YORK INTERNATIONAL
57
FORM 155.16-O3
START
ALL PUMPS
CHECK STRONG
SOLUTION TEMP
@ RT 3
>136°F
(57.8°C)
STEAM
UNIT
ENERGIZE 6 SOL
TO OPEN STEAM
CONDENSATE DRAIN
VALVE
DISPLAY “DAY-TIME-LRT-
CHK FOR CRYSTALLIZATION”
AS STATUS
START 6-MINUTE
DILUTION CYCLE
TIMER
ENTER DILUTION
CYCLE @
8
PAGE 35
EXIT DILUTION
CYCLE @
*
PAGE 42
6 MIN.
DILUTION
TIMER
ELAPSED
REFRIG
TEMP
> 37°F
(2.8°C)
30 MIN.
CHILL WATER
PUMP TIMER
ELAPSED
SHUTDOWN
CHILLED
WATER
PUMP
REFRIG-
TEMP
> 37°F
(2.8°C)
UNIT
SW IN
STOP/
RESET
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
NO
NO
NO
NO
NO
NO
NO
YES
YES
➤
YES
YES
YES
YES
YES
A
B
C
A
B
C
D
E
Summary of Contents for MILLENNIUM YIA-HW-14F3
Page 116: ...YORK INTERNATIONAL 115 FORM 155 16 O3 NOTES...
Page 117: ...116 YORK INTERNATIONAL NOTES...