![York Predator BP078 Installation Manual Download Page 29](http://html1.mh-extra.com/html/york/predator-bp078/predator-bp078_installation-manual_4151013029.webp)
127421-YIM-C-0606
Unitary Products Group
29
TABLE 26: 8-1/2 TON STANDARD MOTOR DOWN SHOT BLOWER PERFORMANCE
*
ESP
†
TURNS OPEN
‡
0
1
2
3
4
5
CFM
W
**
BHP
CFM
W
**
BHP
CFM
W
**
BHP
CFM
W
**
BHP
CFM
W
**
BHP
CFM
W
**
BHP
0.2
-
-
-
4090
1816
1.95
3872
1613
1.73
3681
1448
1.55
3420
1271
1.36
3217
1125
1.21
0.4
3783
1778
1.91
3782
1685
1.81
3548
1489
1.60
3334
1325
1.42
3026
1149
1.23
2796
1010
1.08
0.6
3648
1720
1.84
3387
1529
1.64
3123
1340
1.44
2874
1176
1.26
2495
1002
1.08
-
-
-
0.8
3317
1583
1.70
2903
1354
1.45
2599
1175
1.26
-
-
-
-
-
-
-
-
-
1.0
2788
1385
1.49
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
*.
Blower performance includes two-inch throwaway filters.
†.
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been deducted from the
total static pressure of the blower.
‡.
“Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.
**.
W = Watts
TABLE 27: 8-1/2 TON OPTIONAL MOTOR DOWN SHOT BLOWER PERFORMANCE
*
ESP
†
TURNS OPEN
‡
0
1
2
3
4
5
CFM
W
**
BHP
CFM
W
**
BHP
CFM
W
**
BHP
CFM
W
**
BHP
CFM
W
**
BHP
CFM
W
**
BHP
0.4
-
-
-
-
-
-
-
-
-
4257
2325
2.49
4117
2079
2.23
3878
1816
1.95
0.6
-
-
-
-
-
-
4363
2596
2.78
4114
2248
2.41
3876
1961
2.10
3556
1676
1.80
0.8
-
-
-
4323
2776
2.98
4107
2446
2.62
3838
2104
2.26
3499
1788
1.92
3166
1520
1.63
1.0
4317
2968
3.18
4175
2677
2.87
3803
2276
2.44
3427
1905
2.04
2987
1577
1.69
2710
1355
1.45
1.2
4243
2918
3.13
3869
2486
2.67
3451
2089
2.24
2882
1669
1.79
-
-
-
-
-
-
1.4
3977
2743
2.94
3408
2225
2.39
3051
1888
2.03
-
-
-
-
-
-
-
-
-
1.6
3518
2467
2.65
2790
1927
2.07
2604
1679
1.80
-
-
-
-
-
-
-
-
-
1.8
2868
2125
2.28
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
*.
Blower performance includes two-inch throwaway filters.
†.
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been deducted from the
total static pressure of the blower.
‡.
“Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.
**.
W = Watts
TABLE 28: 10 TON STANDARD MOTOR DOWN SHOT BLOWER PERFORMANCE
*
ESP
†
TURNS OPEN
‡
0
1
2
3
4
5
CFM
W
**
BHP
CFM
W
**
BHP
CFM
W
**
BHP
CFM
W
**
BHP
CFM
W
**
BHP
CFM
W
**
BHP
0.2
-
-
-
-
-
-
-
-
-
3896
1639
1.76
3688
1453
1.56
3447
1268
1.36
0.4
4040
2076
2.23
4005
1934
2.07
3790
1698
1.82
3569
1508
1.62
3333
1330
1.43
3057
1147
1.23
0.6
3890
2006
2.15
3697
1790
1.92
3427
1550
1.66
3152
1356
1.45
-
-
-
-
-
-
0.8
3620
1882
2.02
3324
1629
1.75
2972
1380
1.48
-
-
-
-
-
-
-
-
-
1.0
3227
1708
1.83
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
*.
Blower performance includes two-inch throwaway filters.
†.
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been deducted from the
total static pressure of the blower.
‡.
“Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.
**.
W = Watts