background image

PHASE ROTATION

Scroll  compressors  designed  to  operate  only  in  one  direction.  If  opposite  direction  is  required,  swamp  any  two

phases at the main terminal block. Reciprocating compressors are able to run in either direction without any loss of

performance or reliability.

Special Note for units fitted with Scroll Compressors

Phase sequencing: the Scroll compressor is designed to operate with motor running in only direction. Mis-wiring of

phase power (phase reversal) will cause the compressor to operate in the wrong direction. The Scroll compressor

will run without damaging itself if phasing is improper, but it will not pump refrigerant and will draw minimal current.

In such a case, the internal winding line break will ultimately shut off the compressor. Depending upon the conditions

it could take up to 30 minutes to trip the internal winding protection. The compressor will be noisy, vibrate excessively

and the oil sump will become warm to hot when running backwards.
Because of the scroll compressor design and its capability to accommodate liquid slugging, both oil and refrigerant,

without causing compressor damage, there are some characteristic sounds that differentiate if from those normally

associated with reciprocating type compressors.

These sounds described below, are characteristics and do not affect reliability or indicate that the compressor is

defective.

Cautions

1. Three phase scrolls will only pump when running in right direction.

2. Verify rotation on initial start up by checking pressure.

3. To correct improper motor rotation, switch any two supply lines.

At Start-up:

Under conditions of low refrigerant flows (low suction pressures) such as start-up, a rating sound may emanate from

the compressor.

This is more like to be heard under conditions such as low ambient starts where it takes time to build sufficient head

pressure to allow the thermal expansion valve to flow sufficient refrigerant to increase the suction pressure. This

sound should diminish and disappear as the suction pressure increases.

At Shutdown:

The gas within the scroll expands and causes momentary reverse rotation until the discharge check valve seats.

This results in a “flutter” type noise.

Refrigerant Flooding:

If the compressor experience severe liquid slugging during the operation the compressor will make a loud rattling

sound.

This is normal because of the separation of the scrolls that allow the liquid refrigerant to pass through the compressor

without damaging it.

Summary of Contents for MOC-MOH 07-65

Page 1: ...e line protection The unit must be grounded Installation and maintenance of this air conditioning system should only be carried out by trained and qualified personnel Regular maintenance operations such as cleaning the coils and air filters must be performed to keep the units in proper operati ng condition EN FR 035T83112 001 The units are shipped complete with a charge of R22 R407C refrigerant su...

Page 2: ... 1 590 820 280 56 58 5 8 3 8 1 2 55 12 34 61 1650 1600 1 696 850 285 65 67 5 8 3 8 25 3 3 53 6 77 48 1 35 5 8 3 8 3 5 71 9 10 53 3 6 79 11 72 62 3000 3000 1 1142 850 285 87 88 3 4 3 8 45 3800 3800 1 1142 1060 345 109 111 3 4 3 8 55 900 850 285 76 77 208 230 1 60 or 460 3 60 Reciprocating 2800 2500 1 3 57 16 17 81 1 5 8 3 8 220 240 1 50 or 380 415 3 50 MOC MOH R22 Scroll Flare Nuts 07 1 0 78 3 6 20...

Page 3: ...300 800 200 400 100 300 800 200 400 100 300 800 40 45 55 65 07 12 400 200 100 210 600 To prevent ice build up beneath the unit during winter operation it may be necessary to increase the dimension of C by 50 to 100 mm MOC MOH 07 18 MOC MOH 25 35 MOC MOH 40 65 MOC MOH 07 18 MOC MOH 25 35 MOC MOH 40 65 A minimum of clearance is necessary around the units to ensure proper air circulation and easy acc...

Page 4: ... sunlight especially if it is a cooling only model since direct sunlight will increase condensing pressure and reduce unit efficiency Install units facing North whenever possible In particularly windy places the unit should be installed so that the prevailing wind does not interfere with air discharge from the unit configuration with the wind blowing onto the side of the unit MOH heat pump unit in...

Page 5: ...tall the flare connectors and flare the ends of the pipes Heat pump discharge Evacuate the piping This operation which should last at least 15 minutes or even longer if there are large piping lengths and changes in elevation should be followed by a leak test To this effect when the piping has been evacuated close the pressure gauge tap note the value on the gauge then wait for 15 minutes If the ne...

Page 6: ... 860 0 856 0 852 0 849 0 845 0 842 0 838 0 835 0 831 0 828 0 824 Pipe Length L H 0 m H 3 m H 5 m H 10 m H 20 m H 25 m H 30 m Pipe Length L H 0 m H 3 m H 5 m H 10 m H 20 m H 25 m H 30 m 0 974 0 973 0 972 0 971 0 970 0 969 0 969 0 968 0 967 0 966 0 965 0 964 0 963 0 963 0 962 0 961 0 960 0 959 0 958 0 957 0 957 0 956 0 964 0 963 0 962 0 961 0 960 0 959 0 959 0 958 0 957 0 956 0 955 0 954 0 953 0 953...

Page 7: ...solating valves have been fully opened That the refrigerant charge has been topped up if necessary Start the units and check operation in both the cooling and the heating mode Unit base plate Compressor Diagram n 1 MOC 18 MOH 18 Coil DEFROST Defrost is handled via a defrost management electronic control board model with two potential meters and 6 dip switches see diagram n 2 This enables defrost c...

Page 8: ...le Flare with Schrader COOLING CIRCUIT PRESSURE TAP LOCATION PRESSURE TAP Outdoor unit C a u t i o n Risk of electric shock A fan speed controller is provided as standard on full featured condensing units and can be installed also as an accessory in t he field on all N series condensing units that are equipped with a pressure tap see diagram below for easy installation The Saginomiya pressure type...

Page 9: ...ome characteristic sounds that differentiate if from those normally associated with reciprocating type compressors These sounds described below are characteristics and do not affect reliability or indicate that the compressor is defective Cautions 1 Three phase scrolls will only pump when running in right direction 2 Verify rotation on initial start up by checking pressure 3 To correct improper mo...

Page 10: ...ry check that motors are operating properly Check wire gauges etc Replace it Remedy Cause Symptoms Remedy Ice build up indoor coil Faulty installation Compressor noisy Thermostat Safety device Excessive discharge pressure Insufficient discharge pressure Excessive suction pressure Insufficient suction pressure Low refrigerant charge refrigerant leak Insufficient airflow Low operating temperature li...

Page 11: ...ating valve with pressure tap 7 HP pressure switch Interseason start up safety 8 4 way cycle changeover valve 9 Anti slugging receiver 10 Restrictor Unit Capacity Total cooling capacity can be determined by using correction factors C1 C2 and C3 Given cooling capacity Cooling capacity at standard rating conditions x C1 x C2 x C3 C1 Capacity correction factor for temperature C2 Capacity correction f...

Page 12: ...l and gas isolation are secured in the OFF position The supply cables and gas pipework may then be disconnected and removed For points of connection refer to unit installation instructions 2 Remove all refrigerant from each system of the unit into a suitable container using a refrigerant reclaim or recovery unit This refrigerant may then be reused if appropriate or returned to the manufacturer for...

Reviews: