149
YORK INTERNATIONAL
FORM 201.18-NM1 (102)
If discharge pressure falls between 150 PSIG and 120
120 PSIG, a step of fan cycling will be dropped and the
micro will start a 15 minute timer. If the discharge pres-
sure remains in this range for 15 minutes, another step
of fan cycling will be dropped and the micro will restart
the 15 minute timer.
If discharge pressure rises above 285 PSIG, the micro
will add a step of fan cycling every 5 seconds, until the
discharge pressure drops below 285 PSIG in an effort
to quickly control the discharge pressure to an accept-
able range.
If discharge pressure drops below 120 PSIG or oil to
suction pressure differential falls below 75 PSID, the
micro will turn off a step of fan cycling every 5 sec-
onds; until the discharge pressure rises above 120 PSIG
and oil to suction pressure differential rises above 75
PSID in an effort to quickly control the discharge pres-
sure to an acceptable range.
Table 8 provides a simplified operating graph of the fan
staging for this version.
TABLE 5 –
CONDENSER FAN CONTROL AND FAN CONTACTOR DATA FOR DXST UNITS
WITH 5 FANS/SYSTEM (EPROM VERSIONS C.ACS.09.01 (F350) AND C.AC.09.02 (3902))
* Sys 1 Outputs are on Relay Board #1
Sys 2 Outputs are on Relay Output Board #2
Fan
ON *
OFF *
Fan
Wire
Relay
Stage
Fans
Conditions
Conditions
Contactor
Number
Board
DP
DP & OAT
Output*
1
1
>220 PSIG
<150 PSIG & <60°F
9M
130
15
S
2
3, 5
>235 PSIG
<165 PSIG & <65°F
10M, 11M
131
14
Y
3
7, 9
>250 PSIG
<180 PSIG & <70°F
12M, 13M
132
10
S
4
1, 7, 9
>265 PSIG
<195 PSIG & <75°F
9M, 12M, 13M
130, 132
10, 15
5
3, 5, 7, 9
>280 PSIG
<210 PSIG & <80°F
10M, 11M, 12M, 13M
131, 132
10, 14
1
6
1, 3, 5, 7, 9
>290 PSIG
<220 PSIG & <85°F
9M, 10M, 11M, 12M, 13M
130, 131, 132
10, 14, 15
1
2
>220 PSIG
<150 PSIG & <60°F
15M
230
15
S
2
4, 6
>235 PSIG
<165 PSIG & <65°F
16M, 17M
231
14
Y
3
8, 10
>250 PSIG
<180 PSIG & <70°F
18M, 19M
232
10
S
4
2, 8, 10
>265 PSIG
<195 PSIG & <75°F
15M, 18M, 19M
230, 232
10, 15
5
4, 6, 8, 10
>280 PSIG
<210 PSIG & <80°F
16M, 17M, 18M, 19M
231, 232
10, 14
2
6
2, 4, 6, 8, 10
>290 PSIG
<220 PSIG & <85°F
15M, 16M, 17M, 18M, 19M
230, 231, 232
10, 14, 15
8
TABLE 4 –
CONDENSER FAN CONTROL AND FAN CONTACTOR DATA FOR DXST UNITS
WITH 4 FANS/SYSTEM (EPROM VERSIONS C.ACS.09.01 (F350) AND C.ACS.09.02 (3902)
* Sys 1 Outputs are on Relay Output Board #1
Sys 2 Outputs are on Relay Output Board #2
Fan
ON *
OFF *
Fan
Wire
Relay
Stage
Fans
Conditions
Conditions
Contactor
Number
Board
DP
DP & OAT
Output*
1
1
>220 PSIG
<150 PSIG & <60°F
9M
130
15
S
2
3
>235 PSIG
<165 PSIG & <65°F
10M
131
14
Y
3
5, 7
>250 PSIG
<180 PSIG & <70°F
11M ,12M
132
10
S
4
1, 5, 7
>265 PSIG
<195 PSIG & <75°F
9M, 11M, 12M
130, 132
10, 15
5
3, 5, 7
>280 PSIG
<210 PSIG & <80°F
10M, 11M, 12M
131, 132
10, 14
1
6
1, 3, 5, 7
>290 PSIG
<220 PSIG & <85°F
9M, 10M, 11M, 12M
130, 131, 132
10, 14, 15
1
2
>220 PSIG
<150 PSIG & <60°F
15M
230
15
S
2
4
>235 PSIG
<165 PSIG & <65°F
16M
231
14
Y
3
6, 8
>250 PSIG
<180 PSIG & <70°F
17M, 18M
232
10
S
4
2, 6, 8
>265 PSIG
<195 PSIG & <75°F
15M, 17M, 18M
230, 232
10, 15
5
4, 6, 8
>280 PSIG
<210 PSIG & <80°F
16M, 17M, 18M
231, 232
10, 14
2
6
2, 4, 6, 8
>290 PSIG
<220 PSIG & <85°F
15M, 16M, 17M, 18M
230, 231, 232
10, 14, 15
Summary of Contents for MILLENNIUM YCAS0230
Page 45: ...45 YORK INTERNATIONAL FORM 201 18 NM1 102 This page intentionally left blank 7 ...
Page 70: ...70 YORK INTERNATIONAL FORM 201 18 NM1 102 Technical Data FIG 30 DETAIL B LD03285 ...
Page 166: ...166 YORK INTERNATIONAL FORM 201 18 NM1 102 ...