APPLICATION DATA

LIMITATION

MIN.

MAX.

Voltage Variation 

1

208/230-3-60

187V

252V

460-3-60

432V

504V

575-3-60

540V

630V

380/415-3-50

342V

456V

Ambient Air on Condenser Coil.

45

°

F

2

115

°

F

3

Suction Pressure at Compressor and
Corresponding Temp. at Saturation

57.5 psig

32.0

°

F

90.0 psig

53.5

°

F

PHYSICAL DATA

ELECTRICAL DATA

MODEL

(HCE)

VOLTAGE

CODE

COMPRESSOR

CONDENSER FAN MOTOR

UNIT

AMPACITY

(AMPS)

MAX.

FUSE
SIZE

1

(AMPS)

MIN.

WIRE
SIZE

2

(AWG)

POWER

SUPPLY

RLA

LRA

POWER
SUPPLY

HP

QTY

FLA

090

25

208/230-3-60

29.5

260

208/230-1-60

3/4

1

4.2

37.4

50

8

46

460-3-60

14.1

128

460-1-60

3/4

1

2.3

18.2

25

12

58

575-3-60

12.8

104

575-1-60

3/4

1

1.8

16.2

20

12

120

25

208/230-3-60

34.6

300

208/230-1-60

1/2

2

3.0

45.0

60

6

46

460-3-60

19.2

146

460-1-60

1/2

2

1.8

25.2

30

10

58

575-3-60

14.1

124

460-1-60

3

1/2

2

1.8

18.7

25

12

150

25

208/230-3-60

41.4

312

208/230-1-60

1/2

2

3.0

52.6

70

6

46

460-3-60

20.0

140

460-1-60

1/2

2

1.8

26.1

35

8

58

575-3-60

16.4

108

460-1-60

3

1/2

2

1.8

21.3

30

10

1

Dual element.

2

Based on three, 60

°

C insulated copper conductors in steel conduit.

3

Unit includes a 575 to 460-volt transformer.

ARI RATINGS

1

CONDENSING

UNIT MODEL

INDOOR  BLOWER

 UNIT MODEL

SYSTEM

MBH

SYSTEM

EER

CONDENSING UNIT

SOUND LEVEL

2

(bels)

H4CE090A25, 46

K4EU090A33

88

3

9.2

9.0

K3EU120A33

95

3

9.5

H2CE120A25, 46

K3EU120A33

120

4

8.9

9.0

K1EU180A33

132

4

9.5

H1CE150A25, 46

K1EU180A33

140

4

9.0

-

1

Ratings are in accordance with ARI Standard 210.

3

Deduct 0.5 MBH for units operating at 208 volts.

2

Sound ratings are in accordance with ARI Standard 270.

4

Deduct 1.0 MBH for units operating at 208 volts.

EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh
            per watt (Btuh/watt).

1

Utilization range ‘‘A’’ in accordance with ARI Standard 110.

2

Low Ambient accessories are available to permit stable

  system operation at ambient temperatures down to 0

°

F.

3

These units can operate at a maximum ambient temperature

  of 120

°

F providing the wet bulb temperature of the air entering

  the evaporator coil does not exceed 67

°

F.

NOTE:  Refer to Form 550.23-N1Y for refrigerant piping limitations.

Model

HCE

Compressor

(Tandem)

Condenser

Unit Weight

(Lbs.)

Charge,

Lbs.-Oz.

(Refrigerant-22)

Fan (Propeller)

Fan Motor

1

Coil

3

Rating

(Tons)

Cap.

(Stages)

Qty.

Dia.
(in.)

Nom.

CFM

Blades

Qty. HP RPM Rotation

2

Face

Area

(Ft.

2

)

Finned
Length

(in.)

Rows

High

Ship. Oper. Holding Oper.

4

Qty.

Pitch

(Deg.)

090

7-1/2

1

1

24

4677

3

29

1

3/4 1120

CW

18.7

90

30

365

360

1 - 12

12 - 0

5

120

10

1

2

24

8034

3

27

2

1/2 1110

CCW

23.8

96

36

510

505

2 - 12

17 - 0

6

150

12-1/2

1

2

24

7950

3

27

2

1/2 1110

CCW

23.8

96

36

510

505

-

19-5

1

These PSC motors are directly connected to the condenser fans and have inherent protection, ball bearings and a 48 frame.

2

When viewing the shaft end of the motor.

3

These condenser coils have 2 rows of 3/8" OD copper tubes and 16 aluminum fins per inch.

4

Includes matched indoor blower unit but no piping.

5

Add an additional 1 lb. charge when used with KEU120 (10 ton) indoor units.

6

Add an additional 5 lbs. charge when used with KEU180 (15 ton) indoor units.

550.23-TG1Y 

2

Unitary Products Group

Summary of Contents for Sunline 2000

Page 1: ...nt FEATURES Condenser coil constructed of copper tubes and aluminum fins for durability and long lasting efficient operation Permanently attached base rails with fork lift slots and lifting holes This...

Page 2: ...ing at 208 volts 2 Sound ratings are in accordance with ARI Standard 270 4 Deduct 1 0 MBH for units operating at 208 volts EER Energy Efficiency Ratio at full load the cooling capacity in Btu s per ho...

Page 3: ...02 9 0 94 9 4 86 9 9 120 61 6 35 134 10 0 126 10 3 117 10 6 108 10 9 98 11 2 88 11 6 68 5 40 148 10 7 139 11 0 129 11 3 119 11 6 109 11 9 99 12 4 76 0 45 160 11 2 150 11 5 140 11 8 130 12 2 120 12 6 1...

Page 4: ...73 109 13 1 109 90 69 62 118 11 6 118 117 95 73 110 12 1 110 110 91 70 101 12 6 101 101 86 66 57 112 11 2 112 112 111 89 104 11 6 104 104 104 85 95 12 1 95 95 95 81 4000 72 131 12 3 92 72 123 12 8 88...

Page 5: ...ondenser fan motor s UNIT OPERATION 7 1 2 10 12 1 2 TON When the external control calls for cooling at terminal Y1 1 The system controller SC is energized The system con troller starts the tandem comp...

Page 6: ...ITS An auto transformer and temperature control maintain stable system operation by reducing the speed of the condenser fan motor TYPICAL FIELD WIRING w AIR HANDLER TYPICAL FIELD WIRING WITH 7 1 2 TON...

Page 7: ...8 16 1 2 12 1 2 Ton 70 1 8 32 29 5 8 16 1 2 HCE120 10 TON HCE150 12 1 2TON CLEARANCES Overhead Top 1 120 Front Piping and Access Panels 30 Left Side 24 Right Side 24 Rear 24 Bottom2 0 1 Units must be...

Page 8: ...POINT LOADS HCE090 HCE120 150 UNIT 4 POINT LOAD LBS TOTAL A B C D 120 505 110 151 141 103 150 510 111 152 143 104 550 23 TG1Y 8 Unitary Products Group...

Page 9: ...mounted on isolators to limit the transmission of sound and vibration IV Condenser and Fans A Fan motors shall be single phase direct drive with propeller type condenser fans which discharge air verti...

Page 10: ...iciently to operate the indoor fan C All condenser fan motors and the secondary of each transformer shall be grounded VIII Accessories and Options A Head Pressure Control Shall include a condenser fan...

Page 11: ...550 23 TG1Y Unitary Products Group 11...

Page 12: ...up P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1998 All Rights Reserved Code EBY EGY 550 23 TG1Y Superse...

Reviews: