SWITCH 2: Ambient Temp. Low Limit
Open:
Standard Ambient Mode auto-programs the Low Ambi-
ent Cutout setting at 25°F (-4°C) and is not adjustable.
Closed:
Low Ambient Mode allows the Low Ambient Cutout
to be programmed from 0 to 50 °F (-18 to 10°C). Val-
ues above 25°F (-4°C) can be used to automatically
shut down the chiller when direct cooling methods be-
come operational.
SWITCH 3: Refrigerant
Open:
The R-407C Mode MUST be selected for models us-
ing refrigerant R-407C. Incorrect selection of this
switch may cause serious damage to the chiller.
Closed:
The R-22 Mode MUST be selected for models using
refrigerant type R-22. Incorrect selection of this switch
may cause serious damage to the chiller.
S 1 - 2
A M B I E N T
C O N T R O L
S T A N D A R D
S 1 - 2
A M B I E N T
C O N T R O L
L O W
A M B I E N T
S 1 - 3
R E F R I G E R A N T
R - 4 0 7 C
S 1 - 3
R E F R I G E R A N T
R - 2 2
Dip Switch Physical Location and Setting
FIG. 51 –
ENLARGED PHOTOGRAPH OF DIP
SWITCHES ON MICROPROCESSOR
BOARD
LD03511A
LD03511B
“OPEN” Position:
Left side of switch
pushed in
“CLOSED” Position:
Right side of switch
pushed in