![background image](http://html1.mh-extra.com/html/york/predator-bp078/predator-bp078_installation-manual_4151013009.webp)
127421-YIM-C-0606
Unitary Products Group
9
RIGGING AND HANDLING
Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation. Rig
the unit by attaching chain or cable slings to the lifting holes
provided in the base rails. Spreader bars, whose length
exceeds the largest dimension across the unit,
MUST
be
used across the top of the unit.
Units may be moved or lifted with a forklift. Slotted openings
in the base rails are provided for this purpose.
LENGTH OF FORKS MUST BE A MINIMUM OF 60
INCHES.
If a unit is to be installed on a roof curb other than a
YORK roof curb, gasketing must be applied to all
surfaces that come in contact with the unit under-
side.
Before lifting, make sure the unit weight is distrib-
uted equally on the rigging cables so it will lift evenly.
All panels must be secured in place when the unit is
lifted.
The condenser coils should be protected from rig-
ging cable damage with plywood or other suitable
material.
FIGURE 5 -
UNIT 4 POINT LOAD
D
A
C
B
L E F T
F R O N T
TABLE 3:
UNIT WEIGHTS
Model
Shipping Weight (lb.)
Operating Weight
(lb.)
BP078
1104
1099
BP090
895
890
BP102
1178
1173
BP120
1212
1207
BP150
1202
1197
Econ.
85
84
w/ PE
150
148
Elec. Heat
*
49
49
*.
54kW heater.
TABLE 4:
4 POINT LOAD WEIGHT
Model
Location (lbs.)
A
B
C
D
BP078
241
206
300
352
BP090
199
148
232
311
BP102
257
220
321
375
BP120
265
226
330
386
BP150
263
224
327
383
TABLE 5:
6 POINT LOAD WEIGHT
Model
Location (lbs.)
A
B
C
D
E
F
BP078
165
148
134
195
216
241
BP090
139
113
94
147
128
218
BP102
176
158
143
208
231
257
BP120
181
163
147
214
237
264
BP150
180
161
146
213
235
262
FIGURE 6 -
UNIT 6 POINT LOAD
D
A
C
B
E
F
L E F T