![background image](http://html1.mh-extra.com/html/york/sunline-2000/sunline-2000_user-manual_4236528003.webp)
UNIT COOLING CAPACITIES AND POWER REQUIREMENTS
Model
HCE
Suction Press. & Corresponding
Temp. @ Saturation
Temperature of Air on Condenser Coil,
°
F
65
75
85
95
105
115
PSIG
°
F
MBH
KW*
MBH
KW*
MBH
KW*
MBH
KW*
MBH
KW*
MBH
KW*
090
61.6
35
98
7.0
92
7.2
85
7.4
78
7.6
71
7.8
64
8.1
68.5
40
108
7.5
101
7.7
94
7.9
87
8.1
80
8.4
72
8.7
76.0
45
116
7.9
109
8.1
102
8.3
95
8.6
87
8.9
79
9.3
84.0
50
123
8.2
116
8.4
109
8.7
102
9.0
94
9.4
86
9.9
120
61.6
35
134
10.0
126
10.3
117
10.6
108
10.9
98
11.2
88
11.6
68.5
40
148
10.7
139
11.0
129
11.3
119
11.6
109
11.9
99
12.4
76.0
45
160
11.2
150
11.5
140
11.8
130
12.2
120
12.6
110
13.1
84.0
50
170
11.6
159
11.9
149
12.3
139
12.7
129
13.2
119
13.8
150
61.6
35
140
9.4
133
10.4
127
11.3
119
12.6
112
13.8
105
15.1
68.5
40
151
9.6
144
10.6
137
11.5
129
12.8
122
14.1
114
15.4
76.0
45
165
9.9
156
10.9
148
11.8
140
13.1
132
14.4
124
15.8
84.0
50
178
10.2
169
11.2
159
12.1
151
13.4
142
14.8
134
16.1
*
Includes compressor and condenser fan motor(s).
550.23-TG1Y
Unitary Products Group
3