background image

835959-UIM-D-0814

Johnson Controls Unitary Products

5

10.Release the refrigerant charge into the system in accordance with

the SYSTEM CHARGE procedures. Open the liquid line base valve
first and let pressures equalize. Then, open the suction line base
valve. When opening either valve, use an appropriate hex head
wrench and back seat the base valve by turning it counter clockwise
until it stops against the chamfered retaining wall, and then turn it
back 1/8 turn. If the service valve is a ball valve, use an adjustable
end wrench to turn valve stem one-quarter turn counterclockwise to
open. Do not overturn (or the valve stem may break or become dam-
aged).

11.To prevent leaks, replace base valve caps finger tight, and then

tighten the cap an additional 1/12 turn (1/2 hex flat).

12.Replace cap on service ports. Do not remove the flare caps from the

service ports except when necessary for servicing the system. 

13. See “System Charge” section for checking and recording system

charge.

SECTION IV: INDOOR EXPANSION DEVICE

THERMOSTATIC EXPANSION VALVE 

(

TXV) INSTAL-

LATION

Before accomplishing the following procedures, verify the proper TXV
kit to be installed on the coil. Refer to supplied Tabular Data Sheet for
specific TXV kit and indoor coil match up. 

The following are basic steps for installation of a TXV kit. For detailed
instructions, refer to the Installation Instructions accompanying the TXV
kit.

Install TXV kit as follows:

1. Relieve nitrogen holding charge by depressing the Schrader valve

stem located in the end of the suction line. After nitrogen holding
charge is completely discharged, cut off the spundown copper end of
the suction line to allow installation of the field supplied suction line.

2. Slide indoor coil out of cabinet far enough to gain access to equal-

izer fitting on the suction line.

3. Before the suction line from the outdoor unit is brazed to the indoor

coil suction line, remove and discard black plastic cap from equalizer
fitting on the indoor coil suction line.

4. Loosen and remove distributor cap seal.

5. Install the TXV to the distributor assembly by hand tightening, and

then turn fitting an additional 1/4 turn to seal. 

Do not overtighten fit-

tings.

6. Install the liquid line to the top of the TXV using the liquid line fitting

which is supplied with the indoor coil. Hand modify the liquid line to
align with casing opening. Hand tighten the liquid line on the TXV,
and tighten an additional 1/4 turn to seal.

7. Install the TXV equalizer line onto the equalizer fitting of the suction

line. Hand tighten the 1/4” SAE nut to the equalizer fitting, and
tighten an additional 1/3 turn to seal.

8. Install the TXV bulb to the suction line near the equalizer line, using

the bulb clamp(s) furnished with the TXV assembly kit. Ensure the
bulb is making maximum contact.

a.

Install the bulb on the suction line near the equalizer line with
the bulb horizontal to the suction line. On a suction line under
7/8” Outside Diameter (O.D.), install the bulb on top of the
line. On a suction line 7/8” O.D. or larger, install the bulb at
about the 2 or 10 o'clock position.

b.

If bulb must be installed vertically to the suction line, position

the bulb at least 16 inches (40.6 cm) from any bend and on
the opposite side of the bend plane. Positioned the bulb with
the bulb tail at the top, so that the bulb acts as a reservoir.

c.

Use thermal insulation provided to protect the bulb from the

effect of the surrounding ambient temperature. Cover the
bulb completely to insulate from air-stream.

9. Slide indoor coil back into cabinet.

10.Leak test system after outdoor unit is connected.

Do not connect manifold gauges unless trouble is suspected. Approx-
imately 3/4 ounce of refrigerant will be lost each time a standard man-
ifold gauge is connected.

In all cases, do not mount the TXV bulb until after the suction line is
brazed and has had sufficient time to cool.

Dry nitrogen should always be supplied through the tubing while it is
being brazed, because the temperature is high enough to cause oxi-
dation of the copper unless an inert atmosphere is provided. The flow
of dry nitrogen should continue until the joint has cooled. Always use
a pressure regulator and safety valve to insure that only low pressure
dry nitrogen is introduced into the tubing. Only a small flow is neces-
sary to displace air and prevent oxidation.

All connections to be brazed are copper-to-copper and should be
brazed with a phosphorous-copper alloy material such as Silfos-5 or
equivalent. Soft solder is NOT to be used.

NOTICE

Do not install TXV onto distributor assembly until field supplied liquid
line is brazed onto the indoor coil liquid line and cooled.

Do not use slip joint pliers. Damage and distortion of distributor can
prevent proper seal. Use appropriate sized adjustable end wrench.

A schrader valve core MUST NOT be installed in the equalizer fitting
when the TXV kit is installed. Poor system performance or system
failure could result.

Do not install TXV equalizer line onto equalizer fitting nor the TVX
bulb onto the suction vapor line until field supplied suction line is
brazed onto the indoor coil suction line and cooled.

The TXV bulb is to be installed on the suction line near the equalizer
line, using the two bulb clamps furnished with the TXV assembly kit.
The bulb is to make maximum contact. The TXV installation instruc-
tion provide an illustration of proper bulb location.

NOTICE

NOTICE

NOTICE

Summary of Contents for THJF60

Page 1: ...al line lengths Refer to Appli cation Data covering General Piping Recommendations and Refriger ant Line Length Part Number 247077 SECTION II SAFETY This is a safety alert symbol When you see this sym...

Page 2: ...er of hot air into the outdoor unit Provide adequate structural support ADD ON REPLACEMENT RETROFIT When this unit is being used as a replacement for an R 22 unit it is required that the outdoor unit...

Page 3: ...eet The charge given is applicable for total tubing lengths up to 15 feet See Application Data Part Number 247077 for installing tubing of longer lengths and elevation differences PRECAUTIONS DURING L...

Page 4: ...er grommet from the vapor connection at the indoor coil Braze the vapor line to the evaporator vapor connection After the connection has cooled place the rubber grommet back into the mounting position...

Page 5: ...al 1 3 turn to seal 8 Install the TXV bulb to the suction line near the equalizer line using the bulb clamp s furnished with the TXV assembly kit Ensure the bulb is making maximum contact a Install th...

Page 6: ...coil adjustment if any from Tabular Data Sheet 3 Calculate the additional charge for refrigerant piping using the Tabu lar Data Sheet if line length is greater than 15 feet 4 6 m 4 Total system charge...

Page 7: ...itches and over current protection must be supplied by the installer Wire size should be sized per NEC requirements The complete connection diagram and schematic wiring label is located on the inside...

Page 8: ...he recommended air flow settings for each size condensing unit Set the cooling speed per the instructions for the air handler or furnace by selecting the correct COOL and ADJUST or ADJ taps Verify the...

Page 9: ...4 Volt Hot W3 Third Stage Heat COM 24 Volt Common R 24 Volt Hot W1 First Stage Aux Heat W2 Second Stage Aux Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve Energ...

Page 10: ...uxiliary Heat COM 24 Volt Common R 24 Volt Hot W1 First Stage Aux Heat W2 Second Stage Aux Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve Energized in Cool X L...

Page 11: ...energized only when the unit is not running If the main switch is disconnected for long peri ods of shut down do not attempt to start the unit until 8 hours after the switch has been connected This wi...

Page 12: ...GRN GREEN GRY GREY ORG ORANGE PUR PURPLE RED RED WHT WHITE YEL YELLOW Y B YEL BLK LEGEND AS AMBIENT SENSOR CAP CAPACITOR COMP COMPRESSOR CC CONTACTOR COIL CCH CRANKCASE HEATER DS DISCHARGE SENSOR HPS...

Page 13: ...plicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is connecte...

Page 14: ...p Cut Out Balance Point Defrost Curve Y2 Lock FFUEL Switch Point Hot Heat Pump Fill in the information ie ON OFF or the appropriate Value for the fields that apply to the defrost control board install...

Page 15: ...plain operation of system to equipment owner Explain the importance of regular filter replacement and equipment maintenance Owner Education Provide owner with the owner s manual Explain thermostat use...

Page 16: ...change without notice Published in U S A 835959 UIM D 0814 Copyright 2014 by Johnson Controls Inc All rights reserved Supersedes 835959 UIM C 0614 York International Corp 5005 York Drive Norman OK 73...

Reviews: