FORM 201.10-NM3
121
YORK INTERNATIONAL
PROBLEM
CAUSE
SOLUTION
Compressor Won’t Load
1. Demand not great enough.
1. No problem. Consult
Installation Manual to aid
in understanding
compressor operation.
2. Low oil pressure.
2. Check oil circuit.
Assure oil load solenoid
valve is working.
Assure that discharge
pressure is at least
50 pounds over suction.
Contact the local YORK
service representative.
3. Defective water
3. Compare the display with
temperature sensor.
a thermometer. Should be
or - 2 degrees.
Lack of Cooling Effect
1. Fouled evaporator surface.
1. Contact the local YORK
Low suction pressure
service representative.
will be observed.
2. Improper flow through the
2. Reduce flow to within
evaporator.
chiller design specs.
3. Low refrigerant charge.
3. Check subcooling and
Low suction pressure
add charge as needed.
will be noted.
“PHASE ROTATION” FAULT
1. Chiller wiring phased
1. Rewire chiller wiring.
incorrectly.
“MOTOR CURRENT
1. Incoming voltage not
1. Resolve incoming voltage
UNBALANCE”
balanced phase to phase.
imbalance.
Summary of Contents for Millennium YCAS 310
Page 11: ...FORM 201 10 NM3 11 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS English Units LD01594 LD01593...
Page 13: ...FORM 201 10 NM3 13 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS SI Units LD01598 LD01597...
Page 21: ...FORM 201 10 NM3 21 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Page 36: ...YORK INTERNATIONAL 36 YCAS 310 380 SYSTEMS 1 AND 2 CONNECTION DIAGRAM WYE DELTA START LD02032...
Page 37: ...FORM 201 10 NM3 37 YORK INTERNATIONAL LD02033...
Page 42: ...YORK INTERNATIONAL 42 YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM WYE DELTA START LD02038...
Page 43: ...FORM 201 10 NM3 43 YORK INTERNATIONAL LD02039...
Page 48: ...YORK INTERNATIONAL 48 LD02021...
Page 54: ...YORK INTERNATIONAL 54 LD02027...