This message shows the Run Time logged on the sys-
tem since the last compressor start, in Days (D), Hours
(H), Minutes (M), and Seconds (S).
These four messages indicate the compressor motor
average and individual line currents in amps and as a
percentage of Full Load Amps.
This message shows the system differential oil pres-
sure at the time of the fault.
These four messages indicate the compressor suction
gas conditions or pressure, saturation temperature, ac-
tual temperature and superheat at the time of the fault.
These three messages indicate the compressor dis-
charge gas conditions of pressure, saturation tempera-
ture and actual temperature at the time of the fault.
This message gives the system oil line temperature at
the time of the fault.
This message indicates that the Liquid Injection Sole-
noid Valve on this system was either energized (On) or
de-energized (Off) at the time of the fault.
These two messages indicate the number of pairs of
condenser fans running in the forward and reverse di-
rections for this system at the time of the fault.
This message indicates that the Liquid Line Solenoid
Valve on this system was either energized (On) or de-
energized (Off) at the time of the fault.
This message indicates if the system Run Permissive (flow
switch, remote Start/Stop) was in the Run mode (On/
Closed) or Stop mode (Off/open) at the time of the fault.
YCAS 3 SYSTEM MODELS:
YCAS 3 system models are constructed in two sections.
One section contains numbers 1 and 2 refrigerant sys-
tems plus the common 3 circuit evaporator. This section
is called the Master section. The second section contains
number 3 refrigerant system and is called the
Subordinate
sec-tion. Both sections have their own
control panel, but only
the master panel is fitted with a
keypad and display.
When the History key is pressed, the following mes-
sage will appear:
To select a Safety Shutdown, press the appropriate key on
the numeric keypad then press Enter. Remember that the
most recent fault information is stored as shutdown No. 1.
Repetitively pressing the Enter key now scrolls through
the information available in the Safety Shutdown buffer.
This is divided into Common (whole chiller) Data, Mas-
ter Section Individual System Data and
Subordinate
Section
Individual System Data as follows:
S Y S
#
R U N
T I M E
1 -
3 - 4 8 - 1 7
D - H - M - S
S Y S
#
A V G
M O T O R
A M P S
7 8 %
F L A
8 8
A M P S
S Y S
#
P H A S E
L 1
7 9 %
F L A
8 9
A M P S
S Y S
#
P H A S E
L 2
8 0 %
F L A
9 0
A M P S
S Y S
#
P H A S E
L 3
7 6 %
F L A
8 6
A M P S
S Y S
#
O I L
P R E S S U R E
1 2
P S I D
S Y S
#
S U C T I O N
P R E S S
5 9
P S I G
S Y S
#
S A T
S U C T
T E M P
3 4 . 1
° F
S Y S
#
S U C T I O N
T E M P
4 4 . 1
° F
S Y S
#
S U P E R H E A T
1 0 . 0
° F
S Y S
#
D S C H
P R E S S
2 7 7
P S I G
S Y S
#
S A T
D S C H
T E M P
1 1 0 . 1
° F
S Y S
#
D I S C H A R G E
T E M P
1 8 7 . 2
° F
S Y S
#
O I L
T E M P
1 4 7 . 8
° F
S Y S
#
L I Q U I D
I N J E C T I O N
V A L V E
O F F
S Y S
#
F O R W A R D
F A N S
2
S Y S
#
R E V E R S E
F A N S
O F F
S Y S
#
R U N
P E R M I S S I V E
O N
D I S P L A Y
S A F E T Y
S H U T -
D O W N
N O . 1
( 1
T O
9 )
S Y S
#
L I Q
L I N E
O N
Summary of Contents for Millennium YCAS 310
Page 11: ...FORM 201 10 NM3 11 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS English Units LD01594 LD01593...
Page 13: ...FORM 201 10 NM3 13 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS SI Units LD01598 LD01597...
Page 21: ...FORM 201 10 NM3 21 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Page 36: ...YORK INTERNATIONAL 36 YCAS 310 380 SYSTEMS 1 AND 2 CONNECTION DIAGRAM WYE DELTA START LD02032...
Page 37: ...FORM 201 10 NM3 37 YORK INTERNATIONAL LD02033...
Page 42: ...YORK INTERNATIONAL 42 YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM WYE DELTA START LD02038...
Page 43: ...FORM 201 10 NM3 43 YORK INTERNATIONAL LD02039...
Page 48: ...YORK INTERNATIONAL 48 LD02021...
Page 54: ...YORK INTERNATIONAL 54 LD02027...