GUIDE SPECIFICATION

Furnish and install YORK Sunline air-cooled condensing units
or equivalent, suitable for ground or roof mounting.  Units shall
have capacities and efficiencies as outlined in the schedules
shown on the plans and shall be installed in accordance with
all applicable national and local codes.  

I. General

A. Units shall be manufactured in a facility registered under

the ISO 9002 manufacturing quality standard.

B. Units shall be UL and CSA approved.

C Unit shall be packaged to allow outdoor storage

D. Hermetic compressors shall be covered by a five year

limited warranty.

All other unit parts shall be covered by a full year limited
warranty.

II. Unit Cabinet

A. Cabinet shall be constructed of 18 gauge, zinc-coated

steel, finished with a powder paint process capable of
withstanding a minimum of 750 salt spray hours
according to ASTM B117.

B. Cabinet screws shall comply with the ASTM B117 salt

spray test for a minimum of 750 hours.

C. Panels shall be removable for easy access to all internal

components during maintenance and service.

D. Cabinet shall feature a separate access panel for the

controls so that unit airflow need not be disturbed during
servicing.

E. Permanently attached base rails shall have 3-way fork

lift access and lifting holes for ease of installation.

III. Compressor

A. Compressor shall be a tandem reciprocating or scroll

compressor with integral motor overload protection.

B. Reciprocating compressors shall have an integral

crankcase heater to keep refrigerant from diluting the
compressor oil in the sump (H*CE150 is a scroll).
Crankcase heater shall be field replaceable without
removal of the charge.

C. Compressor shall be mounted on isolators to limit the

transmission of sound and vibration.

 IV. Condenser and Fans

A. Fan motors shall be single phase, direct-drive with

propeller-type condenser fans which discharge air
vertically upward.

B. Units with more than one condenser fan motor shall be

wired to distribute the single phase motor loads across
the 3 phase power supply, thus minimizing phase
imbalance on multiple unit installations.

C. Fan motors shall totally enclosed with permanently

lubricated ball-bearings for longer wear during start and
stop cycles.

D. Fan motors shall have inherent overload protection.

E. Coil shall be constructed of rifled copper tubing

mechanically expanded and bonded to louvered
aluminum fins.  Coil shall include an integral subcooler.

V.Refrigeration Components - Refrigeration system shall

contain the following:

High and low pressure cut-outs

Service valves to ease installation and recovery of
refrigerant

External ports to accomodate gauge lines, allowing for
easy servicing

Filter drier shipped in unit for field installation

Holding charge of R-22 

VI. Controls - Unit controls shall include:

A. 24 volt control circuit with terminal blocks.

B. Color-coded wiring for easy service and troubleshooting.

C. Independent line break thermal protection for the

condenser fans.

C. 5 minute anti-short cycle timer to protect the compressor

from frequent cycling.

D. Unit safety lockouts which automatically reset from the

thermostat once the anti-short cycle timer is satisfied.
Safety lockouts will also generate a 24 volt signal to the
"X" terminal, allowing notification to the user via the
thermostat fault light (if present).  These safety lockouts
shall include:

1.  High refrigerant pressure

2. Low refrigerant pressure (low refrigerant pressure shall

be  bypassed for the first 90 seconds of operation to
eliminate  nuisance trips).

550.23-TG1Y 

Unitary Products Group

9

Summary of Contents for Sunline 2000

Page 1: ...nt FEATURES Condenser coil constructed of copper tubes and aluminum fins for durability and long lasting efficient operation Permanently attached base rails with fork lift slots and lifting holes This...

Page 2: ...ing at 208 volts 2 Sound ratings are in accordance with ARI Standard 270 4 Deduct 1 0 MBH for units operating at 208 volts EER Energy Efficiency Ratio at full load the cooling capacity in Btu s per ho...

Page 3: ...02 9 0 94 9 4 86 9 9 120 61 6 35 134 10 0 126 10 3 117 10 6 108 10 9 98 11 2 88 11 6 68 5 40 148 10 7 139 11 0 129 11 3 119 11 6 109 11 9 99 12 4 76 0 45 160 11 2 150 11 5 140 11 8 130 12 2 120 12 6 1...

Page 4: ...73 109 13 1 109 90 69 62 118 11 6 118 117 95 73 110 12 1 110 110 91 70 101 12 6 101 101 86 66 57 112 11 2 112 112 111 89 104 11 6 104 104 104 85 95 12 1 95 95 95 81 4000 72 131 12 3 92 72 123 12 8 88...

Page 5: ...ondenser fan motor s UNIT OPERATION 7 1 2 10 12 1 2 TON When the external control calls for cooling at terminal Y1 1 The system controller SC is energized The system con troller starts the tandem comp...

Page 6: ...ITS An auto transformer and temperature control maintain stable system operation by reducing the speed of the condenser fan motor TYPICAL FIELD WIRING w AIR HANDLER TYPICAL FIELD WIRING WITH 7 1 2 TON...

Page 7: ...8 16 1 2 12 1 2 Ton 70 1 8 32 29 5 8 16 1 2 HCE120 10 TON HCE150 12 1 2TON CLEARANCES Overhead Top 1 120 Front Piping and Access Panels 30 Left Side 24 Right Side 24 Rear 24 Bottom2 0 1 Units must be...

Page 8: ...POINT LOADS HCE090 HCE120 150 UNIT 4 POINT LOAD LBS TOTAL A B C D 120 505 110 151 141 103 150 510 111 152 143 104 550 23 TG1Y 8 Unitary Products Group...

Page 9: ...mounted on isolators to limit the transmission of sound and vibration IV Condenser and Fans A Fan motors shall be single phase direct drive with propeller type condenser fans which discharge air verti...

Page 10: ...iciently to operate the indoor fan C All condenser fan motors and the secondary of each transformer shall be grounded VIII Accessories and Options A Head Pressure Control Shall include a condenser fan...

Page 11: ...550 23 TG1Y Unitary Products Group 11...

Page 12: ...up P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1998 All Rights Reserved Code EBY EGY 550 23 TG1Y Superse...

Reviews: