background image

5894307-UIM-B-0920

Johnson Controls Ducted Systems

3

CODES AND STANDARDS

Follow  all  national  and  local  codes  and  standards  in  addition  to  this
installation manual. The installation must comply with regulations of the
serving gas supplier, local building, heating, and plumbing codes, and
other codes. In the absence of local codes, the installation must comply
with the national codes listed below and all authorities having jurisdic-
tion.
In the United States and Canada, follow all codes and standards for the
following, using the latest edition available:

Safety

• US: National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1 and

the Installation Standards, Warm Air Heating and Air Conditioning
Systems ANSI/NFPA 90B

• CANADA: CAN/CGA-B149.1 National Standard of Canada. Natu-

ral Gas and Propane Installation Codes (NSCNGPIC)

General Installation

• US: Current edition of the NFGC and NFPA 90B. For copies, con-

tact: 

National Fire Protection Association Inc.
Batterymarch Park
Quincy, MA 02269

or for only the NFGC, contact: 

American Gas Association, 
400 N. Capital, N.W. 
Washington DC 20001 

or www.NFPA.org

• CANADA: NSCNGPIC. For a copy, contact:

Standard Sales, CSA International
178 Rexdale Boulevard
Etobicoke, (Toronto) Ontario Canada M9W 1RS

Combustion and Ventilation Air

• US: Section 5.3 of the NFGC, air for Combustion and Ventilation
• CANADA: Part 7 of NSCNGPIC, Venting Systems and Air Supply

for Appliances

Duct Systems

• US  and  CANADA:  Air  Conditioning  Contractors  Association

(ACCA) Manual D, Sheet Metal and Air Conditioning Contractors
Association  National Association  (SMACNA),  or American  Soci-
ety  of  Heating,  Refrigeration,  and  Air  Conditioning  Engineers
(ASHRAE) 1997 Fundamentals Handbook Chapter 32.

Acoustical Lining and Fibrous Glass Duct

• US and CANADA: Current edition of SMACNA and NFPA 90B as

tested by UL Standard 181 for Class 

1

 Rigid Air Ducts

Gas Piping and Gas Pipe Pressure Testing

• US: NFGC - chapters 2, 3, 4, and 9 and National Plumbing Codes
• CANADA: NSCNGPIC Part 5

Electrical Connections

• US: National Electrical Code (NEC) ANSI/NFPA 70
• CANADA: Canadian Electrical Code CSA C22.1

These instructions cover minimum requirements and conform to exist-
ing  national  standards  and  safety  codes.  In  some  instances,  these
instructions  exceed  certain  local  codes  and  ordinances,  especially
those  that  do  not  reflect  changing  residential  and  non-HUD  modular
home construction practices. These instructions are required as a mini-
mum for a safe installation.

INSPECTION

On receiving a unit, inspect the unit for possible damage during transit.
If  damage  is  evident,  note  the  extent  of  the  damage  on  the  carrier’s
freight bill. Make a separate request for inspection by the carrier’s agent
in writing. Before installation, check the unit for screws or bolts that may
have loosened in transit. There are no shipping or spacer brackets that
need to be removed from the interior of this unit.

FURNACE LOCATION AND CLEARANCES

Locate the furnace using the following guidelines:

• Where  a  minimum  amount  of  air  intake/vent  piping  and  elbows

are required

• As centralized with the air distribution as possible
• Where  adequate  combustion  air  is  available  (particularly  when

the appliance is not using outdoor combustion air)

• Where it does not interfere with correct air circulation in the con-

fined space

• Where the outdoor vent terminal is not blocked or restricted. See

the  VENT  CLEARANCES  section.  These  minimum  clearances
must be maintained in the installation.

• Where the unit is installed in a level position side-to-side. The unit

must be installed with a slight (1/4 in.) slope toward the front of
the unit to assist in condensate drainage.

Installation in freezing temperatures:

• Install  the  furnace  in  an area  where  ventilation  facilities  provide

for  safe  limits  of  ambient  temperature  under  normal  operating
conditions. Ambient temperatures must not fall below 32°F (0°C)
unless the condensate system is protected from freezing. 

• Do not allow the return air temperature to be below 55ºF (13°C)

for extended periods. To do so can cause condensation to occur
in the main heat exchanger, leading to premature heat exchanger
failure.

• If  this  furnace  is  installed  in  an  unconditioned  space  and  an

extended  power  failure  occurs,  there  is  potential  for  damage  to
the internal components. Following a power failure, do not oper-
ate the unit until inspection and repairs are performed.

Clearances for access/service:

Provide ample clearances to permit easy access to the unit. The follow-
ing minimum clearances are recommended:

• 24 in. (61 cm) between the front of the furnace and an adjacent

wall or another appliance, when access is required for servicing
and cleaning

• 18 in. (46 cm) at the side where access is required for passage to

the front when servicing or for inspection or replacement of flue/
vent connections.

In all cases, accessibility clearances take precedence over clearances
for combustible materials where accessibility clearances are greater.

Installation in a residential garage:

A  gas-fired  furnace  for  installation  in  a  residential  garage  must  be
installed so the burners and the ignition source are located not less than
18 in. (46 cm) above the floor, and the furnace must be located or pro-
tected to avoid physical damage by vehicles.

 WARNING

The furnace area must not be used as a broom closet or for any other
storage purposes, as a fire hazard may be created. Never store items
such as the following on, near or in contact with the furnace.

1. Spray or aerosol cans, rags, brooms, dust mops, vacuum clean-

ers or other cleaning tools

2. Soap  powders,  bleaches,  waxes  or  other  cleaning  compounds;

plastic  items  or  containers;  gasoline,  kerosene,  cigarette  lighter
fluid, dry cleaning fluids or other volatile fluid

3. Paint thinners and other painting compounds
4. Paper bags, boxes or other paper products

Never operate the furnace with the blower door removed. To do
so  could  result  in  serious  personal  injury  and/or  equipment
damage.

!

 WARNING

Improper installation in an ambient below 32ºF (0.0° C) could create a
hazard, resulting in damage, injury or death.

 WARNING

Liquid  anti-freeze  will  cause  damage  to  internal  plastic  parts  of  this
furnace. 

DO  NOT  attempt  to  winterize  the  furnace  using  liquid

anti-freeze.

!

!

Summary of Contents for TL9E Series

Page 1: ...Wiring Diagram 32 LIST OF TABLES Unit Clearances to Combustibles 4 Cabinet and Duct Dimensions 6 Recommended Filter Sizes High Velocity 600 FPM 7 Ratings and Physical Electrical Data 8 Maximum Equival...

Page 2: ...alled directly on carpeting tile or other combustible material other than wood flooring Check the rating plate and power supply to be sure that the elec trical characteristics match All models use nom...

Page 3: ...t piping and elbows are required As centralized with the air distribution as possible Where adequate combustion air is available particularly when the appliance is not using outdoor combustion air Whe...

Page 4: ...be needed to ensure against drain pan distortion On all installations without a coil a removable access panel is recom mended in the outlet duct such that smoke or reflected light would be observable...

Page 5: ...ION This appliance is certified for line contact when the furnace is installed in the horizontal left or right position The line contact is only permissible between lines that are formed by the inters...

Page 6: ...t and quiet fur nace operation When suspending the furnace use a secure platform constructed of plywood or other building materials secured to the floor or ceiling joists See Figure 5 for details and...

Page 7: ...p leg and ground union is required See Figure 10 For left side supply gas pipe arrangement two 1 2 in elbows and two 1 2 in x 1 1 2 in pipe nipples must be used The arrangement shown in Figure 9 align...

Page 8: ...with DOE test procedures Wire size and overcurrent protection must comply with the National Electrical Code NFPA 70 latest edition and all local codes The furnace must be installed so the electrical...

Page 9: ...Figure 11 LOW VOLTAGE CONTROL WIRING CONNECTIONS Install the field supplied thermostat by following the instructions that come with the thermostat With the thermostat set in the OFF position and the m...

Page 10: ...1 67 LU RQGLWLRQHU 9ROW RPPRQ RPSUHVVRU RQWDFWRU XOO 6WDJH HDW 7 50267 7 Figure 13 Thermostat Chart Single Stage HP with Single Stage Furnaces 6LQJOH 6WDJH R1R XUQDFH 6LQJOH 6WDJH HDW 3XPS 6HFRQG 6WDJ...

Page 11: ...pplied to the hose con nected to the top of the condensate trap Screw the condensate trap to the condensate trap bracket supplied Then thread the hose adapters together below the furnace casing using...

Page 12: ...collec tor box as shown in Figures 16 and 17 The drain hose must not sag or droop after it is installed If glue is used when connecting the intake pipe to the intake coupling the drain opening in the...

Page 13: ...5894307 UIM B 0920 Johnson Controls Ducted Systems 13 Figure 16 Upflow Configuration UPFLOW LEFT SIDE DRAIN UPFLOW RIGHT SIDE DRAIN EXTERNAL CONDENSATE TRAP EXTERNAL CONDENSATE TRAP A1128 001...

Page 14: ...DRAIN AIRFLOW EXTERNAL CONDENSATE TRAP HORIZONTAL LEFT HORIZONTAL RIGHT MOVE RAIN GUTTER HOSE TO THIS POSITION MOVE CONDENSATE DRAIN HOSE TO THIS POSITION INTAKE PIPE DRAIN AIRFLOW EXTERNAL CONDENSAT...

Page 15: ...models are supplied with 2 in 5 1 cm vent connections When the pipe must be increased to 3 in 7 6 cm diameter the transition from 2 in to 3 in must be done as close to the furnace as possible The 2 i...

Page 16: ...igure 18 Elbow Dimensions A A A A STANDARD ELBOW LONG SWEEP ELBOW Table 6 Elbow Dimensions Elbow A Dimension Illustrated in Figure 18 2 in Standard 2 5 16 in 3 in Standard 3 1 16 in 2 in Sweep 3 1 4 i...

Page 17: ...nform to ASTM D2564 for PVC or ASTM D2235 for ABS piping 7 All joints must provide a permanent airtight and watertight seal 8 Install the combustion air and vent piping such that it has a 1 4 in ft 21...

Page 18: ...equirements of the gas supplier 12 in 30 5 cm or in accordance with local installation codes and the requirements of the gas supplier F Clearance to outside corner 12 in 30 5 cm or in accordance with...

Page 19: ...3 to 24 Each furnace must have a separate vent pipe Under NO circumstances can the two vent pipes be tied together The combustion air side of the two pipe configuration shown in Figures 23 and 24 can...

Page 20: ...tion See Figure 28 VENTILATED COMBUSTION AIR Combustion air is supplied through a PVC or ABS pipe that is connected to the PVC coupling attached to the burner box and is terminated in a ventilated att...

Page 21: ...operated damper or manually adjustable louvers are not permitted for use An automatically operated damper or automatically adjustable louvers must be interlocked so the main burner can not operate un...

Page 22: ...kW of the total input rating of all equipment located in the enclosure Not less than the sum of all vent connectors in the confined space The duct must be least the same cross sectional area as the fr...

Page 23: ...s dryers and TURN ON any exhaust fans such as range hoods and bathroom exhausts so they shall operate at maximum speed Open the fireplace dampers Do not operate a summer exhaust fan 4 Follow the light...

Page 24: ...surface igniter glows for about 17 s b After this warm up the induced draft blower starts again and the ignition module opens the main gas valve c After flame is established the supply air blower sta...

Page 25: ...0 300 750 78 46 92 231 25 144 288 720 80 45 90 225 26 138 277 692 82 44 88 220 27 133 267 667 84 43 86 214 28 129 257 643 86 42 84 209 29 124 248 621 88 41 82 205 30 120 240 600 90 40 80 200 31 116 23...

Page 26: ...ws on main gas valve 2 Turn on gas and electrical supplies and follow the operating instruc tions to place the unit back in operation 3 Adjust manifold pressure by adjusting gas valve regulator screw...

Page 27: ...gas sample for analysis it is permissi ble to drill a small hole in the plastic flue pipe for a sample probe pro vided that the vent piping is PVC and the hole is correctly sealed afterwards If using...

Page 28: ...ated on the furnace vesti bule panel near the gas valve This is an automatic reset control that provides over temperature protection due to reduced airflow This may be caused by the following A dirty...

Page 29: ...sensed within 1 0 s The gas valve de energizes and the control begins a recycle operation A normal ignition sequence begins after a 15 s inter purge If during the five recycles the gas supply does not...

Page 30: ...d Red Flashes Indicates incorrect line voltage polarity The polar ity of the incoming power to the furnace is reversed Soft Lockout The control includes a soft lockout that resets automati cally after...

Page 31: ...Door 1 5 ft required GROMMET 3 required HARNESS WIRING HOSE CONDENSATE HOSE RAIN GUTTER KNOB QUARTER TURN 4 required MOTOR MOUNT ORIFICE BURNER PAN CONDENSATE PLUG SEAL 7 8 in PLUG SEAL 2 3 8 in PLUG...

Page 32: ...5894307 UIM B 0920 32 Johnson Controls Ducted Systems SECTION XII WIRING DIAGRAM Figure 33 Wiring Diagram...

Page 33: ...ree Ells of 90 Degree Ells Polarity is correct black is L1 hot white is N neutral Ground wire is connected Line voltage value to furnace volts AC Low voltage value between R and C on furnace control b...

Page 34: ...ure in w c Return Static in w c after Air Side Heating Air Side Cooling Air Side Continuous Fan Clean Up Give owner the owner s manual provided Explain thermostat use and programming if applicable to...

Reviews: