GUIDE SPECIFICATIONS

GENERAL

Units shall be manufactured by Unitary Products in an ISO 
9001 certified facility. Package units give you the flexibility and 
choices you need in today’s market. These packaged cooling/
heating units are designed for outdoor installation. Only utility 
and duct connections are required at the point of installation. 
The two-stage gas fired heaters have stainless steel tubular 
heat exchangers and spark to burner ignition. They are 
available in natural gas with field conversion to propane.

DESCRIPTION

Units shall be factory-assembled, single packaged, Heat 
Pumps with Electric Cooling/Gas Heating units, designed for 
outdoor installation. They shall have built in, equal size, field 
convertible duct connections for supply/return or horizontal 
supply/return. The units shall be factory wired, piped, charged 
with R-410A Refrigerant and factory tested prior to shipment. All 
unit wiring shall be both numbered and color coded. All models 
shall be rated in accordance with DOE and AHRI test 
procedures for both heating and cooling operation. Units shall 
be CSA listed and classified to ANSI Z21.47/CAN/ CSA 2.3 
standards and UL 1995/CAN/CSA No. 236-M90 standards.

Operating Efficiency - 

All Heat Pump models shall be rated 

at 14.0 SEER, 11.0 EER, and 8.0 HSPF for heat pump cool-
ing and heating operation. All models shall be rated at 81.0% 
AFUE for gas heating operation.

Low Operating Sound Level - 

The upward air flow carries 

the normal operating noise up and away from the living area. 
The rigid top panel effectively isolates noise. Isolator 
mounted compressor and the rippled fins of the outdoor coil 
muffle the normal fan motor and compressor operating 
sounds. The unique formed base pan also aids in sound 
attenuation with its structural design. Sound ratings as tested 
under AHRI test procedures shall be less than 77 dbA for all 
models.

UNIT CABINET

Unit cabinet shall be a single piece design, with drip edges and 
no-seam corners to provide optimum water integrity. Unit shall 
have a rigidly mounted outdoor coil guard to provide protection 
from objects and personnel after installation. Indoor blower 
section shall be insulated with foil-faced or foam insulation, 
fastened to prevent insulation from entering the air stream. 
Cabinet panels shall be separate, easily removable for 
servicing and maintenance. Unit shall be built on a formed, 
design base pan, with embossments at critical points to add 
strength and rigidity and to aid in minimizing sound. Full 
perimeter base rails shall be provided to assure reliable transit 
of equipment, overhead rigging, for truck access and proper 
sealing on roof curb applications. Base rails shall be easily 
removable, when required to lower unit height. Filters shall be 
field installed and field provided and be accessible through a 
removable access door, sealed airtight. Units vertical discharge 
and return duct configuration shall be designed to fit between 
standard 24” O.C. beams without modification to building 
structure, duct work and base unit. Condensate pan shall be 
internally sloped and conform to ASHRAE 62-89 self-draining 
standards, with 3/4” NPT female ridged mount connection.

Durable Finish - 

The cabinet shall be is made of G90 galva-

nized steel with a powder paint coating for appearance and 
protection. The pre-treated galvanized steel shall provide a 
better paint-to-steel bond, which resists corrosion and rust 
creep. Powder paint finish shall provide superior corrosion 
resistance (1000 hour salt spray tested).

On Site Flexibility -

 All model sizes shall use a compact 

design cabinet in one of two footprints. This provides installer 
flexibility for placing the proper capacity unit on curbs or pads 
with the smallest footprint after the internal load has been 
determined. Field convertible duct connections from side 
shot to down shot allows the installer to have greater flexibil-
ity with less inventory.

Attractive Appearance -

 A single-piece top cover containing 

a top-discharge outdoor fan arrangement shall be used 
which requires less square footage on installation and pro-
vides a wider variety of installations. The one-piece design 
adds greater water integrity. Rounded corners with water drip 
edges add to the attractive appearance and prevent water 
penetration.

Convertible Airflow Design -

 The bottom duct openings are 

covered when they leave the factory, ready to be used for a 
side supply/side return application. If a bottom supply/bottom 
return application is desired, simply remove the two panels 
from the bottom of the unit and place them in the side supply/
side return duct openings. No panel cutting is required and 
no accessory panel is necessary. Convertible airflow design 
allows maximum field flexibility and minimum inventory.

Utility Connections Made Easy -

 Electric utility access shall 

be provided through the bottom or the side of the unit. Utility 
connections should be made quickly and with a minimum 
amount of field labor. A field supplied and field installed elec-
trical disconnect switch must be installed.

Easy Service Access -

 Individual access panels are pro-

vided in access to all major components - compressors, 
indoor coils, blower, controls/gas heating section, filters, etc. 
that makes servicing easy. Removing these panels allow 
easy removal of the components such as the blower assem-
bly for maintenance and ease of troubleshooting.

Top Discharge -

 The top-discharge outdoor fan does not 

disrupt neighboring areas or dry out vegetation surrounding 
the unit. The warm air from the top mounted fan is blown up 
and away from the structure and any landscaping. 

Outdoor Coil Grille -

 All models utilize a stamped slotted 

design which provides superior impact protection against 
small objects during transit and after installation.

Indoor Blower Assembly - 

Fan shall be direct drive design. 

Blower wheel shall be double-inlet type with forward-curved 
blades, dynamically balanced to operate smoothly throughout 
the entire range of operation. Airflow design shall be constant 
air volume. Bearings shall be sealed and permanently 
lubricated for longer life and no maintenance. Fan assembly 
shall be a slide-out design for easy removal and cleaning. 
Indoor blower motors shall be equipped with a high efficiency 
brushless DC motor (constant torque) also known as an 
enhanced ECM motor.

Summary of Contents for PHG6 24 Series

Page 1: ...t and tested prior to shipment Test sta tions using a state of the art computerized process system are used to insure product quality Refrigerant charge and component part numbers are verified via com...

Page 2: ...ed The electrical control box is not located in the compressor compartment The controls are mounted to allow the separate access panel to be removed for trouble shooting and maintenance without affect...

Page 3: ...minal Capacity etc 9 Revision Level A original release B second release Examples PHG4B421002X1 is a dual fuel 14 SEER 3 1 2 ton large cabinet single stage heat 100 000 BTU gas heat 230 volt single pha...

Page 4: ...e to round duct adapter Adapters are preformed and designed to fit over current horizontal duct openings on the base unit Transition is from rectangle to 12 round for the 1AK0110 kit and from rectangl...

Page 5: ...it Condensate pan shall be internally sloped and conform to ASHRAE 62 89 self draining standards with 3 4 NPT female ridged mount connection Durable Finish The cabinet shall be is made of G90 galva ni...

Page 6: ...l be of the tubular type constructed of stainless steel for corrosion resistance and allowing minimum mixed air entering temperature of 40 F Burners shall be of the in shot type constructed of aluminu...

Page 7: ...burners 2 3 2 3 2 3 2 3 2 3 4 2 3 4 No stages 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Temperature Rise Range High Fire F 40 70 40 70 40 70 40 70 40 70 40 70 Temperature Rise Range Low Fire F 20 50 20 50 25 55 25...

Page 8: ...gal Centrifugal Centrifugal Centrifugal Motor HP each 1 3 1 2 1 3 1 2 1 2 3 4 3 4 3 4 1 RPM 1200 Max 1200 Max 1200 Max 1200 Max 1200 Max 1200 Max Frame size 48 48 48 48 48 48 Filters Filter Size A A B...

Page 9: ...6 6 9 0 7 1 7 9 8 5 7 9 K W 1 71 1 71 1 70 1 69 1 68 1 64 1 64 1 64 1 63 1 62 1 57 1 56 1 58 1 57 1 55 COOLING PERFORMANCE DATA 2 TON HIGH SPEED PACKAGED UNIT MODEL NO PHG6A24 CONDENSER ENTERING AIR...

Page 10: ...9 2 8 9 10 1 8 2 11 6 8 8 8 1 10 3 9 1 K W 2 55 2 54 2 54 2 53 2 51 2 54 2 53 2 53 2 53 2 50 2 53 2 51 2 53 2 53 2 50 COOLING PERFORMANCE DATA 2 5 TON HIGH SPEED PACKAGED UNIT MODEL NO PHG6A30 CONDEN...

Page 11: ...5 16 1 14 3 14 9 11 2 15 7 17 5 16 6 17 4 12 8 K W 2 68 2 67 2 68 2 66 2 64 2 62 2 61 2 63 2 61 2 58 2 56 2 56 2 58 2 56 2 53 COOLING PERFORMANCE DATA 3 TON HIGH SPEED PACKAGED UNIT MODEL NO PHG6B36...

Page 12: ...3 19 1 16 9 17 9 12 8 22 7 19 9 18 9 20 4 14 1 K W 3 04 3 03 3 02 3 02 2 97 3 03 3 02 3 03 3 02 2 98 3 03 3 02 3 04 3 03 3 00 COOLING PERFORMANCE DATA 3 5 TON HIGH SPEED PACKAGED UNIT MODEL NO PHG6B4...

Page 13: ...3 2 20 0 17 4 20 8 14 3 24 4 22 1 18 8 23 3 16 0 K W 4 16 4 16 4 15 4 15 4 09 4 11 4 12 4 14 4 11 4 07 4 06 4 08 4 12 4 06 4 04 COOLING PERFORMANCE DATA 4 TON HIGH SPEED PACKAGED UNIT MODEL NO PHG6B48...

Page 14: ...6 7 24 9 21 6 23 2 16 7 27 1 24 7 22 6 24 6 17 6 K W 4 79 4 77 4 78 4 74 4 70 4 78 4 77 4 78 4 75 4 71 4 78 4 77 4 79 4 75 4 72 COOLING PERFORMANCE DATA 5 TON HIGH SPEED PACKAGED UNIT MODEL NO PHG6B60...

Page 15: ...DOOR UNIT AIR TEMP ENTERING INDOOR COIL ID CFM 550 750 950 MBH COP KW MBH COP KW MBH COP KW 60 60 28 9 4 46 1 83 30 1 4 96 1 69 31 4 5 51 1 55 70 27 5 3 87 2 01 28 7 4 30 1 86 29 9 4 80 1 71 80 26 2 3...

Page 16: ...IT AIR TEMP ENTERING INDOOR COIL ID CFM 750 950 1150 MBH COP KW MBH COP KW MBH COP KW 60 60 38 5 4 76 2 13 37 5 4 60 2 22 36 6 4 44 2 30 70 36 5 4 15 2 34 35 7 3 99 2 44 34 8 3 83 2 55 80 34 6 3 63 2...

Page 17: ...UTDOOR UNIT AIR TEMP ENTERING INDOOR COIL ID CFM 1000 1200 1400 MBH COP KW MBH COP KW MBH COP KW 60 60 43 9 4 52 2 53 43 0 4 45 2 58 42 0 4 37 2 64 70 42 1 4 01 2 76 41 2 3 94 2 82 40 3 3 87 2 88 80 4...

Page 18: ...UTDOOR UNIT AIR TEMP ENTERING INDOOR COIL ID CFM 1070 1270 1470 MBH COP KW MBH COP KW MBH COP KW 60 60 47 0 4 42 2 80 46 5 4 36 2 89 46 1 4 30 2 98 70 44 7 3 86 3 07 44 3 3 81 3 17 43 9 3 76 3 26 80 4...

Page 19: ...TDOOR UNIT AIR TEMP ENTERING INDOOR COIL ID CFM 1300 1500 1700 MBH COP KW MBH COP KW MBH COP KW 60 60 61 4 4 63 3 46 60 8 4 52 3 56 60 1 4 42 3 68 70 58 7 4 04 3 82 58 2 3 93 3 97 57 7 3 82 4 12 80 56...

Page 20: ...TDOOR UNIT AIR TEMP ENTERING INDOOR COIL ID CFM 1530 1730 1930 MBH COP KW MBH COP KW MBH COP KW 60 60 73 6 4 77 4 15 73 1 4 56 4 18 72 5 4 37 4 21 70 70 6 4 22 4 53 70 2 4 03 4 60 69 8 3 85 4 67 80 67...

Page 21: ...within a confined space and recirculate Direction Distance in Direction Distance in Top3 3 Units must be installed outdoors Over hanging structure or shrubs should not obstruct condenser air discharge...

Page 22: ...ne Frequency Hz 125 250 500 1000 2000 4000 8000 PHG6A24 70 3 64 7 59 2 59 8 58 1 54 3 49 2 43 2 PHG6A30 69 0 57 5 58 0 58 0 63 8 53 2 47 6 49 7 PHG6B36 72 8 60 1 62 5 60 4 64 5 58 8 53 0 46 0 PHG6B42...

Page 23: ...453 28 15 161 102 90 100 PHG6B36065 503 498 29 14 176 122 104 96 PHG6B36100 510 505 29 14 178 123 109 95 PHG6B42065 537 532 29 14 190 132 112 98 PHG6B42100 539 534 29 14 191 133 109 101 PHG6B48065 556...

Page 24: ...237 192 Low Cool A 902 822 764 713 669 612 557 513 480 437 B 855 734 669 615 572 509 454 418 385 334 C 827 678 611 545 504 448 396 356 311 263 D 675 546 466 404 347 277 205 160 126 80 High Heat A 118...

Page 25: ...A 1126 1067 1006 945 860 777 718 664 608 551 B 1015 952 884 802 709 646 582 528 467 402 C 955 886 821 721 642 584 508 453 391 324 D 910 836 774 661 592 537 453 396 333 265 Low Heat A 970 902 837 742...

Page 26: ...704 1667 1645 1612 1572 1520 1477 1419 1384 1327 B 1506 1468 1441 1404 1358 1302 1259 1203 1159 1101 C 1322 1278 1238 1191 1138 1077 1030 975 920 859 D 1251 1205 1157 1107 1051 987 938 884 824 761 Low...

Page 27: ...4 930 872 810 High Heat A 2114 2046 1974 1914 1874 1815 1745 1696 1645 1582 B 1982 1930 1887 1844 1806 1752 1697 1643 1604 1545 C 1785 1746 1720 1687 1647 1596 1551 1494 1459 1402 D 1614 1578 1554 152...

Page 28: ...75 1329 1280 1232 1181 1135 C 1410 1361 1307 1255 1204 1155 1100 1044 992 938 D 1323 1270 1213 1156 1104 1052 993 933 880 821 Low Heat A 1594 1553 1507 1462 1415 1369 1321 1274 1223 1178 B 1323 1270 1...

Page 29: ...06 0 02 0 16 1300 0 07 0 03 0 17 1400 0 08 0 04 0 18 42 3 5 1100 0 02 0 02 0 04 1200 0 03 0 02 0 04 1300 0 04 0 02 0 05 1400 0 05 0 03 0 05 1500 0 06 0 04 0 06 1600 0 07 0 04 0 07 1700 0 07 0 04 0 08...

Page 30: ...N REAR DUCT ROOF CURB INSTALLATION BOTTOM DUCT SLAB ON GROUND INSTALLATION A032 UNIT TYPICAL SLAB ON GROUND INSTALLATION A0325 001 SUPPLY AIR DUCT TO POWER SUPPLY RETURN AIR DUCT FIELD SUPPLIED DISCON...

Page 31: ...roducts 31 UNIT TYPICAL ROOF CURB INSTALLATION SUPPLY AIR DUCT TO POWER SUPPLY RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH CONTROL WIRING TO INDOOR THERMOSTAT TO GAS SUPPLY LINE MANUAL GAS SHUTOF...

Page 32: ...change without notice Published in U S A 5331896 YTG C 1017 Copyright 2017 by Johnson Controls Inc All rights reserved Supersedes 5331896 YTG B 0817 York International Corp 5005 York Drive Norman OK 7...