ELECTRICAL DATA FOR
- 230-3-60 SINGLE SOURCE POWER
Model
Compressor
OD
Fan
Motor
ID
Blower
Motor
Electric Heat Option
MCA
1
(Total
Unit)
1. MCA = Minimum Circuit Ampacity.
Max
Fuse
2
or
Breaker
Size
3
(Total
Unit)
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker to be field installed.
MCA
1
(Unit
Less
Heater)
Max
Fuse
2
or
Breaker
Size
3
(Unit Less
Heater)
MCA
1
Unit
(Heater Only)
Max
Fuse
2
or
Breaker
Size
3
(Heater
Only)
Heater Kit
4
4. Single Point Connection Required.
Heater
kW
Stages
Heater
Amps
RLA LRA MCC FLA
FLA
230
230
230
230
230
230
230
230
PCE6A36 11.6 73.0 18.1
1.7
3.8
none
--
--
--
20.0
30
20.0
30
-
-
6HK06501025
8.8
1
22.1
31.4
35
20.0
30
27.6
30
6HK06501525
13.2
1
33.1
45.2
50
20.0
30
41.4
45
PCE6B48 14.0 83.1 21.9
1.7
5.4
none
--
--
--
24.6
35
24.6
35
-
-
6HK06501025
8.8
1
22.1
33.0
35
24.6
35
27.6
30
6HK06501525
13.2
1
33.1
46.8
50
24.6
35
41.4
45
6HK06501825
15.9
1
39.9
55.3
60
24.6
35
49.9
50
6HK16502025
17.6
2
44.2
60.6
70
24.6
35
55.2
*
PCE6B60 16.2 110.0 25.3
1.7
7.0
none
--
--
--
29.0
45
29.0
45
-
-
6HK06501025
8.8
1
22.1
34.6
45
29.0
45
27.6
30
6HK06501525
13.2
1
33.1
48.4
50
29.0
45
41.4
45
6HK06501825
15.9
1
39.9
56.9
60
29.0
45
49.9
50
6HK16502025
17.6
2
44.2
62.2
70
29.0
45
55.2
*
6HK16502525
22.0
2
55.2
76.0
80
29.0
45
69.0
*
NOTES:
Single-source power MCA and MOP requirements are given here for reference if the unit is to be installed with a field-installed single-point power modification.
*
Breakers for heaters are included in the 20kW and 25kW heater kits.
ELECTRICAL DATA FOR
230-3-60 MULTI SOURCE POWER
Model
Compressor
OD
Fan
Motor
ID
Blower
Motor
Electric Heat Option
Multi Source
Heater Kit
Heater
kW
Stages
Heater
Amps
RLA LRA MCC FLA
FLA
230
230
230
230
230
230
230
230
Multi Source: Compressor Circuit and
Heat Circuits
Multi Source: Circuit #1 - Compressor
Circuit #2 - 1st Stage Heater
Circuit #3 - 2nd Stage Heater
MCA
1
Amps
Max Fuse
2
or Breaker
Size
3
MCA
1
Amps
Max Fuse
2
or Breaker
Size
3
MCA
1
Amps
Max Fuse
2
or Breaker
Size
3
Circuit #1
Circuit #2
Circuit #3
PCE6B36 11.6 73.0 18.1
1.7
3.8
none
--
--
--
20.0
30
--
--
--
--
6HK06501025
8.8
1
22.1
20.0
30
27.6
30
--
--
6HK06501525
13.2
1
33.1
20.0
30
41.4
45
--
--
PCE6B48 14.0 83.1 21.9
1.7
5.4
none
--
--
--
24.6
35
--
--
--
--
6HK06501025
8.8
1
22.1
24.6
35
27.6
30
--
--
6HK06501525
13.2
1
33.1
24.6
35
41.4
45
--
--
6HK06501825
15.9
1
39.9
24.6
35
49.9
50
--
--
6HK16502025
17.6
2
44.2
24.6
35
27.6
30
27.6
30
PCE4B60 16.2 110.0 25.3
1.7
7.0
none
--
--
--
29.0
45
--
--
--
--
6HK06501025
8.8
1
22.1
29.0
45
27.6
30
--
--
6HK06501525
13.2
1
33.1
29.0
45
41.4
45
--
--
6HK06501825
15.9
1
39.9
29.0
45
49.9
50
--
--
6HK16502025
17.6
2
44.2
29.0
45
27.6
30
27.6
30
6HK16502525
22.0
2
55.2
29.0
45
34.5
35
34.5
35
NOTES:
1. MCA = Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker to be field installed.