factory settings are at recommended G-L-H-Aux speed settings 7/24/17
L-H settings MUST be located within boldface CFM range or higher
“Aux” is factory setting for auxiliary heat and must be equal to or above the “H” setting as well as at least the minimum required
for the auxiliary heat package
“G” may be located anywhere within the airflow table
CFM is controlled /-5% up to the maximum ESP
Max ESP includes allowance for wet coil
Dual Capacity ECM Blower Table with IntelliZone2
MODEL
MAX
ESP
AIR FLOW SPEED SETTINGS
1
2
3
4
5
6
7
8
9
10
11
12
026
0.50
400
G
475
625
L 55%
725
70%
775
85%
850
H 100%
950
1050
1175
Aux
038
0.50
650
700
G
825
L 55%
950
70%
1075
1175
85%
1275
H 100%
1375
1450
1500
Aux
038 W/1HP*
0.75
675
G
850
L 55%
1025
70%
1250
85%
1425
H 100%
1625
1750
1925
2075
Aux
2225
049
0.75
675
850
G
1000
L 55%
1200
70%
1400
85%
1600
H 100%
1750
1900
2100
2150
Aux
064
0.75
700
875
G
1025
1225
L 55%
1425
70%
1625
1775
85%
1925
H 100%
2125
2175
Aux
072
0.75
700
875
1025
G
1225
1425
L 55%
1625
70%
1775
1925
85%
2125
H 100%
2175
Aux
Factory settings are at recommended G-L-H-Aux speed settings
L-H settings MUST be located within boldface CFM range
“Aux” is factory setting for auxiliary heat and must be equal to or above the “H” setting as well as at least the minimum required
for the auxiliary heat package
“G” may be located anywhere within the airflow table
CFM is controlled /-5% up to the maximum ESP
Max ESP includes allowance for wet coil
9/18/17
Dual Capacity ECM Blower Table without Zoning
MODEL
MAX
ESP
AIR FLOW SPEED SETTINGS
1
2
3
4
5
6
7
8
9
10
11
12
026
0.50
400
475
G
625
725
L
775
850
H
950
1050
1175
Aux
038
0.50
650
700
G
825
950
1075
L
1175
1275
H
1375
1450
1500
Aux
038 W/1HP*
0.75
675
850
G
1025
L
1250
H
1425
1625
1750
1925
2075
Aux
2225
049
0.75
675
850
G
1000
1200
1400
L
1600
H
1750
1900
2100
2150
Aux
064
0.75
700
875
G
1025
1225
1425
1625
L
1775
1925
H
2125
2175
Aux
072
0.75
700
875
1025
G
1225
1425
1625
1775
L
1925
2125
H
2175
Aux
Factory settings are at recommended G-L-H-Aux speed settings
L-H settings MUST be located within boldface CFM range
“Aux” is factory setting for auxiliary heat and must be equal to or above the “H” setting as well as at least the minimum required
for the auxiliary heat package
“G” may be located anywhere within the airflow table
CFM is controlled /-5% up to the maximum ESP
Max ESP includes allowance for wet coil
7/24/17
Blower Performance Data
AFFINITY SERIES
OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL