background image

5894307-UIM-B-0920

2

Johnson Controls Ducted Systems

SPECIFIC SAFETY RULES AND PRECAUTIONS

• Only Natural gas is approved for use with this furnace.
• Install  this  furnace  only  in  a  location  and  position  specified  in

these instructions.

• A gas-fired furnace for installation in a residential garage must be

installed as specified in these instructions.

• Provide  adequate  combustion  and  ventilation  air  to  the  furnace

space as specified in these instructions.

• Combustion products must be discharged outdoors. Connect this

furnace  only  to  an  approved  vent  system  as  specified  in  SEC-
TION  VII:  COMBUSTION  AIR  AND  VENT  SYSTEM  of  these
instructions.

• Test for gas leaks as specified in these instructions.

• Always install the furnace to operate within the furnace’s intended

temperature rise range. Connect the furnace only to a duct sys-
tem  that  has  an  external  static  pressure  within  the  allowable
range, as specified on the furnace rating plate.

• When a furnace is installed so supply ducts carry air circulated by

the furnace to areas outside the space containing the furnace, the
return air must also be handled by a duct or ducts sealed to the
furnace casing and terminating outside the space containing the
furnace.

• Do  not  use  this  furnace  for  heating  of  buildings  or  structures

under construction. 

• When installed in a non-HUD-approved modular home or building

constructed  on-site,  combustion  air  must  not  be  supplied  from
occupied spaces.

• The size of  the  unit must  be based on an  acceptable heat  loss

calculation for the structure. ACCA, Manual J, or other approved
methods can be used.

• When  moving  or  handling  this  furnace  before  installation,  leave

the doors on the furnace to provide support and prevent damage
or warping of the cabinet. When lifting the furnace by the cabinet,
support the ends of the furnace rather than lifting the furnace by
the cabinet flanges at the return air openings (bottom or sides) or
supply air opening.

• When lifting the furnace, it is acceptable to use the primary heat

exchanger  tubes  as  a  lifting  point,  provided  that  the  tubes  are
lifted  at  the  front  of  the  heat  exchangers  where  attached  to  the
vestibule  panel.  Do  not  use  the  top  return  bend  of  the  heat
exchangers  as  lifting  points  because  the  tubes  can  shift  out  of
position or their location brackets/baffles.

SAFETY REQUIREMENTS

• Refer to the unit rating plate for the furnace model number, and

then see Figure 6 for return air plenum dimensions. The plenum
must be installed according to the instructions.

• Provide clearances from combustible materials as listed in Table

1.

• Provide clearances for servicing, ensuring that service access is

allowed for both the burners and blower.

• These models 

are not 

CSA listed or approved for installation in a

HUD-approved  modular  home

  or  a 

manufactured  (mobile)

home

.

• This  furnace  is  not  approved  for  installation  in  trailers  or  recre-

ational vehicles.

• Furnaces  for  installation  on  combustible  flooring  must  not  be

installed directly on carpeting, tile, or other combustible material
other than wood flooring.

• Check the rating plate and power supply to be sure that the elec-

trical characteristics match. All models use nominal 115-VAC,    1-
Phase,  60-Hz  power  supply.  DO  NOT  CONNECT THIS APPLI-
ANCE  TO A 50-Hz  POWER  SUPPLY  OR A VOLTAGE ABOVE
130 V.

• Install  the  furnace  so  the  electrical  components  are  protected

from water.

• Installing and servicing heating equipment can be hazardous due

to the electrical components and the gas-fired components. Only
trained and qualified personnel must install, repair, or service gas
heating  equipment.  Untrained  service  personnel  can  perform
basic maintenance functions such as cleaning and replacing the
air filters. When working on heating equipment, observe precau-
tions in the manuals and on the labels attached to the unit and
other safety precautions that apply.

COMBUSTION AIR QUALITY 

(LIST OF CONTAMINANTS)

The furnace requires 

OUTDOOR AIR

 for combustion when the furnace

is located in any of the following environments:

• Buildings with indoor pools
• Chemical exposure
• Commercial buildings
• Hobby or craft rooms
• Laundry rooms
• Furnaces installed near chemical storage areas
• Restricted environments

The furnace requires 

OUTDOOR AIR

 for combustion when the furnace

is located in an area where the furnace is exposed to the following sub-
stances and/or chemicals.

• Antistatic fabric softeners for clothes dryers
• Carbon tetrachloride
• Cements and glues
• Chlorine based swimming pool chemicals
• Chlorinated waxes and cleaners
• Cleaning solvents (such as perchloroethylene)
• Deicing salts or chemicals
• Halogen type refrigerants
• Hydrochloric acid
• Masonry acid washing materials
• Permanent wave solutions
• Printing inks, paint removers, varnishes, etc.
• Water softening chemicals

When outdoor air is used for combustion, the combustion air intake duct
system termination must be located external to the building in an area
where there is no exposure to the substances listed above.

 WARNING

Improper  installation  may  create  a  condition  where  the  operation  of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service, or maintenance
can cause injury or property damage. 

Failure to carefully read and

follow all instructions in this manual can result in furnace mal-
function, death, personal injury, and/or property damage. 

Only a

qualified  contractor,  installer,  or  service  agency  should  install  this
product.

 WARNING

FIRE OR EXPLOSION HAZARD
Failure  to  follow  the  safety  warnings  exactly  could  result  in  serious
injury, death or property damage.
Never  test  for  gas  leaks  with  an  open  flame.  Use  a  commercially
available  soap  solution  made  specifically  for  detection  of  leaks  to
check all connections. A fire or explosion may result causing property
damage, personal injury or loss of life.

IMPORTANT:  

During installation, doors must remain on the furnace

when moving or lifting.

!

!

 CAUTION

This product must be installed in strict compliance with the installation
instructions  and  any  applicable  local,  state,  and  national  codes
including, but not limited to building, electrical, and mechanical codes.

!

Summary of Contents for TL9E Series

Page 1: ...Wiring Diagram 32 LIST OF TABLES Unit Clearances to Combustibles 4 Cabinet and Duct Dimensions 6 Recommended Filter Sizes High Velocity 600 FPM 7 Ratings and Physical Electrical Data 8 Maximum Equival...

Page 2: ...alled directly on carpeting tile or other combustible material other than wood flooring Check the rating plate and power supply to be sure that the elec trical characteristics match All models use nom...

Page 3: ...t piping and elbows are required As centralized with the air distribution as possible Where adequate combustion air is available particularly when the appliance is not using outdoor combustion air Whe...

Page 4: ...be needed to ensure against drain pan distortion On all installations without a coil a removable access panel is recom mended in the outlet duct such that smoke or reflected light would be observable...

Page 5: ...ION This appliance is certified for line contact when the furnace is installed in the horizontal left or right position The line contact is only permissible between lines that are formed by the inters...

Page 6: ...t and quiet fur nace operation When suspending the furnace use a secure platform constructed of plywood or other building materials secured to the floor or ceiling joists See Figure 5 for details and...

Page 7: ...p leg and ground union is required See Figure 10 For left side supply gas pipe arrangement two 1 2 in elbows and two 1 2 in x 1 1 2 in pipe nipples must be used The arrangement shown in Figure 9 align...

Page 8: ...with DOE test procedures Wire size and overcurrent protection must comply with the National Electrical Code NFPA 70 latest edition and all local codes The furnace must be installed so the electrical...

Page 9: ...Figure 11 LOW VOLTAGE CONTROL WIRING CONNECTIONS Install the field supplied thermostat by following the instructions that come with the thermostat With the thermostat set in the OFF position and the m...

Page 10: ...1 67 LU RQGLWLRQHU 9ROW RPPRQ RPSUHVVRU RQWDFWRU XOO 6WDJH HDW 7 50267 7 Figure 13 Thermostat Chart Single Stage HP with Single Stage Furnaces 6LQJOH 6WDJH R1R XUQDFH 6LQJOH 6WDJH HDW 3XPS 6HFRQG 6WDJ...

Page 11: ...pplied to the hose con nected to the top of the condensate trap Screw the condensate trap to the condensate trap bracket supplied Then thread the hose adapters together below the furnace casing using...

Page 12: ...collec tor box as shown in Figures 16 and 17 The drain hose must not sag or droop after it is installed If glue is used when connecting the intake pipe to the intake coupling the drain opening in the...

Page 13: ...5894307 UIM B 0920 Johnson Controls Ducted Systems 13 Figure 16 Upflow Configuration UPFLOW LEFT SIDE DRAIN UPFLOW RIGHT SIDE DRAIN EXTERNAL CONDENSATE TRAP EXTERNAL CONDENSATE TRAP A1128 001...

Page 14: ...DRAIN AIRFLOW EXTERNAL CONDENSATE TRAP HORIZONTAL LEFT HORIZONTAL RIGHT MOVE RAIN GUTTER HOSE TO THIS POSITION MOVE CONDENSATE DRAIN HOSE TO THIS POSITION INTAKE PIPE DRAIN AIRFLOW EXTERNAL CONDENSAT...

Page 15: ...models are supplied with 2 in 5 1 cm vent connections When the pipe must be increased to 3 in 7 6 cm diameter the transition from 2 in to 3 in must be done as close to the furnace as possible The 2 i...

Page 16: ...igure 18 Elbow Dimensions A A A A STANDARD ELBOW LONG SWEEP ELBOW Table 6 Elbow Dimensions Elbow A Dimension Illustrated in Figure 18 2 in Standard 2 5 16 in 3 in Standard 3 1 16 in 2 in Sweep 3 1 4 i...

Page 17: ...nform to ASTM D2564 for PVC or ASTM D2235 for ABS piping 7 All joints must provide a permanent airtight and watertight seal 8 Install the combustion air and vent piping such that it has a 1 4 in ft 21...

Page 18: ...equirements of the gas supplier 12 in 30 5 cm or in accordance with local installation codes and the requirements of the gas supplier F Clearance to outside corner 12 in 30 5 cm or in accordance with...

Page 19: ...3 to 24 Each furnace must have a separate vent pipe Under NO circumstances can the two vent pipes be tied together The combustion air side of the two pipe configuration shown in Figures 23 and 24 can...

Page 20: ...tion See Figure 28 VENTILATED COMBUSTION AIR Combustion air is supplied through a PVC or ABS pipe that is connected to the PVC coupling attached to the burner box and is terminated in a ventilated att...

Page 21: ...operated damper or manually adjustable louvers are not permitted for use An automatically operated damper or automatically adjustable louvers must be interlocked so the main burner can not operate un...

Page 22: ...kW of the total input rating of all equipment located in the enclosure Not less than the sum of all vent connectors in the confined space The duct must be least the same cross sectional area as the fr...

Page 23: ...s dryers and TURN ON any exhaust fans such as range hoods and bathroom exhausts so they shall operate at maximum speed Open the fireplace dampers Do not operate a summer exhaust fan 4 Follow the light...

Page 24: ...surface igniter glows for about 17 s b After this warm up the induced draft blower starts again and the ignition module opens the main gas valve c After flame is established the supply air blower sta...

Page 25: ...0 300 750 78 46 92 231 25 144 288 720 80 45 90 225 26 138 277 692 82 44 88 220 27 133 267 667 84 43 86 214 28 129 257 643 86 42 84 209 29 124 248 621 88 41 82 205 30 120 240 600 90 40 80 200 31 116 23...

Page 26: ...ws on main gas valve 2 Turn on gas and electrical supplies and follow the operating instruc tions to place the unit back in operation 3 Adjust manifold pressure by adjusting gas valve regulator screw...

Page 27: ...gas sample for analysis it is permissi ble to drill a small hole in the plastic flue pipe for a sample probe pro vided that the vent piping is PVC and the hole is correctly sealed afterwards If using...

Page 28: ...ated on the furnace vesti bule panel near the gas valve This is an automatic reset control that provides over temperature protection due to reduced airflow This may be caused by the following A dirty...

Page 29: ...sensed within 1 0 s The gas valve de energizes and the control begins a recycle operation A normal ignition sequence begins after a 15 s inter purge If during the five recycles the gas supply does not...

Page 30: ...d Red Flashes Indicates incorrect line voltage polarity The polar ity of the incoming power to the furnace is reversed Soft Lockout The control includes a soft lockout that resets automati cally after...

Page 31: ...Door 1 5 ft required GROMMET 3 required HARNESS WIRING HOSE CONDENSATE HOSE RAIN GUTTER KNOB QUARTER TURN 4 required MOTOR MOUNT ORIFICE BURNER PAN CONDENSATE PLUG SEAL 7 8 in PLUG SEAL 2 3 8 in PLUG...

Page 32: ...5894307 UIM B 0920 32 Johnson Controls Ducted Systems SECTION XII WIRING DIAGRAM Figure 33 Wiring Diagram...

Page 33: ...ree Ells of 90 Degree Ells Polarity is correct black is L1 hot white is N neutral Ground wire is connected Line voltage value to furnace volts AC Low voltage value between R and C on furnace control b...

Page 34: ...ure in w c Return Static in w c after Air Side Heating Air Side Cooling Air Side Continuous Fan Clean Up Give owner the owner s manual provided Explain thermostat use and programming if applicable to...

Reviews: