246653-YTG-E-0108
78
Johnson Controls Unitary Products
NOTE: If the Millennium is VAV with ERV, add the weight of an
exhaust VFD - it will be in the unit.
TABLE 57: UNIT WEIGHTS
COMPONENT
25 TON
30 TON
40 TON
Basic Unit
4410
4565
4845
Gas Heat
267 MBH
180
180
180
533 MBH
320
320
320
800 MBH
-
-
450
Electric Heat
40KW
40
40
40
80KW
105
105
105
108KW
110
110
110
Hot Water Heat
1 Row Coil
70
70
70
2 Row Coil
85
85
85
Steam Heat
1 Row Coil
85
85
85
Blower
Forward Curve Fan (Std Fan)
0
0
0
FC IGV
155
155
175
Air Foil Fan
135
135
155
AF IGV
155
155
180
Motor - Supply Fan
7.5hp
110
-
-
10hp
145
145
145
15hp
200
200
200
20hp
240
240
240
25hp
-
300
300
Supply Fan Motor VFD
See Table 58
Refrigeration
Hi Cap. Evap. Coil
-
50
15
T-Coat Evap.
32
30
40
T-Coat cond.
32
30
40
Hot Gas Bypass
10
10
10
Low Ambient Head Pressure Control
208-230/380/460
5
5
5
575
25
25
25
Filters
6" Rigid
70
70
70
Exhaust
1
1.
If ERV and Supply Fan VAV are selected, add the weight of an
Exhaust VFD, Table 58.
Exhaust Type
Barometric
45
65
65
Modulated
140
275
275
Exhaust Motor
5hp
80
80
80
7.5hp
110
110
110
10hp
145
145
145
15hp
200
200
200
Exhaust Motor VFD
See Table 59
Economizer
Std. Econ.
235
235
235
Econ. w/ERV
50
50
50
Control
Disconnect
15
15
15
110V outlet
55
55
55
Optilogic
20
20
20
Roof Curb
Partial Curb
415
415
415
TABLE 58: SUPPLY FAN MOTOR VFD WEIGHTS
Supply Fan Motor VFD
230V
460V
575V
W/O Bypass
7.5hp
60
25
30
10hp
60
25
30
15hp
75
50
60
20hp
75
50
60
25hp
115
50
60
W/Bypass
7.5hp
155
90
120
10hp
155
90
120
15hp
185
140
155
20hp
185
140
155
25hp
255
140
155
TABLE 59: EXHAUST FAN MOTOR VFD WEIGHTS
Exhaust Fan Motor
230V
460V
575V
W/O Bypass
5hp
15
10
20
7.5hp
50
15
20
10hp
50
15
20
15hp
65
40
50
FIGURE 27 - CENTER OF GRAVITY
TABLE 60: UNIT CENTER OF GRAVITY
MODEL
25
TON
30
TON
40
TON
X
Y
X
Y
X
Y
B
ASIC
U
NIT
99”
48”
100”
47”
96”
46"
B
ASIC
U
NIT
/
W
E
CON
.
110”
48”
110”
47”
100”
46"
B
ASIC
U
NIT
/
W
E
CON
. & G
AS
OR
E
LECT
. H
EAT
,
S
TEAM
OR
H
OT
W
ATER
H
EAT
104”
48”
104”
46”
99”
45"
B
ASIC
U
NIT
/
W
E
CON
. & G
AS
OR
E
LECT
. H
EAT
, &
P
OWER
E
XHAUST
118”
47”
114”
46”
111”
45"
BACK
CENTER OF
GRAVITY
CONDENSER
COIL END
FRONT
X
Y
"
240"
A
B
C
D
92