246653-YTG-E-0108
56
Johnson Controls Unitary Products
TABLE 42: COMPONENT STATIC RESISTANCE
1, 2
COMPONENT COIL
LOSSES
CFM
6,000
8,000
10,000
12,000
14,000
16,000
18,000
S
TD
. 25 T
ON
, D
RY
-0.06
-0.08
-0.10
-0.13
-
-
-
S
TD
. 25 T
ON
, W
ET
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
S
TD
. 30 T
ON
, D
RY
-0.045
-0.075
-0.112
-0.157
-0.207
-0.264
-0.326
S
TD
. 30 T
ON
, W
ET
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
H
I
C
AP
30 T
ON
, D
RY
-0.019
-0.035
-0.052
-0.073
-0.098
-0.124
-0.155
H
I
C
AP
30 T
ON
, W
ET
0.042
0.069
0.103
0.142
0.186
0.236
0.290
S
TD
. 40 T
ON
, D
RY
-0.030
-0.051
-0.076
-0.106
-0.140
-0.177
-0.219
S
TD
. 40 T
ON
, W
ET
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
H
I
C
AP
40 T
ON
, D
RY
-0.020
-0.033
-0.050
-0.069
-0.092
-0.116
-0.144
H
I
C
AP
40 T
ON
, W
ET
0.023
0.038
0.057
0.079
0.105
0.133
0.164
F
ILTER
L
OSSES
2” TA
OR
HI E
FF
.
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
R
IGID
6”, 65%
0.048
0.080
0.119
0.165
0.217
0.274
0.338
R
IGID
6”, 95%
0.189
0.308
0.448
0.609
0.790
0.988
1.205
IGV L
OSSES
25 & 30 T
ON
0.048
0.085
0.132
0.190
0.259
0.338
0.428
40 T
ON
0.027
0.049
0.076
0.110
0.149
0.195
0.246
G
AS
H
EAT
267 MBH H
EAT
0.106
0.141
0.177
0.212
0.247
0.283
0.318
533 MBH H
EAT
0.212
0.283
0.353
0.424
0.495
0.566
0.636
800 MBH H
EAT
0.318
0.423
0.531
0.636
0.741
0.849
0.954
E
LECTRIC
H
EAT
0.050
0.100
0.150
0.310
0.430
0.530
0.680
E
CONOMIZER
0.063
0.104
0.153
0.210
0.276
0.349
0.429
P
OWER
E
XHAUST
0.046
0.081
0.127
0.182
0.248
0.324
0.410
1.
Baseline losses based on system/cabinet effects, wet standard coil and 2” throwaway filters at 70°F, 0 feet elevation with standard air.
2.
See Tables 10, 12, 15, 18, 21 and 23 for hot water and steam water coil static resistance.