background image

The size of the unit should be based on an acceptable heat loss
calculation for the structure. ACCA, Manual J or other approved
methods may be used.

The furnace should be located using these guidelines:

1.  Where a minimum amount of vent piping and elbows will

be required.

2.  As centralized with the air distribution as possible.

3.  Where adequate combustion air will be available.

4.  In an area where ventilation facilities provide for safe limits of

ambient temperature under normal operating conditions.

5.  Where it will not interfere with proper air circulation in the

confined space.

6.  Where the vent will not be blocked or restricted.

7.  Where sufficient space is provided to allow proper service

access. Minimum recommended service clearances are
as follows:

Twenty-four (24) inches between the front of the furnace
and an adjacent wall or another appliance, when access
is required for servicing and cleaning.

Eighteen (18) inches at the side where access is required
for passage to the front when servicing or for inspection
or replacement of flue/vent connections.

8.  Where it will not interfere with the cleaning, servicing or

removal of other appliances.

9.  Where the following minimum clearances (in inches) to

combustibles can be maintained:

 Location  Upflow      Horizontal      Downflow
Top

1

0

0

Front

  6*

  6*

6*

Vent Piping

   3**

    3**

3**

Rear

0

0

0

Sides

0

     1 

(flue 

side)

0

     0 

(opposite

      (flue 

side)

Floor

Combustible

Combustible

1***

Closet

Yes

No

Yes

Alcove

Yes

Yes

Yes

Attic

Yes

Yes

Yes

Line Contact

No

Yes

No

 * 

Clearance may be 3 in. when Type B-1 vent is used.

   **

 May be 1" for Type B-1/BH vent

.

 ***

Special floor base or air conditioning coil required

      for combustible floor.

UNIT INSTALLATION

COMBUSTION AIR

All installations must comply with Section 5.3, Air for Combus-
tion and Ventilation of the National Fuel Gas Code, ANSI
Z223.1 or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149.1 or .2
Installation Code - latest editions.

The following must be considered to obtain proper air for
combustion and ventilation in confined spaces:

1.  Air Source from Inside the Building - 

Two permanent openings, one within 12 inches of the top
of the confined space and one within 12 inches of the
bottom, shall each have a free area of not less than one
square inch per 1,000 Btuh of total input rating of all
appliances located in the space. The openings shall com-
municate freely with interior areas having adequate infil-
tration from the outside.

NOTE: At least 100 square inches free area shall be used for

each opening.

2.  Air Source from Outdoors - 

Two permanent openings, one within 12 inches  of the top
of the confined space and one within 12 inches  of the
bottom, shall communicate directly, or by means of ducts,
with the outdoors or to such crawl or attic spaces that freely
communicate with the outdoors.

a.  Vertical Ducts - Each opening must have a free area of

not less than one square inch per 4,000 Btuh of total
input of all appliances located in the space.

EXAMPLE:

Total Input of All Appliances  

=  Square Inches Free Area

     4000

b.  Horizontal Ducts - Each opening must have a free area

of not less than one square inch per 2,000 Btuh of total
input of all appliances located in the space.

NOTE: Ducts must have the same cross-sectional area as the free

area in the opening to which they are connected. The mini-
mum dimension of rectangular ducts shall be three inches.

3.  Louvers, Grilles and Screens

a.  In calculating free area, consideration must be given to

the blocking effects of louvers, grilles and screens.

b.  If the free area of a specific louver or grille is not known,

refer to Table 1 to estimate free area.

TABLE 1 - ESTIMATED FREE AREA

4.  Special Combustion and Ventilation Considerations

Operation of a mechanical exhaust, such as an exhaust
fan, kitchen ventilation system, clothes dryer or fireplace
may create conditions requiring special attention to avoid
unsatisfactory operation of gas appliances.

The size of combustion air openings previously discussed will
not necessarily govern when a special engineering design
ensures an adequate supply of air for combustion and ventilation.
Where the return duct system is not complete, the return
connection must be run full size from the furnace to a location
outside the utility room or basement. 

NOMENCLATURE

P  2  MP   D12   N   064  01  F

 Style
 Voltage Code 
 01 

120 

-1-60

 Nominal Capacity
   (MBH Output)
 Heating Fuel 
  N = Natural, L = Low Nox
  Type drive & CFM (x100) 
   D = Direct, V = Variable
 Product Identifier
  MP = Upflow, Horizontal
  DP = Downflow
 Product Generation
  2 (U.S. & Canada), 9 (Canada)
 Product Category 
 P = Furnace

Wood or Metal

Louvers or Grilles

Wood 20-25%*

Metal 60-70%*

Screens**

1/4 in. mesh or larger 100%

    * Do not use less than 1/4 in. mesh

  ** Free area or louvers and grilles varies widely; installer

      should follow louver or grille manufacturer’s instructions.

650.69-N3

Unitary Products Group

3

Summary of Contents for P2MP Series

Page 1: ...s supplier s instructions If you cannot reach your gas supplier call the fire department IAMON 80 D D UPFLOW MULTI POSITION GAS FIRED FURNACES INDUCED DRAFT STYLE G INSTALLATION INSTRUCTION Supersedes...

Page 2: ...ired appli ances as allowed by the National Fuel Gas Code NFPA 54 ANSI Z223 1 latest edition WARNING This appliance is not to be used for temporary heating of buildings or structures under constructio...

Page 3: ...pace The openings shall com municate freely with interior areas having adequate infil tration from the outside NOTE At least 100 square inches free area shall be used for each opening 2 Air Source fro...

Page 4: ...2MPD20 11201 35 65 180 3 4 11 x 10 13 8 15 14 16 X 25 25 X 27 163 Variable Speed Blower Models P2MPV12N06401 25 55 180 1 2 10 x 7 12 15 14 16 X 25 16 X 27 119 P2MPV14N08001 30 60 180 1 2 10 x 9 12 15...

Page 5: ...3 8 15 14 2 14 X 20 168 Model designator may be N for standard units or L for factory built low NOx units Model A B C D P2DPD10 04801 16 1 4 14 15 3 P2DPD12 06401 16 1 4 14 15 4 P2DPD12 08001 22 1 4 2...

Page 6: ...al Fuel Gas Code ANSI Z223 1 or the CAN CGA B149 Installation Codes and these in structions Determine that there is no blockage or restric tion leakage corrosion or other deficiencies which could caus...

Page 7: ...ilter and Mounting System A return air filter grille or duct mounted filter may be provided The following minimum sizes are recom mended NOTE Air velocity through throw away type filters may not excee...

Page 8: ...ing rod pipe or straps refer to Physical Data Page 4 for furnace weights to determine suitable means of suspension Angle supports should be placed at the supply air end and near the blower deck Units...

Page 9: ...ied on the rating plate or a matching cooling coil Follow the instructions with the combustible floor base acces sory The floor opening dimensions for the floor base are shown in Figure 10 This base c...

Page 10: ...with the provisions of the National Electrical Code ANSI NFPA No 70 latest edition Canadian Electric Code C22 1 Part 1 latest edition and or local codes Electrical wires which are field installed shal...

Page 11: ...t rely upon the interlock switch as a main power disconnect Rollout Switch Controls These controls are mounted on the burner assembly If the temperature in the burner compartment exceeds its set point...

Page 12: ...t is not within 2 of the furnace rating with allowance being made for the permissible range of the regula tor setting 0 3 inches W C replace the orifice spuds with spuds of the proper size CAUTION Be...

Page 13: ...use the same speed tap for heating and cooling the heat terminal and cool terminal must be connected using a jumper wire and connected to the desired motor lead Place all unused motor leads on Park t...

Page 14: ...l begin and the burner will operate normally if the gas supply returns or the fault condition is corrected prior to the last ignition attempt Otherwise the control will lockout The control will repeat...

Page 15: ...n Start the system by setting the thermostat above room temperature Observe the system s response Then use the Troubleshooting tables in this manual to check the system s operation Use the troubleshoo...

Page 16: ...tat G to R contacts close FAN ONLY CHECK COOLING CYCLE CHECK Does the circulator blower energize at cool speed Is 25 volts present across terminals Y C Is 25 volts present across terminals R C Is 25 v...

Page 17: ...or circuit breaker System is functioning properly Connect voltmeter across terminals of igniter harness Check wiring If ok replace thermostat Energize system and check for proper operation No No Yes...

Page 18: ...esent Check wiring If OK replace module Energize and check for proper operation Reverse 120 V hot and neutral line wires Less than 30 V Unplug circulator blower wires and connect voltmeter across term...

Page 19: ...WIRING DIAGRAM UPFLOW MULTI SPEED MODELS NOTE The furnace s control system depends on correct polarity of the power supply 650 69 N3 Unitary Products Group 19...

Page 20: ...WIRING DIAGRAM DOWNFLOW MODELS NOTE The furnace s control system depends on correct polarity of the power supply 650 69 N3 20 Unitary Products Group...

Page 21: ...2110 2004 1913 1797 1581 MED 2027 1986 1945 1917 1877 1820 1763 1653 1558 1445 LOW 1349 1327 1312 1281 1233 1150 1078 P2MPD20N11201 See Notes 6 7 HIGH 2204 2154 2081 2055 2002 1933 1843 1706 1545 1409...

Page 22: ...PD16 08001 HIGH 2043 2000 1893 1823 1726 1627 1503 1382 1249 1134 MED 1706 1655 1593 1533 1450 1366 1265 1163 1062 950 LOW 1452 1406 1373 1317 1245 1174 1112 1025 935 817 P2DPD16 09201 HIGH 2053 1977...

Page 23: ...NOTES 650 69 N3 Unitary Products Group 23...

Page 24: ...y Products Group P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1994 All Rights Reserved Code SBY 650 69 N3...

Reviews: