127421-YIM-C-0606
44
Unitary Products Group
the defrost thermostats is found to be closed and the DC
enters defrost mode.
When the DC enters the defrost mode, it’s on-board defrost
relay is powered. This energizes both reversing valves, de-
energizes both condenser fan motors and energizes the
unit’s optional electric heater. The DC remains in defrost
mode until either of the following two conditions is met:
1.
Both of the liquid line thermostats are open. Each is set
to open at 55 degrees (+/- 3).
2.
The maximum defrost run time of 10 minutes is met.
The DC also contains a set of test pins. Placing a jumper
across these pins will result in the following actions:
•
If the ASCD timer is active, it is now by-passed, allowing
the compressor to run.
•
If the DC is in a lockout condition, the lockout is reset.
•
If the compressor is running, the DC is forced into defrost
mode. The control will remain in defrost mode for as long
as the jumper is in place. When the jumper is removed,
the control will terminate the defrost mode in the normal
manner as described above.
NOTE:
The DC has two flashing codes which are only initi-
ated if the two pressure switch terminals are open.
As used in the Predator
®
, there is a jumper across
the pressure switch terminals. Therefore the field
should never experience a DC lockout mode unless
that jumper is removed or broken.
a.
the heating requirements of the conditioned space.
ELECTRIC HEAT OPERATION ERRORS
TEMPERATURE LIMIT
If the UCB senses zero volts from the high temperature limit,
the indoor blower motor is immediately energized.
This limit is monitored regardless of unit operation status, i.e.
the limit is monitored at all times.
If the temperature limit opens three times within one hour, it
will lock-on the indoor blower motor and a flash code is initi-
ated (See Table 55).
SAFETY CONTROLS
The UCB monitors the temperature limit switch of electric
heat units.
The control circuit includes the following safety controls:
LIMIT SWITCH (LS)
This control is located inside the heater compartment and is
set to open at the temperature indicated in the Electric Heat
Limit Setting tables. It resets automatically. The limit switch
operates when a high temperature condition, caused by inad-
equate supply air flow occurs, thus shutting down the heater
and energizing the blower.
TABLE 47: ELECTRIC HEAT LIMIT SETTING 50”
CABINET
TABLE 48: ELECTRIC HEAT LIMIT SETTING 42”
CABINET
VOLTAGE
HEATER
kW
LIMIT
SWITCH
OPENS
°F
54
140
54
135
54
150
54
150
150
18
150
24
150
34
150
BP 120 (10)
BP 078, 102
480
BP 078, 102, 120, 150
(6.5, 8.5, 10, 12.5)
BP 120, 150 (10, 12.5)
BP 120, 150 (10, 12.5)
UNIT (TONS)
BP 078, 102
BP 078, 102, 120, 150
BP 078, 102, 120, 150
(6.5, 8.5)
(6.5, 8.5, 10, 12.5)
BP 078, 102, 120, 150
(6.5, 8.5, 10, 12.5)
18
BP 078, 102, 120, 150
34
BP 150 (12.5)
208/230
(6.5, 8.5)
(6.5, 8.5, 10, 12.5)
9
18
150
24
150
(6.5, 8.5)
(6.5, 8.5, 10, 12.5)
(6.5, 8.5, 10, 12.5)
60
0
9
150
150
BP 078, 102
150
(6.5, 8.5, 10, 12.5)
BP 078, 102, 120, 150
24
150
(6.5, 8.5, 10, 12.5)
34
150
BP 078, 102, 120, 150
BP 078, 102, 120, 150
(6.5, 8.5, 10, 12.5)
BP 078, 102, 120, 150
9
140
VOLTAGE
HEATER
kW
LIMIT
SWITCH
OPENS
°F
9
135
18
150
24
165
34
190
9
135
18
150
24
165
34
185
9
135
18
150
24
150
34
185
UNIT (TONS)
480
BP 090
(7.5)
BP 090
(7.5)
600
208/230
BP 090
(7.5)