background image

ENGLISH

8

ø 65 mm

PARTS INSTALLATION

NOTES

INDOOR UNIT

INSTALLATION PROCEDURE

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

 Fixing

   Place the installation guide pattern on the designated 

installation place and mark the hole position.

   Drill a hole and mount installation plate.

   After determining the pipe hole position. Drill the hole    

at a slight downward slant towards the outdoor side.

Outdoor

Indoor

Note: 

When installing the 
refrigerant pipes from 
others side. A hole 
must be place to 
allow fall towards the 
outdoor unit.

  Make 6 mm 4-6 holes, in the wall at the four corners of 

mouting plate (bracket) then insert appropriate mouting 
devices.

  Install the mounting plate using 4-6 pieces of mounting 

screw securely at four corners and tighten the screw 
completely. Do not over tighten the screws and deform 
the back plate.

CAUTIONS

  Ensure that the space around the left and right of the 

indoor unit is more than 12cm.

 

The indoor unit should be installed allowing a minimum 
clearance of 15cm from the ceiling.

  Use a stud 

fi

 nder to locate studs to prevent unnecessary 

damage to the wall.

  A minimum pipe run of 3 metres is required to minimise 

vibration & excessive noise.

  The indoor unit should be installed on the wall at a height 

of 2.3 metres or more from the 

fl

 oor .

  A, B and C directions should be free from obstructions.

NOTES

  This illustration is for explanation purposes only.

  Copper lines must be insulated independently.

C

B

A

1

2

3

5

4

7

6

Self-tapping screw B
ST3.9X10

Loop the 
connective 
cable.

Remote Controller

Air F

ilter

Remote Controller
holer

30cm

 mini

mum

200cm m

inimum

60cm m

inimum

30cm m

inimum

12cm minim

um

12cm min

imu

m

15cm mi

nimum

60cm minimum

Except the above parts provided, the other parts needed 
during installation you must purchase.

750

45

250

Right refrigerant
pipe hole 

65

Installation plate

Indoor unit outline

Left refrigerant
pipe hole 

65

150mm or more to ceiling

120mm or more
to wall

120mm or more
to wall

150mm or more to ceiling

Indoor unit outline

Installation plate

920

293

Right refrigerant
pipe hole 

65

Left refrigerant
pipe hole 

65

120mm or more
to wall

120mm or more
to wall

(

12000Btu/h model)

MODEL 07-12

MODEL 18

Number

Name of part

Q’ty

1

Installation plate

1

2

Clip anchor

8

3

Self-tapping screw A ST3.9X25

8

4

Connecting

pipe

assembly

Liquid side ø 6.35

Parts you

must

purchase

Gas side

ø 9.53 (<12000Btu/h model)

ø 12.7 (21000Btu/h model > Cooling 
capacity 

f

 

12000Btu/h model) 

ø 16 (

f

21000Btu/h model)

5

Remote controller

1

6

Self-tapping screw B ST3.9X10

2

7

Remote controller holder

1

8

Seal

1

9

Drain joint

1

J277-EN.indd   8

J277-EN.indd   8

26.12.2005   15:15:19 Uhr

26.12.2005   15:15:19 Uhr

Summary of Contents for RLCA-RLHA 07-30

Page 1: ...ELS RLCA RLHA 07 30 RLCB RLHB 07 28 RACC RAHC 07 28 MINISPLIT HIGH WALL AIR CONDITIONER EN 035M80147 000 The units comply with one or more of the following marks see unit for details J277 EN 1 J277 EN...

Page 2: ...tent reli ability in product service and support through superior quality service culture and distinctive technology R22 R407C 50Hz 60Hz 50Hz Set RLCAxxFSAAAR RLCAxxFSAADR RLCBxxFSAAAR RLHAxxFSAAAR RL...

Page 3: ...ous and can cause injury Installation and maintenance of this air conditioning system should only be carried out by trained and qualified personnel After unpacking please check the unit carefully for...

Page 4: ...ERATURE indicator Displays the temperature settings when the air conditioner is operational 4 OPERATION indicator This indicator flashes after power is on and illuminates when the unit is in operation...

Page 5: ...conditioner will automatically increase cooling or decrease heating 1 C per hour The set temperature will be steady 2 hours later The fan speed will be automatically controlled DRYING OPERATION The d...

Page 6: ...ord and the main breaker capacity are sufficient and the installation area is sufficient and complies with the requirements Check that the power supply available agrees with name plate voltage Electri...

Page 7: ...48 115 90 266 272 298 285 290 530 110 62 590 750 RLDA RLJA 07 09 RLDB RLJB 07 09 RADC RAJC 07 RLDA RLJA 12 18 RLDB RLJB 12 RADC RAJC 09 12 RLDA RLJA 24 30 RLDB RLJB 24 28 RADC RAJC 18 28 RLDB RLJB 18...

Page 8: ...tres or more from the floor A B and C directions should be free from obstructions NOTES This illustration is for explanation purposes only Copper lines must be insulated independently C B A 1 2 3 5 4...

Page 9: ...l Carefully arrange pipes so that pipes do not stick out of the rear plate of the indoor unit A B C D E F MODEL 24 30 Right Right Right Right Left Rear Bottom Drain hose Drain hose is flexible and can...

Page 10: ...smitted to the building struc ture Connect the pipe correctly Do not apply the excessive torque Use an appropriate bending tool to form curves and avoid over tightening the refrigerant tubes To preven...

Page 11: ...rs Liquid Cooling GAS Cooling suction Low pressure High pressure Manifold Gas valve Liquid valve Pressure tap Outdoor unit Indoor unit Gas line Liquid line R22 R407C R410A Outdoor heat pump unit insta...

Page 12: ...isconnecting device must have a contact separation of at least 3 mm Models 07 18 Cooling only Power supply Indoor L N 1 2 N 1 2 N Outdoor CAUTIONS Models 07 18 Cooling and Heating L N 1 2 N 3 4 1 2 N...

Page 13: ...1 2 N S L N Terminal block of indoor unit Cooling only type cooling heating type Terminal block of indoor unit Cord clamp To outdoor unit To outdoor unit Terminal block of outdoor unit Wire holding b...

Page 14: ...50Hz 32A 220 230V 60Hz NOTE b Unit has been running at high temperature protection mode for 90 minute High temperature protection mode when coil temperature of indoor unit reaches 55 C outdoor unit w...

Page 15: ...the unit 2 Stop the air conditioner and disconnect power Remove the batteries from the remote controller 3 The outdoor unit requires periodic maintenance and cleaning Do not attempt to do this yourse...

Page 16: ...condition when the air conditioner has not been used for a long time or during first use of the unit 5 A peculiar smell comes out from the indoor unit This is caused by the indoor unit giving off sme...

Page 17: ...s tem 1 Remove charge repair evacuate and recharge 2 Insulate them separately 3 Wait while unit has enough time to cool the room D The compressor runs con tinuously 1 Thermostat adjustment too low in...

Page 18: ...Hz 220 240 1 50 Ph 1 1 1 1 1 1 Fan Air flow m3 h 400 400 450 450 580 580 800 800 1080 1080 1150 1150 Input Power W 39 5 39 5 39 5 39 5 38 5 38 5 53 53 65 65 70 70 Running Current A 0 17 0 17 0 17 0 1...

Page 19: ...0 14 0 14 0 14 0 14 0 24 0 24 0 68 0 68 0 34 0 34 Dimension Height mm 250 250 250 250 265 265 292 292 330 330 330 330 Width mm 710 710 710 710 790 790 920 920 1080 1080 1080 1080 Depth mm 190 190 190...

Page 20: ...Running Current A 0 17 0 17 0 17 0 17 0 2 0 2 0 26 0 26 0 37 0 37 0 32 0 32 Dimension Height mm 250 250 250 250 265 265 292 292 330 330 330 330 Width mm 710 710 710 710 790 790 920 920 1080 1080 1080...

Page 21: ...65 65 70 70 Running Current A 0 17 0 17 0 17 0 17 0 2 0 2 0 26 0 26 0 37 0 37 0 32 0 32 Dimension Height mm 250 250 250 250 265 265 292 292 330 330 330 330 Width mm 710 710 710 710 790 790 920 920 108...

Page 22: ...ces should refrigerant be vented to atmosphere Where appropriate drain the refrigerant oil from each system into a suitable container and dispose of according to local laws and regulations governing d...

Reviews: