5291656-YTG-E-1117

Johnson Controls Unitary Products

15

NOTES: 

1. Airflow tested with dry coil conditions, without air filters, at 230 volts
2. Applications above 0.8" w.c. external static pressure are not recommended.
3. Brushless DC high efficiency enhanced ECM blower motor used for all indoor blower assemblies.
4. Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.
5. Minimal variations in airflow performance data results from using downflow duct applications. Data above may be used in those cases.
6. Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.

RECOMMENDED BLOWER SPEED FOR ELECTRIC HEAT

Model

Heater kW

10

15

18

20

25

PCE6B36

C (ML)

A (HI)

--

--

--

PCE6B48

D (LO)

C (ML)

B (MH)

A (HI)

--

PCE6B60

D (LO)

D (LO)

C (ML)

B (MH)

A (HI)

NOTE: T

he recommended HEAT speed selections above will give approximately a 45 degree temperature rise at 0.3" static with 230V power supply. If lower or higher

             heating airflow is desired, or if duct static or voltage are different than specified, other speed taps may be used.

AIRFLOW PERFORMANCE - SIDE DUCT APPLICATION 

Model

Jumper Position

External Static Pressure (Inches WC)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

36

High Cool

A

1345

1318

1271

1222

1172

1108

1035

961

894

841

B

1264

1211

1170

1115

1056

981

894

826

775

729

C

1232

1178

1131

1077

1012

929

853

790

738

690

D

1058

999

931

859

762

694

635

582

523

459

Low Cool

A

1153

1095

1036

979

899

810

751

697

643

588

B

1015

952

884

802

709

646

582

528

467

402

C

882

805

741

625

556

501

415

359

297

228

D

805

718

642

523

436

376

294

247

193

118

Electric Heat

A

1190

1133

1079

1026

953

861

798

742

689

638

B

1112

1054

991

928

840

760

701

648

591

532

C

955

886

821

721

642

584

508

453

391

324

D

856

776

708

591

516

459

375

321

262

191

48

High Cool

A

1851

1809

1781

1746

1707

1656

1609

1552

1518

1460

B

1689

1652

1630

1597

1556

1504

1461

1404

1368

1310

C

1614

1578

1554

1520

1477

1424

1382

1324

1286

1228

D

1374

1333

1298

1255

1204

1145

1100

1044

993

933

Low Cool

A

1473

1435

1406

1368

1320

1264

1220

1164

1119

1060

B

1374

1333

1298

1255

1204

1145

1100

1044

993

933

C

1322

1278

1238

1191

1138

1077

1030

975

920

859

D

1286

1241

1197

1149

1095

1032

984

930

872

810

Electric Heat

A

1441

1407

1373

1325

1279

1232

1182

1108

1042

1039

B

1327

1286

1242

1192

1143

1081

1024

949

881

834

C

1187

1136

1084

1028

968

886

827

767

702

657

D

1087

1031

974

909

832

750

704

653

600

537

60

High Cool

A

2149

2114

2077

2030

1989

1948

1905

1859

1816

1768

B

2013

1977

1941

1898

1860

1816

1772

1726

1677

1630

C

1936

1900

1864

1822

1783

1739

1695

1649

1597

1551

D

1719

1685

1642

1600

1555

1508

1465

1418

1372

1327

Low Cool

A

1629

1591

1546

1502

1455

1409

1362

1315

1266

1220

B

1558

1516

1469

1423

1375

1329

1280

1232

1181

1135

C

1453

1406

1355

1305

1255

1207

1153

1100

1047

997

D

1410

1361

1307

1255

1204

1155

1100

1044

992

938

Electric Heat

A

1743

1712

1666

1623

1580

1540

1493

1449

1404

1370

B

1485

1436

1380

1329

1283

1234

1185

1139

1084

1032

C

1382

1324

1265

1210

1162

1108

1059

1012

952

891

D

1205

1131

1066

1005

953

892

841

793

724

644

Summary of Contents for PCE6B3631

Page 1: ...0A and tested prior to shipment Test stations using a state of the art computerized process system are used to insure product quality Refrigerant charge and component part numbers are verified via computers during assembly Vital run test statistics such as system pressure motor cur rents air velocity and temperature unit vibration and gas system safeties are monitored and recorded by the system to...

Page 2: ...ust be set to YES and a humidistat is connected from the low volt age R and HUM color coded leads During cooling operation if the humidity level is above the humidistat set point the indoor blower speed is reduced by approximately 15 Simple Control Circuit Field thermostat wiring connect to color coded leads using twist on wire connections Cooling controls use a contactor and a 2nd stage 24 VAC to...

Page 3: ...ot low Nox 3 Cabinet Size A small 35 x 51 B large 45 x 51 8 Generation Level 1 first generation 4 Nominal Air Conditioning Cooling Capacity BTUx1000 24 24 000 BTU etc 9 Revision Level A original release B second release Examples PCE6B4221A is a packaged A C with electric heat 16 SEER 3 1 2 ton large cabinet 230 volt single phase low NOx model first generation first release COMPONENT LOCATION 287 2...

Page 4: ...duct openings on the roof curb Transition is from rectangle to 16 round for the 1AK0108 kit and from rectangle to 18 round for the 1AK0109 kit Roof Curbs S1 1RC0503 S1 1RC0501 NRCA approved curbs provide proper fit to base unit for rooftop installations Curbs are designed to be assembled through hinge pins in each corner Kit also provides seal strip to assure an air tight seal These are 8 inch hig...

Page 5: ...reated galvanized steel shall provide a better paint to steel bond which resists corrosion and rust creep Powder paint finish shall provide superior corrosion resistance 1000 hour salt spray tested On Site Flexibility All model sizes shall use a compact design cabinet Field convertible duct connections from side shot to down shot allows the installer to have greater flexibil ity with less inventor...

Page 6: ...s to control refrigerant flow CONTROLS Simple Control Circuit Field thermostat wiring connects to color coded leads using twist on wire connections Cooling controls use contactor and relays for simple application and troubleshooting Mate n lock plug connectors are used Enhanced ECM indoor blower control is managed by a multi stage indoor blower control board that includes field adjust able speed t...

Page 7: ...pe Interlaced Interlaced Interlaced Evaporator Coil Data Face area Sq Ft 6 3 6 3 6 3 Rows 3 3 4 Fins per inch 16 16 16 Tube diameter 3 8 3 8 3 8 Circuitry Type Interlaced Interlaced Interlaced Refrigerant control TXV TXV TXV Condenser Fan Data Fan diameter Inch 26 26 26 Type Prop Prop Prop Drive type Direct Direct Direct No speeds 1 1 1 Motor HP each 1 3 1 3 1 3 RPM 850 850 850 Nominal total CFM 3...

Page 8: ...7 6 18 1 15 4 16 6 11 0 18 7 19 4 17 7 18 5 11 7 K W 4 23 4 22 4 19 4 19 4 13 4 17 4 18 4 18 4 15 4 10 4 11 4 14 4 17 4 12 4 07 COOLING PERFORMANCE DATA 3 TON HIGH SPEED PACKAGED UNIT MODEL NO PCE6B36 CONDENSER ENTERING AIR TEMPERATURE ID CFM 2050 1800 1550 IDDB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 IDWB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 45 T C 38 5 41 0 40 0 43 2 46 6 41 2 42...

Page 9: ...7 4 17 5 12 5 20 4 11 4 17 9 17 6 11 8 22 3 12 1 K W 3 98 4 10 3 98 3 91 3 89 3 99 4 05 4 00 3 92 3 93 4 00 4 01 4 02 3 93 3 97 COOLING PERFORMANCE DATA 4 TON HIGH SPEED PACKAGED UNIT MODEL NO PCE6B48 CONDENSER ENTERING AIR TEMPERATURE ID CFM 1400 1600 1800 IDDB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 IDWB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 45 T C 46 5 54 3 55 5 56 6 59 6 47 9 54...

Page 10: ...2 24 3 27 5 24 6 25 9 18 4 25 1 26 7 25 2 27 5 19 6 K W 4 57 4 38 4 39 4 35 4 32 4 58 4 47 4 49 4 46 4 43 4 58 4 57 4 59 4 56 4 54 COOLING PERFORMANCE DATA 5 TON HIGH SPEED PACKAGED UNIT MODEL NO PCE6B60 CONDENSER ENTERING AIR TEMPERATURE ID CFM 600 800 1000 IDDB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 IDWB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 45 T C 59 2 68 9 66 5 71 8 77 1 61 3 7...

Page 11: ...of duct 2 Units must be installed outdoors Overhanging structures or shrubs should not obscure outdoor air discharge outlet 3 Units may be installed on combustible floors made from wood or class A B or C roof covering materials Note For units applied with a roof curb the minimum clearance may be reduced from 1 inch to 1 2 inch between combustible roof curb material and this supply air duct INDOOR ...

Page 12: ...n Breakers for heaters are included in the 20kW and 25kW heater kits 1 MCA Minimum Circuit Ampacity 2 Maximum Over Current Protection per standard UL 1995 3 Fuse or HACR circuit breaker to be field installed 4 Single Point Connection Required ELECTRICAL DATA FOR 208 3 60 MULTI SOURCE POWER Model Compressor OD Fan Motor ID Blower Motor Electric Heat Option Multi Source Heater Kit Heater kW Stages H...

Page 13: ...29 0 45 69 0 NOTES Single source power MCA and MOP requirements are given here for reference if the unit is to be installed with a field installed single point power modification Breakers for heaters are included in the 20kW and 25kW heater kits ELECTRICAL DATA FOR 230 3 60 MULTI SOURCE POWER Model Compressor OD Fan Motor ID Blower Motor Electric Heat Option Multi Source Heater Kit Heater kW Stage...

Page 14: ...int Wiring Kit Unit Fuse Size A Heater Fuse Size A PCE6B3631 230 3 60 6HK06501025 S1 2SPWK031 30 30 6HK06501525 S1 2SPWK033 30 45 PCE6B4831 230 3 60 6HK06501025 S1 2SPWK032 35 30 6HK06501525 S1 2SPWK034 35 45 6HK06501825 S1 2SPWK034 35 50 6HK16502025 S1 2SPWK035 35 N A PCE6B6031 230 3 60 6HK06501025 S1 2SPWK032 45 30 6HK06501525 S1 2SPWK034 45 45 6HK06501825 S1 2SPWK034 45 50 6HK16502025 S1 2SPWK0...

Page 15: ...4 635 582 523 459 Low Cool A 1153 1095 1036 979 899 810 751 697 643 588 B 1015 952 884 802 709 646 582 528 467 402 C 882 805 741 625 556 501 415 359 297 228 D 805 718 642 523 436 376 294 247 193 118 Electric Heat A 1190 1133 1079 1026 953 861 798 742 689 638 B 1112 1054 991 928 840 760 701 648 591 532 C 955 886 821 721 642 584 508 453 391 324 D 856 776 708 591 516 459 375 321 262 191 48 High Cool ...

Page 16: ...2 0 16 1300 0 07 0 03 0 17 1400 0 08 0 04 0 18 48 4 0 1100 0 02 0 02 0 04 1200 0 03 0 02 0 04 1300 0 04 0 02 0 05 1400 0 05 0 03 0 05 1500 0 06 0 04 0 06 1600 0 07 0 04 0 07 1700 0 07 0 04 0 08 1800 0 08 0 04 0 09 1900 0 09 0 05 0 10 2000 0 09 0 05 0 11 60 5 0 1100 0 02 0 02 0 04 1200 0 03 0 02 0 04 1300 0 04 0 02 0 05 1400 0 05 0 03 0 05 1500 0 06 0 04 0 06 1600 0 07 0 04 0 07 1700 0 07 0 04 0 08...

Page 17: ...OOF CURB INSTALLATION REAR DUCT ROOF CURB INSTALLATION BOTTOM DUCT SLAB ON GROUND INSTALLATION A0324 001 UNIT TYPICAL SLAB ON GROUND INSTALLATION A0390 001 SUPPLY AIR DUCT TO POWER SUPPLY RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH CONTROL WIRING TO INDOOR THERMOSTAT CONDENSATE DRAIN ...

Page 18: ...s Inc All rights reserved Supersedes 5291656 YTG D 0817 York International Corp 5005 York Drive Norman OK 73069 UNIT TYPICAL ROOF CURB INSTALLATION SUPPLY AIR DUCT TO POWER SUPPLY RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH CONTROL WIRING TO INDOOR THERMOSTAT ROOF CURB ROOF CONDENSATE DRAIN A0389 001 ...