42
YORK INTERNATIONAL
FORM 201.18-NM1 (102)
NOTES:
1. For leaving brine temperature below 40°F (4.40°C), contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 55°F (12.8°C) contact the nearest YORK office for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
TEMPERATURE AND FLOWS
(ENGLISH UNITS)
TEMPERATURE AND FLOWS
(SI UNITS)
Excessive flow, above the max GPM,
will damage the evaporator.
MODEL
LEAVING WATER
COOLER FLOW
AIR ON
NUMBER
TEMPERATURE (
°
C)
(L/S)
3
CONDENSER (
°
C)
YCAS
MIN.
1
MAX.
2
MIN.
MAX.
MIN.
MAX
0130EC
4.4
12.8
9.3
37.8
-17.7
51.7
0140EC
4.4
12.8
10.7
37.8
-17.7
51.7
0150EC
4.4
12.8
11.5
44.2
-17.7
51.7
0160EC
4.4
12.8
11.9
47.1
-17.7
51.7
0170EC
4.4
12.8
12.8
47.1
-17.7
51.7
0180EC
4.4
12.8
13.8
47.1
-17.7
51.7
0200EC
4.4
12.8
14.4
47.1
-17.7
51.7
0210EC
4.4
12.8
15.6
47.1
-17.7
51.7
0230EC
4.4
12.8
17.2
47.1
-17.7
51.7
MODEL
LEAVING WATER
COOLER FLOW
AIR ON
NUMBER
TEMPERATURE
(°
F)
(GPM
3
)
CONDENSER (
°
F)
YCAS
MIN.
1
MAX.
2
MIN.
MAX.
MIN.
MAX
0130EC
40
55
147
600
0
125
0140EC
40
55
170
700
0
125
0150EC
40
55
182
747
0
125
0160EC
40
55
188
747
0
125
0170EC
40
55
203
747
0
125
0180EC
40
55
218
747
0
125
0200EC
40
55
228
747
0
125
0210EC
40
55
248
747
0
125
0230EC
40
55
272
747
0
125
Technical Data