YORK INTERNATIONAL
29
FORM 155.16-O3
CHECK ENTERING
CONDENSER WATER
TEMP @ RT 5
ENT
COND
WATER TEMP
WARNING IN
EFFECT
< MAX
ALLOWED
ENTERING
COND WATER
TEMP
CLEAR “ENT
CONDENSER
WATER TEMP HIGH
LIMIT WARNING
MESSAGE” WHEN
WARNING RESET
KEY PRESSED IN
SERVICE MODE
REMOVE ENT COND
WATER TEMP HIGH
LIMIT. ALLOW UNIT
LOADING TO > 60%
STEAM/HOT WATER
VALVE POSITION
DISPLAY “WARNING-
ENT COND WATER
TEMP HIGH LIMIT”
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
>
PROGRAMMED
LIMIT FOR 10
MINUTES
UNIT
RUNNING
> 30
MINUTES
PUT ENTERING
CONDENSER
WATER TEMP HIGH
LIMIT IN EFFECT-
LIMIT STEAM/HOT
WATER VALVE
POSITION TO 60%
CLOSE ALARM
CONTACTS TB4-89/90
TO SOUND AUDIBLE
ALARM UNTIL RESET
WITH WARNING
RESET KEY
NO
NO
NO
NO
YES
YES
YES