17
YORK INTERNATIONAL
FORM 201.18-NM1 (102)
TABLE 1 –
MOTOR PROTECTOR DIP SWITCH SETTING (CONT’D)
YCAS STYLE F, WYE-DELTA START – 60 HZ
MODEL
VOLT
CHILLER
NO.
MOTOR PROTECTOR
NO.
CODE
NAMEPLATE
LEADS
MP OL
RLA
PER
VALUE
PHASE
SET
DIP SWITCH SETTINGS ON MP (“1” INDICATES ON)
128
64
32
16
8
4
2
1
0130
17
246
*2
193
1
1
0
0
0
0
0
1
28
214
*2
167
1
0
1
0
0
1
1
1
40
130
2
175
1
0
1
0
1
1
1
1
46
107
2
144
1
0
0
1
0
0
0
0
58
86
2
116
0
1
1
1
0
1
0
0
0140
17
267
*4
105
0
1
1
0
1
0
0
1
28
232
*4
91
0
1
0
1
1
0
1
1
40
140
2
189
1
0
1
1
1
1
0
1
46
116
2
157
1
0
0
1
1
1
0
1
58
93
2
126
0
1
1
1
1
1
1
0
0150
17
295
*4
115
0
1
1
1
0
0
1
1
SYS. 1
28
256
*4
100
0
1
1
0
0
1
0
0
40
155
2
209
1
1
0
1
0
0
0
1
46
128
2
173
1
0
1
0
1
1
0
1
58
103
2
139
1
0
0
0
1
0
1
1
0150
17
265
*4
104
0
1
1
0
1
0
0
0
SYS 2.
28
230
*4
90
0
1
0
1
1
0
1
0
40
139
2
188
1
0
1
1
1
1
0
0
46
115
2
155
1
0
0
1
1
0
1
1
58
92
2
124
0
1
1
1
1
1
0
0
0170
17
321
*4
126
1
0
0
0
0
0
1
0
SYS. 1
28
279
*4
109
0
1
1
0
1
1
0
1
40
169
*2
132
1
0
0
0
0
1
0
0
46
140
2
189
1
0
1
1
1
1
0
1
58
112
2
151
1
0
0
1
0
1
1
1
0170
17
295
*4
115
0
1
1
1
0
0
1
1
SYS. 2
28
256
*4
100
0
1
1
0
0
1
0
0
40
155
2
209
1
1
0
1
0
0
0
1
46
128
2
173
1
0
1
0
1
1
0
1
58
103
2
139
1
0
0
0
1
0
1
1
* Indicates one lead/phase through motor protector.
2
Summary of Contents for MILLENNIUM YCAS0230
Page 45: ...45 YORK INTERNATIONAL FORM 201 18 NM1 102 This page intentionally left blank 7 ...
Page 70: ...70 YORK INTERNATIONAL FORM 201 18 NM1 102 Technical Data FIG 30 DETAIL B LD03285 ...
Page 166: ...166 YORK INTERNATIONAL FORM 201 18 NM1 102 ...